72301-04-04-02-01-01-15
Description
I. Model Analysis (7 Segmented Codes)
72301: 7200 Series, 4-channel vibration/ displacement monitoring card (RVXY-II type)
-04: Number of channels / Function combination (4 channels, configurable as vibration/ displacement)
-04: Range code (such as ±2 mm or ±80 mil, suitable for conventional shaft displacement)
-02: Sensitivity (7.874 V/mm = 200 mV/mil, standard eddy current probe)
-01: Output type (4–20 mA analog + relay alarm)
-01: Alarm configuration (2-level alarm: warning / danger)
-15: Hardware version / compatible rack (7200 standard rack, good compatibility)
II. Core Functions
4 independent inputs: Connect 3300XL series 5/8/11 mm eddy current probes
Monitoring parameters: Shaft vibration (peak-to-peak), shaft displacement / thrust, temperature difference, eccentricity, phase difference
Alarm protection: 2-level relays per channel (warning / danger), can be interlocked for shutdown
Signal output: 4–20 mA per channel, direct connection to DCS/PLC; supports RS-485 communication
Configuration flexibility: Set range, alarm values, filtering through 7200 rack software III. Technical Specifications
Power Supply: 24 VDC (backplane power supply, power consumption approximately 15 W)
Accuracy: ±0.5% FS, temperature drift ≤ 0.01%/℃
Frequency Response: 10 Hz~10 kHz (covering the fault frequencies of rotating machinery)
Operating Temperature: 0 ℃~+60 ℃; Storage: −40 ℃~+85 ℃
Size: Standard 7200 rack full-height card (approximately 220×120×30 mm)
Protection: Industrial-grade reinforcement, vibration-resistant (5 g), EMI-resistant
IV. Typical Applications
Electricity: Steam turbines, gas turbines, generators (shaft vibration / thrust monitoring)
Petroleum: Centrifugal compressors, large pumps, fans (shaft displacement / expansion protection)
Metallurgy: High-speed rolling mills, motors (eccentricity / vibration monitoring)
V. Installation and Wiring
Insert into the full-height slot of the 7200 rack, lock the clamping mechanism
Probe → Extension cable → Preamplifier → Module channel input end
Alarm output connected to the interlock circuit; 4–20 mA connected to the DCS analog input
Configuration: Set the range, alarm value, filtering parameters, and save as effective
VI. Maintenance Points
Daily: Observe the panel LED (power / alarm / communication)
Regularly: Tighten the terminals every 6 months, calibrate the probe gap, test the alarm
Fault: Check the power supply / probe / cable for no data; re-calibrate the gap / ground for drift; check the alarm anomaly for threshold verification