140CRP93100C
Description
140CRP93100C
Modicon Quantum S908 RIO Head‑End Adapter (Single Coax, Conformal Coated)
1 × 75Ω Coaxial Port, Conformal Coated, 2‑Slot
English Datasheet / Instruction Manual (Full Text)
1. General Description
Manufacturer: Schneider Electric
Series: Modicon Quantum (140 Series)
Module Type: S908 RIO Head‑End Adapter (Single Coax)
Form Factor: 2 slots, hot‑swap
Coating: Conformal coated (for harsh environments)
Weight: ~0.55 kg
Application: Distributed I/O, process control, plant‑wide RIO, humid/dusty/chemical areas
2. Electrical Specifications
Backplane Voltage: 24 VDC (20 … 30 VDC)
Backplane Current: 600 mA
Power Dissipation: 3 W
Isolation: 500 VDC (coax center to ground)
Fuse Recommendation: 1 A slow‑blow
3. Communication Interface (S908 RIO)
Protocol: S908 RIO (Quantum proprietary)
Media: 75 Ω coaxial cable (RG‑6/U)
Data Rate: 1.544 Mbps (T1)
Topology: Single cable, multidrop, up to 31 drops
I/O per Drop: 64 In / 64 Out words max
Distance: Up to 3,000 m (depending on cable & drops)
Connector: BNC female
Termination: 75 Ω at both ends
4. Environmental Specifications (Coated Version Enhanced)
Operating Temperature: 0 °C … +60 °C
Storage Temperature: −40 °C … +85 °C
Relative Humidity: 5% … 95% non‑condensing
Altitude: ≤ 2,000 m
Shock/Vibration: Industrial standard
ESD: 4 kV contact / 8 kV air
EMI: 10 V/m (80–2000 MHz)
Protection Class: IP20
Coating Protection: Conformal coated – resistant to moisture, dust, chemical vapors, salt mist, and condensation.
5. Physical & Mechanical
Dimensions (W × H × D): 114 × 122 × 52 mm (2 slots)
Mounting: Any 2 consecutive slots, hot‑swap
LED Indicators (Front):
PWR (Green) – Power OK
RUN (Green) – Module operational
COM (Green Blink) – RIO network activity
ERR (Red) – Comm fault / config error / duplicate drop address
6. Wiring & Pinout (BNC)
Center: Data (RIO signal)
Shield: Ground (PE)
Termination: 75 Ω at head (CRP93100C) and last drop (CRA931/932/931C)
Shield grounding: Ground at one end only to avoid ground loops
7. Software Configuration
Unity Pro (recommended)
Concept v2.2+
Modsoft v2.32+
Add 140CRP93100C (2 slots) to I/O configuration.
Enable S908 RIO master function.
Set drop addresses: 1 … 31
Map remote I/O (%I, %Q, %MW) to Quantum memory.
Download configuration to CPU.
8. Troubleshooting
PWR OFF: Check 24 VDC backplane; reseat module.
RUN OFF: Missing/invalid config; re‑download project.
ERR ON: Wrong termination, cable short, duplicate drop address, or baud mismatch.
COM no blink: No drops on bus; check cabling/termination.
9. Certifications
CE (EN 55011, EN 61131‑2)
UL 508
CSA C22.2 No. 142
RoHS compliant
Class I Div 2 (hazardous locations)
Conformal coating certified for harsh environments
10. Ordering Information
140CRP93100: S908 RIO Head, single coax, non‑coated (standard)
140CRP93100C: S908 RIO Head, single coax, conformal coated (harsh environment)
Related Coated Drops:
140CRA93100C: RIO Drop, single coax, coated
140CRA93200C: RIO Drop, dual coax, coated
Get a Quote