140CPS12400
May 16, 2026

140CPS12400

Schneider Electric 140CPS12400 Modicon Quantum – 5.1 VDC Redundant Backplane Power Supply (8 A, 115/230 VAC, Redundant Operation)

Description

施耐德14.jpg

Schneider Electric

140CPS12400

Modicon Quantum – 5.1 VDC Redundant Backplane Power Supply

(8 A, 115/230 VAC, Redundant Operation)

1. General Information

  • Manufacturer: Schneider Electric

  • Part Number: 140CPS12400

  • Series: Modicon Quantum PLC

  • Type: Rack‑mount main backplane power supply (redundant‑only model)

  • Output: 5.1 VDC (logic power for Quantum backplane)

  • Application: Supplies 5.1 VDC to CPU, I/O, and backplane logic; designed for redundant pair operation (2 units required for full power).

  • Coating: Non‑coated (standard)


2. Electrical Specifications

Input

  • Voltage: 115 / 230 VAC (dual range)

    • 93–138 VAC (115 V range)

    • 170–276 VAC (230 V range)

  • Frequency: 47–63 Hz

  • Input Current:

    • 115 VAC: 1.1 A typical

    • 230 VAC: 0.6 A typical

  • Inrush Current:

    • 115 VAC: 38 A

    • 230 VAC: 19 A

  • Fuse: 2 A slow‑blow (external)

  • Rated Power: 130 VA

Output

  • Voltage: 5.1 VDC ±1% (regulated)

  • Current (@60°C):

    • Redundant pair (2 units): 8 A continuous total

    • Standalone: Not recommended / derated

  • Power Dissipation: 6 + (1.5 × Iout) W (Iout in A)

  • Ripple & Noise: < 50 mV typical

  • Harmonic Distortion: ≤ 10% of fundamental RMS

Protection

  • Overvoltage (OVP)

  • Overload (OLP)

  • Short‑circuit (SCP)

  • Overcurrent (OCP)

  • Thermal shutdown


3. Environmental & Mechanical

  • Operating Temperature: 0 °C to +60 °C

  • Storage Temperature: −40 °C to +85 °C

  • Relative Humidity: 95% RH max, non‑condensing

  • Protection Class: IP20 (indoor use)

  • Mounting: 1 slot in Modicon Quantum backplane

  • Weight: Approx. 0.75 kg


4. Key Features

  1. 5.1 VDC redundant backplane supply for Quantum CPU & I/O logic.

  2. Universal 115/230 VAC input for global use.

  3. Designed for redundant operation: 2 units in parallel for 8 A total fault‑tolerant power.

  4. Green “PWR OK” LED status indication.

  5. Built‑in fault protection: OVP / OLP / SCP / thermal shutdown.

  6. High efficiency: ≥ 90% typical.


5. Certifications

  • CE

  • UL 508

  • CUL / CSA

  • FM Class 1 Div 2

  • RoHS compliant


6. Ordering Notes

  • 140CPS12400: 5.1 VDC, 8 A (redundant pair), non‑coated

  • Difference from 140CPS11420: This is a redundant‑optimized model (lower current, dedicated for 1+1 redundant systems).


Get a Quote