140CPS52400
Description

Schneider Electric
140CPS52400
Modicon Quantum – 5.1 VDC Backplane Power Supply
1. General Information
Manufacturer: Schneider Electric
Part Number: 140CPS52400
Series: Modicon Quantum PLC
Type: Rack‑mount backplane power supply (redundant / summable)
Input: 100–150 VDC (nominal 125 VDC)
Output: 5.1 VDC (logic power for Quantum backplane)
Application: Quantum racks with 125 VDC plant supply; large/heavy‑load racks; supports 1+1 redundancy and parallel summing (up to 2 units → 16 A)
Coating: Non‑coated (standard)
Key Trait: Redundancy capable (1+1), no alarm contact
“C” version: 140CPS52400C = conformal coated
2. Electrical Specifications
Input (DC)
Voltage: 100–150 VDC (nominal 125 VDC)
Input Current: 0.5 A @ 125 VDC
Inrush Current: 28 A max @ 125 VDC
Hold‑up Time: ≤ 1 ms @ 125 VDC
External Fuse: 2 A time‑lag (slow‑blow)
Output
Voltage: 5.1 VDC ±1% (regulated)
Current (@60°C): 0.5–8 A continuous (redundant / summable)
Redundancy: Supported (1+1 mode) (two units for full redundancy)
Total Parallel Current: Up to 16 A (2 × 8 A modules, summable only)
Ripple & Noise: < 50 mVpp typical
Protection: OVP / OLP / SCP / thermal shutdown (all internal)
Power Dissipation: 6 + (1.5 × Iout) W (Iout in A)
Efficiency: ≥ 85% typical
Signaling & Alarm
Local Indication: Green “PWR OK” LED
Alarm Contact: None (no relay output)
3. Environmental & Mechanical
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −40 °C to +85 °C
Relative Humidity: 95% RH max, non‑condensing
Altitude: Up to 5,000 m
Protection Class: IP20 (indoor use)
Mounting: 1 slot in Quantum backplane; hot‑swappable
Dimensions: 103.9 × 40.3 × 250 mm
Weight: Approx. 0.65 kg
4. Key Features
100–150 VDC wide‑range input: for 125V DC industrial systems。
8A high‑current 5.1 VDC output: for large/heavy‑load Quantum racks。
Redundant (1+1): two units for fault‑tolerant operation。
Summable (2 units max): parallel up to 16 A total。
Basic protection: OVP/OLP/SCP/thermal shutdown。
Green “PWR OK” LED: local status only (no alarm relay)。
Hot‑swappable: replace without rack shutdown。
Non‑coated (standard): for general industrial environments。
5. Certifications
CE
UL 508
CUL / CSA C22.2 No 142
FM Class 1 Div 2
RoHS compliant
6. Ordering Notes
140CPS52400: 100–150 VDC, 8 A redundant/summable, non‑coated, no alarm contact。
Compare to 140CPS52400C: 52400 = non‑coated; 52400C = conformal coated。
Compare to 140CPS51100/51100C: 52400 = 8A redundant; 51100 = 3A non‑redundant。
Compare to 140CPS2xxx/4xxx: 52400 = 125V input; 2xxx=24V; 4xxx=48V。
Get a Quote