13A0076G01
Description
Model Explanation
13A: Ovation System I/O Series
0076: Function Code (16-channel digital output, QBO type)
G01: Initial Hardware Version
Basic Information
Manufacturer: Emerson Process Management
Origin: United States
Form: Standard single-slot card, supports hot swapping
Weight: Approximately 0.40 kg
Installation: Ovation I/O Backplane (universal for 13A series)
Certifications: CE, UL/CSA, Class I Div.2
Status: Active mainstream digital output spare part, commonly used in power / chemical industries Function positioning
Output 24VDC source-type signals to drive on-site relays, contactors, solenoid valves, indicator lights, etc.
16 independent outputs, with optical isolation between channels, strong anti-interference
High-side switch (Source), directly providing 24VDC to the load
Channel-level overcurrent / short-circuit protection, fault self-diagnosis and reporting
Each channel has an LED status indicator light, facilitating on-site debugging and maintenance
Suitable for conventional switch quantity control scenarios, without external relays
Core parameters
Output points: 16 channels (source type / PNP)
Output signal: 24VDC (10–30VDC wide range)
Single channel current: maximum 500mA
Total output current: maximum 4A (per card)
Isolation voltage: 1500VAC (channel - system)
Response time: <100μs (on), <150μs (off)
Protection functions: Overcurrent, short circuit, overtemperature (135°C shutdown)
Operating temperature: 0°C ~ +60°C
Power supply: Backplane 5VDC power supply; on-site 24VDC auxiliary power supply
Power consumption: approximately 4.0W
Adapting accessories
I/O backplane: Ovation 13A series backplane
Terminal unit: 1B30028G01 (16-channel DO dedicated terminal base)
Field cable: shielded twisted pair (recommended 1.0–1.5mm²)
Compatible modules: same series digital input, analog I/O cards
Typical applications
Thermal power / gas power plants: valve switch control, pump / fan start-stop, solenoid valve drive, alarm indicator light
Water treatment: dosing pump control, valve switch, liquid level / pressure alarm output
Oil and gas / chemical: emergency stop (ESD) auxiliary control, on-site solenoid valve, relay drive
Papermaking / metallurgy: motor start-stop, equipment interlock, alarm signal output
Key differences (13A0076G01 vs 1C31122G01)
13A0076G01: 16-channel transistor source-type DO (24VDC), no relay, fast response, long lifespan
1C31122G01: 16-channel relay output DO, dry contact, withstands 250VAC/5A, compatible with high-voltage loads
Get a Quote