T9100-F2
May 15, 2026

T9100-F2

The T9100‑F2 is a compact, high‑integrity TMR safety relay module for the AADvance T9000 SIS platform. It provides two independent SIL 3 rated electromechanical relay outputs for safety‑critical loads in oil & gas, power, and chemical ESD/BMS applications. It complements the AADvance T9451 processor and T9xxx I/O modules, offering 3‑2‑0 TMR fault tolerance, per‑channel diagnostics, and hot‑swap in T9100 chassis.

Description

ICS5.jpg

1. Introduction

The T9100‑F2 is a compact, high‑integrity TMR safety relay module for the AADvance T9000 SIS platform. It provides two independent SIL 3 rated electromechanical relay outputs for safety‑critical loads in oil & gas, power, and chemical ESD/BMS applications.
It complements the AADvance T9451 processor and T9xxx I/O modules, offering 3‑2‑0 TMR fault tolerance, per‑channel diagnostics, and hot‑swap in T9100 chassis.
  • Function: Dual‑channel TMR safety relay output (electromechanical, SIL 3)

  • Channels: 2 independent relay outputs (1NO / 1NC each, Form C)

  • Coil Supply: 24 VDC ±10 % (18–30 VDC)

  • Contact Rating: 5 A @ 250 VAC / 30 VDC (resistive)

  • Safety: IEC 61508 SIL 3 (TÜV), CE, UL, CSA, ATEX, IECEx

  • Architecture: 3‑2‑0 TMR, TriVote™ majority voting

  • Diagnostics: Coil fault, contact wear, open/short, TMR mismatch

  • Response Time: ≤ 5 ms (command to contact state)

  • Hot‑swap: Supported (AADvance T9100 chassis)

  • Operating Temp: –40 °C to +70 °C (conformal coated as standard)


2. Product Overview

The T9100‑F2 is a single‑width, 6U TMR safety relay module for AADvance T9100 chassis, integrating TMR voting logic with two independent, gold‑plated electromechanical relays. Each channel provides 1 NO / 1 NC contacts for safety trips, ESD valves, motor contactors, and fire/gas suppression outputs.
Key features:
  • Dual independent relays: Two isolated Form C outputs for diverse safety loads.

  • TMR voting: Three control slices ensure relay actuation only on 2‑of‑3 vote; single‑slice faults safe.

  • High‑speed response: ≤ 5 ms for critical ESD/BMS trips.

  • Comprehensive diagnostics: Coil continuity, contact state, wear estimation, TMR drift.

  • Hot‑swap: Online replacement without safety loop shutdown.

  • SIL 3 certified: Meets IEC 61508 SIL 3 for process safety.

Common applications:
  • ESD solenoid valves (24 VDC / 120/240 VAC)

  • Motor safety trip contactors

  • Fire & gas suppression triggers

  • High‑power alarm beacons/horns

  • BMS fuel valve interlocks


3. Specifications

3.1 Mechanical

  • Form Factor: T9100 chassis single‑width module, 6U

  • Dimensions (H × W × D): 266 mm × 31 mm × 220 mm

  • Weight: Approx. 0.95 kg

  • Mounting: AADvance T9100 chassis slots 1–12

  • Termination: T9850 FTA (Safety Relay FTA, screw terminals)

  • Protection: Conformal coated (standard T9100‑F2)

3.2 Electrical

  • System Supply: 18–30 VDC (nominal 24 VDC)

  • Power Consumption: ≤ 8 W (both coils energized); ≤ 3 W (de‑energized)

  • Relay Type: Electromechanical, TMR‑controlled

  • Contact Configuration: 2 × (1NO / 1NC) Form C

  • Contact Rating (Resistive):

    • 5 A @ 250 VAC

    • 5 A @ 30 VDC

  • Contact Rating (Inductive): 3 A @ 250 VAC (cos φ = 0.4)

  • Minimum Load: 50 mA @ 5 VDC (contact wear diagnostics)

  • Mechanical Endurance: ≥ 150,000 operations

  • Electrical Endurance: ≥ 75,000 operations (5 A @ 250 VAC)

  • Isolation: 2500 VAC (coil ↔ system); 1500 VAC (contacts ↔ coil)

  • Leakage Current (Off): < 0.5 mA @ 250 VAC

3.3 Functional

  • Redundancy: TMR 3‑2‑0 fault tolerance

  • Voting: TriVote™; relay energizes on 2‑of‑3 vote

  • Channel Mapping: 2 independent safety relay channels

  • Diagnostics:

    • Coil open/short detection

    • NO/NC contact mismatch monitoring

    • TMR slice mismatch & drift detection

    • Contact wear counter & estimation

    • On‑board BIST (self‑test every 30 seconds)

  • Response Time: ≤ 5 ms (command to contact state)

  • Fault Tolerance: Single‑slice or contact fault does not prevent safe trip

  • Safe State: Relays de‑energized (NO open, NC closed) on fault/power loss

3.4 Environmental

  • Operating Temperature: –40 °C to +70 °C (conformal coated)

  • Storage Temperature: –40 °C to +85 °C

  • Humidity: 5–95 % RH, non‑condensing

  • Vibration: 10–57 Hz ±0.10 mm; 57–150 Hz 1.5 g

  • Shock: 20 g, ½ sine wave, 11 ms

  • Hazardous Area: ATEX / IECEx Ex ia IIC T4 Ga (with barriers)

3.5 Safety & Certification

  • Safety Standard: IEC 61508 SIL 3 (TÜV Certified)

  • Approvals: CE, UL, CSA, ATEX, IECEx, FM

  • Fault Tolerance: TMR 3‑2‑0; single‑fault safe

  • PFHd: < 3.0 × 10⁻⁹ / hour (SIL 3)


4. Front Panel Indicators

  • PWR (Green): ON = module power healthy

  • RUN (Green): ON = active; FLASHING = BIST/init

  • FAULT (Red): ON = critical fault; FLASHING = minor fault

  • COM (Green): FLASHING = backplane communication active

  • RLY1 / RLY2 (Yellow): ON = relay energized (NO closed, NC open)


5. Installation

  • Chassis: Insert into any vacant slot in AADvance T9100 chassis

  • Hot‑Swap: Supported (T9100 SmartSlot)

  • Front‑Panel Screws: Torque 0.8–1.0 Nm

  • Termination: Connect to T9850 FTA (screw terminals for NO/NC)

  • Environmental Note: Standard T9100‑F2 is conformal coated for harsh environments


6. Wiring

  • Relay Contacts (NO/NC): To ESD valves, contactors, alarms (5 A max)

  • Contact Voltage: Up to 250 VAC / 30 VDC (resistive)

  • Coil Supply: 24 VDC from T9100 backplane (isolated)

  • Isolation: Contacts 1500 VAC isolated from coil; coil 2500 VAC from system

  • Wire Gauge: 14–18 AWG, stranded, Ex‑rated where needed

  • Safety Note: Hazardous areas use approved IS barriers between contacts and field devices


7. Ordering Information

  • T9100‑F2: Dual‑channel TMR safety relay module (–40 °C to +70 °C, coated)

  • T9850: Dedicated safety relay FTA for T9100‑F2 (screw terminals)

  • T9451: AADvance TMR processor module

  • T9100: AADvance system chassis


Get a Quote