1900/65A (Model: 1900/65A-01-01-01-00-00) Brand: Bently Nevada (Bently Nevada) Product Full Name: General Purpose Equipment Monitor Position: Low-cost, multi-channel independent monitor, used for continuous protection of vibration, displacement, temperature, and speed of non-critical rotating machinery/equipment, replacing the economical solution of the traditional 3500 series.

Description

1900/65A (Model: 1900/65A-01-01-01-00-00)

Brand: Bently Nevada (Bently Nevada)

Product Full Name: General Purpose Equipment Monitor

Position: Low-cost, multi-channel independent monitor, used for continuous protection of vibration, displacement, temperature, and speed of non-critical rotating machinery/equipment, replacing the economical solution of the traditional 3500 series.

I. Model Code Analysis (1900/65A-01-01-01-00-00) Table

Section Code Explanation

1 01 Power supply: 110–220 VAC, 50/60 Hz

2 01 Display: Built-in display (no cable)

3 01 Installation: Panel-mounted

4 00 Approval: None

5 00 Communication: No Modbus


II. Core Parameters

1. Input channels (8 channels)

Vibration / Displacement / Speed × 4: Support 2/3-wire accelerometers, speed sensors, eddy current probes (shaft vibration / axial displacement)

Temperature × 4: Support E/J/K/T thermocouples, 2/3-wire RTD (PT100)

Sampling accuracy: 24-bit ADC, high resolution

2. Output

Relay × 6: Programmable (single channel / combinational logic), contact capacity: 250 VAC / 3 A (resistive), 250 VAC / 1.5 A (inductive)

4–20 mA × 4: Arbitrary channel variable transducer output, connected to DCS/PLC

Buffer output × 4: Buffer for raw sensor signals, for oscilloscope / portable meter verification

3. Electrical

Power supply: 110–220 VAC, 50/60 Hz (Model 01)

Power consumption: ≤ 25 W

Insulation: Input / Output isolated from power supply ≥ 500 VAC

4. Environment and Mechanics

Operating temperature: 0 ~ +60 °C

Storage temperature: -40 ~ +85 °C

Humidity: 5%–95% (no condensation)

Size (width × height × depth): 152 × 100 × 50 mm (panel-mounted)

Weight: Approximately 0.77 kg (main unit) + 0.4 kg (display)

III. Main Functions

Multi-parameter monitoring: Simultaneously monitor 4 channels of vibration / displacement / speed + 4 channels of temperature, covering key indicators of general equipment.

Independent alarm / danger: Each channel has independent alarm (Alert) and danger (Danger) thresholds, supports voting logic (AND/OR), 6 relays freely mapped.

Event recording: 200 historical events (timestamp, channel, status), facilitating fault traceability.

Configuration flexibility:

Software: 1900 Configuration Software (PC), Ethernet download configuration.

Local: Built-in display for viewing real-time values, status, supports simple parameter modification.

Bypass / Reset: Supports external contacts to disable alarm (Inhibit), reset alarm (Reset), threshold multiplication (Trip Multiply), suitable for startup / maintenance scenarios.

IV. Panel and Wiring

1. Front panel

LCD display: Real-time values, channel status, alarm / danger indication

Buttons: Menu/Enter/↑/↓, local operation

LED: PWR (power), RUN (operation), FLT (fault), CH1–CH8 (channel status)

2. Back panel wiring (terminal block)

Power: L/N/PE (110–220 VAC)

Sensor input: CH1–CH4 (vibration / displacement), CH5–CH8 (temperature)

Relay output: RL1–RL6 (each channel COM/NO/NC)

4–20 mA output: AO1–AO4 (+/-)

Control input: Inhibit/Reset/Trip Multiply (contacts)

Ethernet: RJ45, for configuration software connection

V. Installation and Configuration

Installation: Standard panel mounting holes (152×100 mm), fix the main unit; display and main unit integrated (Model 01).

Wiring:

Sensor: Shielded wire is grounded at one end, avoiding strong interference from the frequency converter / motor.

Relay: Strong current circuit is connected with a 3 A fuse, with NO/NC options for connecting the alarm light / stop circuit.

Configuration steps:

Connect the device to the Ethernet, and open the 1900 configuration software.

Define the channel type (vibration / temperature), range, alarm / danger threshold.

Configure the relay mapping (e.g. CH1 danger → RL1 action).

Download the configuration, and restart after power off to take effect.

Six. Common Faults

FLT red and bright: Power abnormality, configuration error, sensor short circuit / open circuit → Check power supply, re-download configuration, verify wiring.

No display of channels: Sensor failure, wiring break, range error → Replace sensor, check wiring, verify configuration.

Relay does not act: Mapping error, threshold not triggered, contact damage → Check configuration, confirm over-limit, measure contacts.