T9852
May 15, 2026

T9852

The T9852 is an 8‑channel, dual‑redundant, commoned digital output termination assembly for the AADvance T9000 Safety Instrumented System (SIS). It provides the electrical interface between the T9452 dual‑redundant digital output module and 24 VDC field devices (solenoids, relays, contactors, alarms). T9852 is the dual‑redundant (fault‑tolerant) version of T9851 (simplex), intended for SIL 3 safety loops where dual redundancy is required. It supports two independent field power supplies for maximum reliability.

Description

ICS1.jpg

1. General Description

The T9852 is an 8‑channel, dual‑redundant, commoned digital output termination assembly for the AADvance T9000 Safety Instrumented System (SIS). It provides the electrical interface between the T9452 dual‑redundant digital output module and 24 VDC field devices (solenoids, relays, contactors, alarms).
T9852 is the dual‑redundant (fault‑tolerant) version of T9851 (simplex), intended for SIL 3 safety loops where dual redundancy is required. It supports two independent field power supplies for maximum reliability.

2. Key Features

  • 8 digital output channels, dual‑redundant (fault‑tolerant)

  • Commoned output configuration (common return)

  • Designed for direct use with T9452 (8‑Ch Digital Output Module, Dual‑Redundant)

  • Output rating: 24 VDC, 0.5 A per channel (resistive load)

  • Dual independent field power supplies (2 × 10 A replaceable fuses)

  • Built‑in channel‑wise fuse protection (field fault isolation)

  • LED status indicators per channel (On / Fault)

  • EMI/RFI filtering for noise immunity

  • Screw terminals for field wiring (16 AWG max)

  • Conformal coated PCB for harsh industrial environments

  • Hot‑swap compatible (online replacement)

  • SIL 3 certified per IEC 61508 (system level)


3. Electrical Specifications

Output

  • Number of Channels: 8

  • Redundancy: Dual‑redundant (fault‑tolerant)

  • Configuration: Commoned (common return)

  • Voltage Range: 20.4–32 VDC (nominal 24 VDC)

  • Current Rating: 0.5 A per channel (resistive)

  • Maximum Total Current: 4 A (all channels ON)

  • Fusing: 500 mA fast‑blow fuse per channel; 10 A fuse per field supply

  • Leakage Current: ≤ 100 µA (OFF state)

  • On‑State Voltage Drop: ≤ 1 VDC

Isolation & Protection

  • Backplane to Field: 500 VDC isolation

  • Surge Protection: TVS diode per channel

  • EMI Filter: Low‑pass filter per channel

  • Fault Detection: Overcurrent / short‑circuit (fuse blow)

Backplane Interface

  • Supply Voltage: 18–32 VDC

  • Maximum Current: 250 mA

  • Power Dissipation: ≤ 3 W


4. Mechanical Specifications

  • Form Factor: Single‑width 6U Termination Assembly (AADvance standard)

  • Dimensions (W × H × D): 132 mm × 84 mm × 22 mm

  • Weight: Approximately 260 g (10 oz)

  • Terminals: Screw‑type (field wiring)

  • Mounting: T9300 I/O Base or T9100 System Chassis

  • Cooling: Natural convection


5. Environmental Specifications

  • Operating Temperature: −40 °C to +70 °C

  • Storage Temperature: −40 °C to +85 °C

  • Humidity: 5% to 95% RH, non‑condensing

  • Pollution Degree: PD2

  • Protection: Conformal coated PCB


6. Safety & Approvals

  • Safety Standard: IEC 61508

  • Safety Integrity Level: SIL 3 (system‑level certified)

  • Approvals: CE, UL, CSA, ATEX, IECEx, TÜV, CCC


7. Compatibility & Ordering Information

Compatible Modules

  • T9452: 8‑Channel Digital Output Module, Dual‑Redundant

  • T9300: 3‑Way I/O Base Unit

  • T9100: AADvance System Chassis

Ordering Codes

  • T9852: 8‑Ch Digital Output TA, Dual‑Redundant, Commoned

  • T9452: 8‑Ch Digital Output Module, Dual‑Redundant

  • T9300: I/O Base, 3‑Way


8. Typical Application

  • SIL 3 safety instrumented systems

  • Emergency Shutdown (ESD) critical outputs

  • Fire and Gas (F&G) alarm outputs

  • Solenoid valves, relays, and contactors

  • Critical process control outputs requiring fault tolerance


Get a Quote