The T9851 is an 8‑channel, simplex, commoned digital output termination assembly for the AADvance T9000 Safety Instrumented System (SIS). It provides the electrical interface between the T9451 digital output module and 24 VDC field devices (solenoids, relays, contactors, alarms). T9851 is the simplex (non‑redundant) version of T9852 (dual‑redundant), intended for SIL 2 safety loops where simplex architecture is acceptable.

Description

ICS10.jpg

1. General Description

The T9851 is an 8‑channel, simplex, commoned digital output termination assembly for the AADvance T9000 Safety Instrumented System (SIS). It provides the electrical interface between the T9451 digital output module and 24 VDC field devices (solenoids, relays, contactors, alarms).
T9851 is the simplex (non‑redundant) version of T9852 (dual‑redundant), intended for SIL 2 safety loops where simplex architecture is acceptable.

2. Key Features

  • 8 digital output channels, simplex (non‑redundant)

  • Commoned output configuration (common return)

  • Designed for direct use with T9451 (8‑Ch Digital Output Module, Simplex)

  • Output rating: 24 VDC, 0.5 A per channel (resistive load)

  • Built‑in channel‑wise fuse protection (field fault isolation)

  • LED status indicators per channel (On / Fault)

  • EMI/RFI filtering for noise immunity

  • Screw terminals for field wiring (16 AWG max)

  • Conformal coated PCB for harsh industrial environments

  • Hot‑swap compatible (online replacement)

  • SIL 2 certified per IEC 61508 (system level)


3. Electrical Specifications

Output

  • Number of Channels: 8

  • Redundancy: Simplex (non‑redundant)

  • Configuration: Commoned (common return)

  • Voltage Range: 20.4–32 VDC (nominal 24 VDC)

  • Current Rating: 0.5 A per channel (resistive)

  • Maximum Total Current: 4 A (all channels ON)

  • Fusing: 500 mA fast‑blow fuse per channel

  • Leakage Current: ≤ 100 µA (OFF state)

  • On‑State Voltage Drop: ≤ 1 VDC

Isolation & Protection

  • Backplane to Field: 500 VDC isolation

  • Surge Protection: TVS diode per channel

  • EMI Filter: Low‑pass filter per channel

  • Fault Detection: Overcurrent / short‑circuit (fuse blow)

Backplane Interface

  • Supply Voltage: 18–32 VDC

  • Maximum Current: 150 mA

  • Power Dissipation: ≤ 2 W


4. Mechanical Specifications

  • Form Factor: Single‑width 6U Termination Assembly (AADvance standard)

  • Dimensions (W × H × D): 132 mm × 126 mm × 22 mm

  • Weight: Approximately 0.89 kg

  • Terminals: Screw‑type (field wiring)

  • Mounting: T9300 I/O Base or T9100 System Chassis

  • Cooling: Natural convection


5. Environmental Specifications

  • Operating Temperature: −40 °C to +70 °C

  • Storage Temperature: −40 °C to +85 °C

  • Humidity: 5% to 95% RH, non‑condensing

  • Pollution Degree: PD2

  • Protection: Conformal coated PCB


6. Safety & Approvals

  • Safety Standard: IEC 61508

  • Safety Integrity Level: SIL 2 (system‑level certified)

  • Approvals: CE, UL, CSA, ATEX, IECEx, TÜV


7. Compatibility & Ordering Information

Compatible Modules

  • T9451: 8‑Channel Digital Output Module, Simplex

  • T9300: 3‑Way I/O Base Unit

  • T9100: AADvance System Chassis

Ordering Codes

  • T9851: 8‑Ch Digital Output TA, Simplex, Commoned

  • T9451: 8‑Ch Digital Output Module, Simplex

  • T9300: I/O Base, 3‑Way


8. Typical Application

  • SIL 2 safety instrumented systems

  • Emergency Shutdown (ESD) auxiliary outputs

  • Fire and Gas (F&G) alarm outputs

  • Solenoid valves, relays, and contactors

  • Non‑critical process control outputs