T9432
May 15, 2026

T9432

T9432 is a 16‑channel isolated analog input module for the AADvance T9100 chassis. It’s the 16‑channel counterpart to the 8‑channel T9431, designed to receive 4–20 mA / 0–20 mA and voltage signals from transmitters, temperature, pressure, flow, and level sensors. Supports SIL 3 in TMR/Dual/Simplex configurations, hot‑swap, HART pass‑through, and full per‑channel diagnostics.

Description

ICS4.jpg

1. Introduction

T9432 is a 16‑channel isolated analog input module for the AADvance T9100 chassis. It’s the 16‑channel counterpart to the 8‑channel T9431, designed to receive 4–20 mA / 0–20 mA and voltage signals from transmitters, temperature, pressure, flow, and level sensors.
Supports SIL 3 in TMR/Dual/Simplex configurations, hot‑swap, HART pass‑through, and full per‑channel diagnostics.

2. Main Features

  • 16 analog input channels, individually isolated

  • Input signals: 4–20 mA (default), 0–20 mA, ±10 V, ±5 V, 0–10 V (configurable)

  • 16‑bit resolution, ±0.05% FS accuracy typical

  • Channel‑to‑backplane isolation: 500 VDC

  • HART command #03 supported (read device status)

  • Full diagnostics: open/short circuit, over/under range, line fault

  • Hot‑swap capable (online replacement)

  • Conformal coated for harsh environments

  • Dedicated FTA: T9832Rockwell Automation

  • Scan times: Simplex 1.170 ms / Dual 1.965 ms / Triple 2.656 ms

3. Technical Specifications

Electrical

  • Channels: 16 (isolated)

  • Current input: 0–24 mA (4–20 mA nominal), input resistance 125 Ω

  • Voltage input: ±10 V, ±5 V, ±2.5 V, ±1 V, 0–10 V, 0–5 V, 1–5 V

  • Resolution: 16 bit

  • Accuracy: ±0.05% FS (25 °C)

  • Isolation: 500 VDC (field ↔ logic)

  • Backplane supply: 18–32 VDC, 260 mA maxRockwell Automation

  • Power consumption: 4.0 W max

Mechanical

  • Form: Single‑width 6U module (T9100 chassis)

  • Installation: Any slot (1–12), hot‑swap

  • Matching FTA: T9832Rockwell Automation

  • Weight: ~0.34 kg

Environmental

  • Operating temperature: –40 °C to +70 °C

  • Storage temperature: –40 °C to +85 °C

  • Humidity: 5–95% RH, non‑condensing

  • Vibration/shock: AADvance industrial standard

Safety & Certification

  • Safety: IEC 61508 SIL 3 (TÜV certified)

  • Approvals: CE, UL, CSA, ATEX, IECEx, TÜV

4. Front Panel Indicators

  • PWR (Green): Power OK

  • RUN (Green): Module active

  • FAULT (Red): Module/channel fault

  • CH1–CH16: Per‑channel status (signal/fault)

5. Installation & Wiring

  1. Insert into any T9100 slot (hot‑swap supported)

  2. Connect front FTA T9832Rockwell Automation

  3. Field transmitters (4–20 mA / voltage) wire to T9832 terminals

  4. Use shielded twisted pair for analog signals

  5. Configure via AADvance Workbench (range, diagnostics, scan time)

6. Ordering Information

  • T9432: 16CH Analog Input Module (isolated, 4–20 mA / voltage)

  • T9832: Dedicated FTA for T9432Rockwell Automation

  • T9100: AADvance 6U/12‑slot chassis

  • T9110: AADvance safety processor


Get a Quote