140ACO13000C
May 16, 2026

140ACO13000C

140ACO13000C Modicon Quantum 8‑Channel Isolated Analog Output Module Official English Manual (Condensed)

Description

140ACO13000C.jpg

140ACO13000C(3.jpg

140ACO13000C(2.jpg

140ACO13000C

Modicon Quantum 8‑Channel Isolated Analog Output Module

Official English Manual (Condensed)


1. General Information

  • Manufacturer: Schneider Electric

  • Model: 140ACO13000C

  • Series: Modicon Quantum 140 PLC

  • Type: 8‑channel isolated analog current output module

  • Conformal Coating: Yes (suffix C = coated for harsh environments)

  • Application: Precision control of valves, VFDs, transmitters, and process instruments in industrial automation.


2. Specifications

2.1 Output Channels & Ranges

  • Channels: 8 isolated current outputs

  • Ranges (software selectable):

    • 4–20 mA → 0…16000 counts / 0…4095 counts

    • 0–20 mA → 0…20000 counts

    • 0–25 mA → 0…25000 counts

2.2 Performance

  • Resolution: 16 bits

  • Accuracy: ±0.2% full scale @ 25°C

  • Linearity: ±4 µA typical (0–20/25 mA); ±12 µA (4–20 mA, 0…4095)

  • Temperature Drift: ±0.004% FS/°C typical; ±0.007% FS/°C max

  • Isolation: 1780 V AC for 1 minute (channels ↔ backplane bus)

  • Update Time: 5 ms

  • Settling Time:

    • 3.2 ms to ±0.1% FS

    • 1.6 ms to 5% FS

2.3 Electrical

  • External Loop Supply: 6–30 V DC

  • Max Load: 750 Ω @ 20 mA, 24 V

  • Voltage Drop: <30 V @ 25 mA

  • Backplane Current: 550 mA

  • Power Dissipation: 5 W max

2.4 Environmental

  • Operating Temp: 0°C to +60°C

  • Storage Temp: −40°C to +85°C

  • Humidity: 5–95% non‑condensing

  • Altitude: Up to 5000 m

2.5 Approvals

  • CE, UL 508, CSA C22.2, FM Class 1 Div 2


3. Features

  1. 8‑channel high density: Saves slot count compared to 4‑channel modules.

  2. Multi‑range software selection: Ranges configurable via Unity Pro / EcoStruxure Control Expert.

  3. Open‑circuit detection: Diagnoses broken 4–20 mA loops (4–20 mA range only).

  4. LED status indicators:

    • 8 × Channel ON LEDs (green)

    • 8 × Channel FAULT LEDs (red)

    • BUS ACTIVE / EXT FAULT LEDs

  5. Conformal coating (C): Protects against moisture, dust, and corrosive gases for harsh environments.

  6. High isolation: 1780 V AC isolation improves noise immunity in heavy‑duty plants.


4. Wiring Overview

  • Terminals: Removable screw terminal block.

  • RETURN: Common return for each channel group.

  • N/C: Not connected.

  • VM: Voltmeter tap (≤1 m cable length).

  • Shielding: Use twisted shielded pairs; shield ground at cabinet only.

image

5. Configuration

  • Software: Unity Pro XL / EcoStruxure Control Expert.

  • Parameters:

    • Output range selection

    • Scaling (engineering units)

    • Filtering

    • Fault response (hold / freeze / preset)


6. Compatibility

  • Platform: Modicon Quantum 140‑series backplane (single slot).

  • Compatibility note: Not compatible with Modicon X80 or M340 series.


7. Ordering Information

  • 140ACO13000: Standard (non‑coated)

  • 140ACO13000C: Conformal coated (for harsh environments)


Get a Quote