140CPS51100C
May 16, 2026

140CPS51100C

Schneider Electric 140CPS51100C Modicon Quantum – 5.1 VDC Backplane Power Supply (3 A Standalone / Summable, 100–150 VDC Input, Conformal Coated, No Alarm Contact)

Description

施耐德1.jpg

Schneider Electric

140CPS51100C

Modicon Quantum – 5.1 VDC Backplane Power Supply

(3 A Standalone / Summable, 100–150 VDC Input, Conformal Coated, No Alarm Contact)

1. General Information

  • Manufacturer: Schneider Electric

  • Part Number: 140CPS51100C

  • Series: Modicon Quantum PLC

  • Type: Rack‑mount backplane power supply (standalone / summable)

  • Input: 100–150 VDC (nominal 125 VDC)

  • Output: 5.1 VDC (logic power for Quantum backplane)

  • Application: Quantum racks with 125 VDC plant supply; small/medium racks; parallel summable (2 units max → 6 A)

  • Coating: Conformal coated (Humiseal 1A33) – harsh environment version

  • Difference vs 140CPS51100: Same electrical specs, C = coated

  • Key Trait: No redundancy, no alarm contact (basic 125V coated supply)


2. Electrical Specifications

Input (DC)

  • Voltage: 100–150 VDC (nominal 125 VDC)

  • Input Current: 0.4 A @ 125 VDC

  • Inrush Current: 10 A max

  • Hold‑up Time: ≤ 1 ms @ 125 VDC

  • External Fuse: 0.75 A time‑lag (slow‑blow)

Output

  • Voltage: 5.1 VDC ±1% (regulated)

  • Current (@60°C): 0.3–3 A continuous (standalone / summable)

  • Redundancy: Not supported (no 1+1 mode)

  • Total Parallel Current: Up to 6 A (2 × 3 A modules, summable only)

  • Ripple & Noise: < 50 mVpp typical

  • Protection: OVP / OLP / SCP / thermal shutdown (all internal)

  • Power Dissipation: 2 + (3 × Iout) W (Iout in A)

  • Efficiency: ≥ 85% typical

Signaling & Alarm

  • Local Indication: Green “PWR OK” LED

  • Alarm Contact: None (no relay output)


3. Environmental & Mechanical

  • Operating Temperature: 0 °C to +60 °C

  • Storage Temperature: −40 °C to +85 °C

  • Relative Humidity: 95% RH max, non‑condensing

  • Altitude: Up to 5,000 m

  • Protection Class: IP20 (indoor use)

  • Mounting: 1 slot in Quantum backplane; hot‑swappable

  • Dimensions: 103.9 × 40.3 × 250 mm

  • Weight: Approx. 0.65 kg

  • Conformal Coating: Yes (Humiseal 1A33) – C suffix


4. Key Features

  1. 100–150 VDC wide‑range input: for 125V DC industrial systems。

  2. 3A compact 5.1 VDC output: for small/medium Quantum racks。

  3. Summable (2 units max): parallel up to 6 A total。

  4. Conformal coated: dust, moisture, chemical resistance (harsh environments)。

  5. Basic protection: OVP/OLP/SCP/thermal shutdown。

  6. Green “PWR OK” LED: local status only (no alarm relay)。

  7. Hot‑swappable: replace without rack shutdown。


5. Certifications

  • CE

  • UL 508

  • CUL / CSA C22.2 No 142

  • FM Class 1 Div 2

  • RoHS compliant


6. Ordering Notes

  • 140CPS51100C: 100–150 VDC, 3 A standalone/summable, conformal coated, no alarm contact。

  • Compare to 140CPS51100: 51100C = coated; 51100 = non‑coated。

  • Compare to 140CPS2xxx/4xxx: 51100C = 125V input; 2xxx=24V; 4xxx=48V。