T9831
May 15, 2026

T9831

The T9831 is a dedicated field termination assembly (FTA) designed for the T9431 8-channel analog input module. It provides field wiring termination, signal conditioning, overvoltage protection, noise filtering and galvanic isolation for 4–20 mA analog transmitters. It supports Simplex, Dual and TMR system configurations, suitable for ESD, F&G, BMS and process safety applications. 2. Key Features

Description

ICS1.jpg

1. Overview

The T9831 is a dedicated field termination assembly (FTA) designed for the T9431 8-channel analog input module. It provides field wiring termination, signal conditioning, overvoltage protection, noise filtering and galvanic isolation for 4–20 mA analog transmitters.
It supports Simplex, Dual and TMR system configurations, suitable for ESD, F&G, BMS and process safety applications.

2. Key Features

  • 8 analog input channels, dedicated for T9431

  • Accepts standard 4–20 mA field transmitter signals

  • Built-in surge suppression and EMI filtering

  • Per channel isolation and fault protection

  • Supports 2-wire and 4-wire transmitters

  • Suitable for Simplex / Dual / TMR redundant architecture

  • Screw terminal blocks for easy field wiring

  • Conformal coated PCB for harsh industrial environment

  • Hot-swap compatible with system powered on

3. Electrical Specifications

  • Input Signal: 4–20 mA

  • Input Impedance: 125 Ω

  • Channel Isolation: 500 VDC field to system

  • Overvoltage Protection: Built-in TVS diode per channel

  • Internal Filter: Low pass filter for industrial noise rejection

  • System Interface: Direct rear connector mate with T9431 module

4. Mechanical

  • Form Factor: Single width 6U FTA for T9100 chassis

  • Mounting: Installs at front of T9431 module

  • Termination: Screw type field terminals

  • Weight: Approx. 0.35 kg

5. Environmental

  • Operating Temperature: -40 °C to +70 °C

  • Storage Temperature: -40 °C to +85 °C

  • Humidity: 5%~95% RH non-condensing

6. Safety and Approvals

  • Compliance: IEC 61508 SIL 3 system level

  • Approvals: CE, UL, CSA, ATEX, IECEx, TÜV

7. Installation

  1. Mount T9831 onto the front of T9431 analog input module.

  2. Route shielded twisted pair cable from field transmitters to FTA terminals.

  3. Connect 2-wire or 4-wire sensors according to terminal diagram.

  4. Single point grounding recommended for cable shield.

  5. Support online replacement without system shutdown.

8. Ordering Information

  • T9831: 8CH Analog Input FTA for T9431

  • T9431: 8CH 4–20mA Analog Input Module

  • T9100: AADvance System Chassis

  • T9110: AADvance Safety Processor


Get a Quote