T9451
May 15, 2026

T9451

The T9451 is an 8‑channel isolated digital output module for the AADvance T9100 chassis. It provides 24/48 VDC, 1 A per channel outputs to drive solenoids, relays, contactors, valves, and other safety‑related actuators in ESD, F&G, and BMS applications. Key safety principle: No single‑fault can cause a stuck‑on output; the module is TMR / Dual / Simplex capable and supports hot‑swap.

Description

ICS13.jpg

1. Overview

The T9451 is an 8‑channel isolated digital output module for the AADvance T9100 chassis. It provides 24/48 VDC, 1 A per channel outputs to drive solenoids, relays, contactors, valves, and other safety‑related actuators in ESD, F&G, and BMS applications.
Key safety principle: No single‑fault can cause a stuck‑on output; the module is TMR / Dual / Simplex capable and supports hot‑swap.

2. Features

  • 8 isolated digital output channels (individually isolated)

  • Output rating: 24/48 VDC, 1 A continuous per channel

  • SIL 3 (IEC 61508) with TÜV certification

  • Redundancy: TMR, Dual, Simplex supported

  • Channel diagnostics: open/short circuit, overload, load monitoring

  • Reverse voltage protection, overcurrent & short‑circuit protection

  • Hot‑swap (online replacement)

  • Conformal coated for harsh environments

  • Dedicated FTA: T9851

  • Scan times:

    • Simplex: 1.174 ms

    • Dual: 2.202 ms


3. Electrical Specifications

Output

  • Channels: 8 (isolated)

  • Nominal voltage: 24 VDC

  • Operating range: 18–32 VDC

  • Max voltage (no damage): −1 V to +60 VDC

  • Continuous current: 1 A/channel

  • All channels max: 8 A @ 60 °C; 6 A @ 70 °C

  • Voltage drop (max): 1 VDC

  • Min current for line monitor: 10 mA/channel

Isolation

  • Channel‑to‑channel / channel‑to‑backplane: ±1.5 kVDC, 1 minute

Backplane

  • Supply: 18–32 VDC (redundant)

  • Power dissipation: 3.0 W max (10.2 BTU/h)

  • Backplane current: 165 mA max


4. Mechanical

  • Form: Single‑width 6U module (T9100 chassis)

  • Slots: Any slot 1–12; hot‑swap capable

  • Weight: ~0.34 kg (12 oz)

  • FTA: T9851 (field terminal assembly)


5. Environmental

  • Operating temperature: −40 °C to +70 °C

  • Storage: −40 °C to +85 °C

  • Humidity: 5–95 % RH, non‑condensing


6. Safety & Approvals

  • IEC 61508 SIL 3 (TÜV)

  • Approvals: CE, UL, CSA, ATEX, IECEx, TÜV


7. Front Panel LEDs

  • PWR (Green): Power OK

  • RUN (Green): Module operational

  • FAULT (Red): Module/channel fault

  • CH1–CH8: Channel status / fault indication


8. Installation & Wiring

  1. Insert into any T9100 slot (hot‑swap supported).

  2. Connect front T9851 FTA.

  3. Wire field devices (solenoids/relays) to T9851 terminals.

  4. Use shielded twisted pair for noise immunity.

  5. Configure via AADvance Workbench (logic, diagnostics, safety parameters).


9. Ordering Information

  • T9451: 8‑Channel 24 VDC Isolated Digital Output Module (SIL 3)

  • T9851: FTA for T9451

  • T9100: AADvance 6U/12‑slot chassis

  • T9110: AADvance Safety Processor


Get a Quote