TC-301-02-2M0
May 15, 2026

TC-301-02-2M0

TC-301-02-2M0 is a TMR local expansion cable for the ICS Triplex Trusted T8000 safety system. It connects the Expander Interface Adapter (T8312) to the Expander Processor (T8310) within the same cabinet, providing high-speed, fault-tolerant communication and power for local I/O expansion chassis. Suffix 2M0 = 2 meter standard length; part of the TC-301 series for Trusted system expansion.

Description

ICS1.jpg

1. General Description

TC-301-02-2M0 is a TMR local expansion cable for the ICS Triplex Trusted T8000 safety system. It connects the Expander Interface Adapter (T8312) to the Expander Processor (T8310) within the same cabinet, providing high-speed, fault-tolerant communication and power for local I/O expansion chassis.
Suffix 2M0 = 2 meter standard length; part of the TC-301 series for Trusted system expansion.

2. Key Features

  • TMR triple-path communication + power (24 VDC)

  • Connects T8312 (adapter) ↔ T8310 (expander processor)

  • Length: 2 m (2M0); other lengths: 5M0, 10M0, 20M0

  • LS0H (Low Smoke Zero Halogen) jacket for cabinet use

  • Shielded twisted-pair for EMI/RFI immunity

  • Hot-swap safe (no system downtime during replacement)

  • SIL 3 / SIL 4 compliant per IEC 61508

  • Keyed connectors to prevent miswiring

  • Flame retardant: IEC 60332-3 Cat A


3. Electrical Specifications

  • Number of Channels: TMR (3× communication + power)

  • Power: 24 VDC, 3 A max

  • Conductor: 20 AWG stranded tinned copper

  • Insulation: XLPE, 600 V rated

  • Shielding: Foil + braid (95% coverage)

  • Isolation: 500 VDC between paths

  • Data Rate: High-speed TMR proprietary protocol

  • Current Rating: 3 A per power pair


4. Mechanical Specifications

  • Length: 2 m (6.56 ft)

  • Outer Jacket: Black LS0H, flame retardant

  • Outer Diameter: ~16 mm (0.63 in)

  • Weight: ~0.9 kg (1.98 lb)

  • Connectors:

    • T8312 end: Keyed TMR connector

    • T8310 end: Keyed TMR connector

  • Minimum Bend Radius: 12× OD (~192 mm)

  • Flex Life: >10,000 cycles (cabinet routing)


5. Environmental Specifications

  • Operating Temperature: −40 °C to +70 °C

  • Storage Temperature: −40 °C to +85 °C

  • Humidity: 5%–95% RH, non-condensing

  • Pollution Degree: PD2

  • Flame Rating: IEC 60332-3 Cat A

  • Halogen Free: Yes (LS0H)

  • Oil Resistance: IEC 60811-404


6. Safety & Approvals

  • Safety Standard: IEC 61508

  • SIL Rating: SIL 3 / SIL 4 (system-level)

  • Approvals: CE, UL, CSA, ATEX, IECEx, TÜV

  • Compliance: RoHS, REACH, LS0H


7. Compatibility

Exclusively for Trusted T8000 local expansion:
  • T8310 (Expander Processor)

  • T8312 (Expander Interface Adapter)

  • Trusted T8100 Controller Chassis

  • Trusted T8200 Expander Chassis


8. Ordering Information

  • TC-301-02-2M0: 2 m Local Expansion Cable (T8312↔T8310)

  • TC-301-02-5M0: 5 m version

  • TC-301-02-10M0: 10 m version

  • TC-301-02-20M0: 20 m version


Get a Quote