140CPS51100C
Description

Schneider Electric
140CPS51100C
Modicon Quantum – 5.1 VDC Backplane Power Supply
1. General Information
Manufacturer: Schneider Electric
Part Number: 140CPS51100C
Series: Modicon Quantum PLC
Type: Rack‑mount backplane power supply (standalone / summable)
Input: 100–150 VDC (nominal 125 VDC)
Output: 5.1 VDC (logic power for Quantum backplane)
Application: Quantum racks with 125 VDC plant supply; small/medium racks; parallel summable (2 units max → 6 A)
Coating: Conformal coated (Humiseal 1A33) – harsh environment version
Difference vs 140CPS51100: Same electrical specs, C = coated
Key Trait: No redundancy, no alarm contact (basic 125V coated supply)
2. Electrical Specifications
Input (DC)
Voltage: 100–150 VDC (nominal 125 VDC)
Input Current: 0.4 A @ 125 VDC
Inrush Current: 10 A max
Hold‑up Time: ≤ 1 ms @ 125 VDC
External Fuse: 0.75 A time‑lag (slow‑blow)
Output
Voltage: 5.1 VDC ±1% (regulated)
Current (@60°C): 0.3–3 A continuous (standalone / summable)
Redundancy: Not supported (no 1+1 mode)
Total Parallel Current: Up to 6 A (2 × 3 A modules, summable only)
Ripple & Noise: < 50 mVpp typical
Protection: OVP / OLP / SCP / thermal shutdown (all internal)
Power Dissipation: 2 + (3 × Iout) W (Iout in A)
Efficiency: ≥ 85% typical
Signaling & Alarm
Local Indication: Green “PWR OK” LED
Alarm Contact: None (no relay output)
3. Environmental & Mechanical
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −40 °C to +85 °C
Relative Humidity: 95% RH max, non‑condensing
Altitude: Up to 5,000 m
Protection Class: IP20 (indoor use)
Mounting: 1 slot in Quantum backplane; hot‑swappable
Dimensions: 103.9 × 40.3 × 250 mm
Weight: Approx. 0.65 kg
Conformal Coating: Yes (Humiseal 1A33) – C suffix
4. Key Features
100–150 VDC wide‑range input: for 125V DC industrial systems。
3A compact 5.1 VDC output: for small/medium Quantum racks。
Summable (2 units max): parallel up to 6 A total。
Conformal coated: dust, moisture, chemical resistance (harsh environments)。
Basic protection: OVP/OLP/SCP/thermal shutdown。
Green “PWR OK” LED: local status only (no alarm relay)。
Hot‑swappable: replace without rack shutdown。
5. Certifications
CE
UL 508
CUL / CSA C22.2 No 142
FM Class 1 Div 2
RoHS compliant
6. Ordering Notes
140CPS51100C: 100–150 VDC, 3 A standalone/summable, conformal coated, no alarm contact。
Compare to 140CPS51100: 51100C = coated; 51100 = non‑coated。
Compare to 140CPS2xxx/4xxx: 51100C = 125V input; 2xxx=24V; 4xxx=48V。
Get a Quote