140CPU65160S
Description
140CPU65160S
Modicon Quantum Unity SAFETY PROCESSOR
(Safety & Hot-Standby Redundancy Certified)
1. General Information
Part Number: 140CPU65160S
Manufacturer: Schneider Electric
Series: Modicon Quantum (Unity Pro)
Type: 32-bit Safety Processor, Hot-Standby Redundancy capable
Suffix Meaning: S = Safety / Redundancy
Processor Core: 32-bit PowerPC RISC with FPU
Clock Frequency: 266 MHz
On-board RAM: 1024 KB (1 MB)
Coating: Non-conformal (standard industrial)
Slot Occupancy: 2 slots (wide)
Software Support: Unity Pro XL (Safety & Redundancy)
Product Status: Discontinued (EOL)
Weight: 1.43 kg
Hot-Swappable: Yes
2. Performance Specifications
Boolean Logic: 0.0525 – 0.075 µs/instruction
Word Logic: 0.09 – 0.12 µs/word
Fixed-point Arithmetic: 0.96 – 1.02 µs
Floating-point (FPU): 0.4 – 0.5 µs
Application Tasks:
1 × Cyclic Master Task
1 × Fast Periodic Task
128 × I/O Interrupt Tasks
32 × Timer Interrupt Tasks
Safety-certified task scheduling
3. Memory & Expansion
Internal RAM: 1024 KB (program + data)
PCMCIA Card (not included):
Program memory: up to 7 MB
File storage: up to 8 MB
Backup: 3 V lithium battery (≈10 years life)
Safety Memory: ECC-protected, certified for safety applications
4. I/O Capacity
Distributed Digital I/O: 8,000 In / 8,000 Out per MB+ network
Remote I/O (S908 / Quantum Ethernet RIO): 31,744 points max
Distributed Stations: 63 (Modbus Plus)
Remote Stations: 31 (per RIO bus)
Local Expansion Racks: up to 2
5. Communication Interfaces (Integrated)
1 × Modbus Plus (MB+): D-Sub 9, 1 Mbps, peer-to-peer
2 × 10/100 Mbps Ethernet (RJ45):
Modbus TCP/IP, TCP/IP, Redundancy-capable
1 × Modbus RTU (RS-232/485): D-Sub 9, ASCII/RTU
1 × USB 1.1: Programming & data logging
Expansion Slots: 6 for additional comm modules (Ethernet, Profibus, etc.)
6. Safety & Redundancy Features (Key for “S”)
Safety Certification: Certified for safety-related systems (per IEC 61508)
Redundancy: Hot-Standby Redundancy (HSBY) support
Redundant Sync Port: MT-RJ fiber for CPU-to-CPU sync
Safety Data Handling: Protected memory, safe task isolation
Redundancy Switchover: < 50 ms (typical)
7. Electrical Characteristics
Backplane Current: 2.16 A @ 5.1 VDC
Power Consumption: ~11 W
Battery Voltage: 3 V DC (lithium)
8. Environmental Ratings
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −40 °C to +85 °C
Relative Humidity: 5% – 95% RH, non-condensing
Max Altitude: 5,000 m
Shock/Vibration: Industrial standard (IEC 60068-2)
9. Certifications
CE, UL 508, CSA C22.2 No.142
FM Class 1 Div 2 (hazardous areas)
RoHS Compliant
Safety & Redundancy Certified
10. Differences vs Standard / Coated Versions
140CPU65160S: Safety + Hot-Standby, standard coating
140CPU65160: Standard, non-safety, non-redundancy
140CPU65160C: Conformal coated (harsh env), standard logic
Get a Quote