T9832
Description

1. Overview
2. Key Features
16 analog input channels, Dual redundant, fully isolated per channel
Dedicated for T9432 (16‑Ch 4–20 mA analog input module)
Accepts 4–20 mA field transmitters (2‑wire / 4‑wire)
Channel‑to‑channel & field‑to‑backplane isolation (reinforced)
Built‑in surge suppression (TVS diodes) and EMI/RFI filtering
Per‑channel fault detection: open circuit, short circuit, overvoltage, ground fault
Dual redundancy: single channel/module fault does not affect safety function
Screw terminals for easy field wiring (16 AWG max)
Conformal coated PCB for harsh industrial environments
Hot‑swap compatible (online replacement without system shutdown)
LED status indicators per channel (front‑panel visible)
3. Electrical Specifications
Input
Channels: 16, dual redundant, fully isolated
Signal range: 4–20 mA DC
Input impedance: 125 Ω (per channel)
Resolution: Matches T9432 (16‑bit)
Accuracy: ±0.05% FS (system level)
Transmitter supply: 18–32 VDC (from backplane, redundant)
Isolation
Field‑to‑backplane: ±1.5 kVDC, 1 minute, reinforced
Channel‑to‑channel: Isolated (no common ground)
Protection & Filtering
Surge protection: TVS diode per channel (24 VDC)
EMI filter: Low‑pass filter per channel (50 Hz/60 Hz rejection)
Fault detection: Open/short/overvoltage/ground fault
Backplane Interface
Supply: 18–32 VDC (redundant)
Max current: 450 mA
Power dissipation: ≤ 6 W (20.5 BTU/h)
4. Mechanical
Form factor: Single‑width 6U TA (AADvance standard)
Dimensions: 132 mm × 126 mm (5¼ in × 5 in)
Weight: ~360 g (13 oz)
Terminals: Screw‑type (field wiring)
Mounting: T9300 I/O base (3‑way) or T9100 chassis
Fuse access: Front‑panel (if equipped)
5. Environmental
Operating temperature: −40 °C to +70 °C
Storage temperature: −40 °C to +85 °C
Humidity: 5–95 % RH, non‑condensing
Pollution degree: PD2
Protection: Conformal coated
6. Safety & Approvals
IEC 61508 SIL 3 (system‑level, TÜV certified)
Approvals: CE, UL, CSA, ATEX, IECEx, TÜV, CCC
7. Compatibility & Ordering
Compatible Modules
T9432: 16‑Ch 4–20 mA Analog Input Module (Dual)
Ordering Information
T9832: 16‑Ch Analog Input TA, Dual, Isolated
T9432: 16‑Ch 4–20 mA Analog Input Module
T9300: 3‑Way I/O Base Unit
T9100: AADvance System Chassis
Get a Quote