1. General Description

140CRP93100 is a 2‑slot, hot‑swappable S908 RIO head‑end adapter for the Schneider Electric Modicon Quantum PLC platform. It acts as the local CPU interface (RIO Master) for the S908 remote I/O network, connecting the Quantum CPU to remote I/O drops via single 75Ω coaxial cable. It works with 140CRA93100 / 93200 remote adapters and supports up to 31 RIO drops per network.
  • Manufacturer: Schneider Electric

  • Series: Modicon Quantum (140 Series)

  • Module Type: S908 RIO Head‑End Adapter (Single Coax)

  • Form Factor: 2 slots, hot‑swap

  • Coating: Non‑coated

  • Weight: ~0.55 kg

  • Application: Distributed I/O, process control, plant‑wide RIO


2. Electrical Specifications

  • Backplane Voltage: 24 VDC (20 … 30 VDC)

  • Backplane Current: 600 mA

  • Power Dissipation: 3 W

  • Isolation: 500 VDC (coax center to ground)

  • Fuse Recommendation: 1 A slow‑blow


3. Communication Interface (S908 RIO)

  • Protocol: S908 RIO (Quantum proprietary)

  • Media: 75 Ω coaxial cable (RG‑6/U)

  • Data Rate: 1.544 Mbps (T1)

  • Topology: Single cable, multidrop, up to 31 drops

  • I/O per Drop: 64 In / 64 Out words max

  • Distance: Up to 3,000 m (depending on cable & drops)

  • Connector: BNC female

  • Termination: 75 Ω at both ends


4. Environmental Specifications

  • Operating Temperature: 0 °C … +60 °C

  • Storage Temperature: −40 °C … +85 °C

  • Relative Humidity: 5% … 95% non‑condensing

  • Altitude: ≤ 2,000 m

  • Shock/Vibration: Industrial standard

  • ESD: 4 kV contact / 8 kV air

  • EMI: 10 V/m (80–2000 MHz)

  • Protection Class: IP20


5. Physical & Mechanical

  • Dimensions (W × H × D): 114 × 122 × 52 mm (2 slots)

  • Mounting: Any 2 consecutive slots, hot‑swap

  • LED Indicators (Front):

    • PWR (Green) – Power OK

    • RUN (Green) – Module operational

    • COM (Green Blink) – RIO network activity

    • ERR (Red) – Comm fault / config error / duplicate drop address


6. Wiring & Pinout (BNC)

  • Center: Data (RIO signal)

  • Shield: Ground (PE)

  • Termination: 75 Ω at head (CRP93100) and last drop (CRA931/932)

  • Shield grounding: Ground at one end only to avoid ground loops


7. Software Configuration

Supported software:
  • Unity Pro (recommended)

  • Concept v2.2+

  • Modsoft v2.32+

Configuration steps:
  1. Add 140CRP93100 (2 slots) to I/O configuration.

  2. Enable S908 RIO master function.

  3. Set drop addresses: 1 … 31

  4. Map remote I/O (%I, %Q, %MW) to Quantum memory.

  5. Download configuration to CPU.


8. Troubleshooting

  • PWR OFF: Check 24 VDC backplane; reseat module.

  • RUN OFF: Missing/invalid config; re‑download project.

  • ERR ON: Wrong termination, cable short, duplicate drop address, or baud mismatch.

  • COM no blink: No drops on bus; check cabling/termination.


9. Certifications

  • CE (EN 55011, EN 61131‑2)

  • UL 508

  • CSA C22.2 No. 142

  • RoHS compliant

  • Class I Div 2 (hazardous locations)


10. Ordering Information

  • 140CRP93100: S908 RIO Head, single coax, non‑coated (standard)

  • 140CRP93100C: S908 RIO Head, single coax, conformal coated (harsh environment)

  • Related:

    • 140CRA93100: RIO Drop, single coax

    • 140CRA93200: RIO Drop, dual coax (redundant)