3600/16
Description
II. Model Code Analysis (3300/16-XX-XX-XX-XX-XX-XX)
Take 3300/16-02-01-00-00-00-00 as an example:
3300/16: Dual-channel vibration monitor
02: Input type = Electromagnetic induction probe (standard)
01: Sensitivity = 8 V/mm (200 mV/mil, standard)
00: Frequency response = Standard (4–4000 Hz)
00: Range = 0–5 mil (0–0.127 mm)
00: Output = Standard (4–20 mA)
00: Special options = None
III. Core Parameters
1. Channels and Measurement
Number of channels: 2 independent (X/Y orthogonal or double gap)
Measurement quantity: Radial vibration (peak-to-peak), Axial clearance (DC voltage)
Input: Compatible with 3300 XL 8mm electromagnetic induction probe / Preamplifier
Sensitivity: 8 V/mm (200 mV/mil)
Linear range: 0.25–2.25 mm (8mm probe)
2. Electrical
Power supply: -24 VDC (±10%), approximately 12 mA
Frequency response: 4–4000 Hz (-3dB)
Accuracy: ±0.5 dB (vibration), ±1% (clearance)
Output: Each channel 4–20 mA (can be connected to DCS/PLC)
Alarm relay: 2 channels (warning / danger), contacts 5A @ 250 VAC
3. Mechanical
Size: 245 × 100 × 95 mm (rack-mounted)
Weight: Approximately 1.2 kg
Installation: 3300 standard rack (19", 3U)
4. Environment
Operating temperature: 0°C ~ +65°C
Storage temperature: -40°C ~ +85°C
Humidity: 5%–95% RH (no condensation)
IV. Compatibility and Accessories
Probe: 3300 XL 8mm (330101/330102)
Preamplifier: 330180 (standard), 330181 (high temperature)
Extension cable: 330130 (5m/9m)
Rack: 3300/05 or 3300/06 rack
V. Alternatives and Compatibility
Original factory replacement: 3500/40 (4 channels, more functions, direct replacement)
Compatible alternatives: 3300/16 new version (e.g. 3300/16-02-01-01-00-00-02)
Note: The old 3300/16 and 3500 racks are not compatible, and the entire cabinet needs to be upgraded
VI. Key Features
Dual-channel independent monitoring: Simultaneous measurement of X/Y vibration or double position clearance
High stability: Long-term drift ≤0.1%/year
API 670 compliance: Standard for power / petrochemical industry
LCD display: 63 segments of column chart for each channel, clearance centered indication