T8480C
Description

1. Introduction
Function: 40‑channel TMR analog output (current/voltage, conformal coated)
Channels: 40 independent analog outputs, TMR‑voted per channel
Output Ranges: 4–20 mA (default), 0–20 mA, 0–10 VDC (configurable)
Accuracy: ±0.1% FS typical, ±0.25% FS max
Resolution: 12‑bit
Safety: IEC 61508 SIL 3 (TÜV), CE, UL, CSA, ATEX, IECEx
Architecture: 3‑2‑0 TMR, TriVote™ majority voting, single‑fault safe
Isolation: 2500 VDC opto‑galvanic (field ↔ system)
Diagnostics: Open/short circuit, overload, TMR mismatch, range fault
SOE: 1 ms time‑stamp resolution (output state changes/faults)
Hot‑swap: Supported (Companion Slot / SmartSlot)
Operating Temp: –40 °C to +70 °C (extended harsh range)
2. Product Overview
Conformal coated PCB and components (acrylic resin) for corrosion/moisture/dust protection
Extended operating temperature: –40 °C to +70 °C (vs 0 °C to +60 °C for T8480)
Enhanced resistance to salt mist, chemical vapors, condensation, and particulate contamination
Same TMR core, I/O performance, and safety certification as T8480
40 TMR analog outputs: 4–20 mA (default), 0–20 mA, 0–10 VDC configurable
High accuracy: ±0.1% FS typical, ±0.25% FS max; 12‑bit resolution
TMR voting: auto‑corrects single‑slice faults; no single point of failure
Per‑channel diagnostics: open/short circuit, overload, stuck fault detection
High‑speed SOE: 1 ms resolution for output changes and fault events
Hot‑swap & hot‑standby: online replacement without safety loop interruption
Wide‑range safety certification: SIL 3, ATEX/IECEx for hazardous areas (with external barriers)
3. Specifications
3.1 Mechanical
Form Factor: T8000 chassis single‑width module, 6U height
Dimensions (H × W × D): 266 mm × 31 mm × 303 mm
Weight: Approx. 1.30 kg
Mounting: T8100 / T8400 chassis slots 1–16
Termination: T8880 FTA (40‑Channel Analog Output FTA)
Protection: Conformal coated (acrylic) PCB and components
3.2 Electrical
System Supply: 20–32 VDC (nominal 24 VDC)
Power Consumption: ≤ 28 W (system)
Field Supply: Isolated, derived from system power (no external field power required)
Channels: 40, TMR‑voted per channel
Output Ranges (configurable per channel):
4–20 mA (default)
0–20 mA
0–10 VDC
Current Output (4–20 mA / 0–20 mA):
Compliance Voltage: ≥ 12 VDC @ 20 mA
Load Resistance: 0–600 Ω
Resolution: 12‑bit (≈ 4 µA step @ 4–20 mA)
Accuracy: ±0.1% FS typical, ±0.25% FS max @ 25 °C
Voltage Output (0–10 VDC):
Load Resistance: ≥ 1 kΩ
Resolution: 12‑bit (≈ 2.4 mV step @ 0–10 V)
Accuracy: ±0.1% FS typical, ±0.25% FS max @ 25 °C
Isolation: 2500 VDC opto‑galvanic (field ↔ system)
Leakage Current: < 10 µA (channel off)
Short Circuit Protection: Electronic latching, per‑channel shutdown
Update Rate: 100 ms (configurable)
3.3 Functional
Redundancy: TMR (3 slices, 3‑2‑0 fault tolerance)
Voting: TriVote™; auto‑corrects single‑slice faults
Channel Type: Dedicated analog output (software‑configurable range)
Diagnostics:
Open/short circuit detection (per channel)
Overload / overvoltage protection (per channel)
TMR mismatch & drift monitoring
Stuck output / range fault detection
On‑board BIST (self‑test interval: 5 minutes)
SOE Resolution: 1 ms (output changes, faults, trips)
Response Time: ≤ 100 ms (command to stable output)
Fault Tolerance: Single‑channel/slice fault does not affect safety function
3.4 Environmental (Enhanced for Harsh Conditions)
Operating Temperature: –40 °C to +70 °C
Storage Temperature: –40 °C to +85 °C
Humidity: 5–95 % RH, non‑condensing (coating reduces condensation risk)
Vibration: 10–57 Hz ±0.075 mm; 57–150 Hz 1.0 g
Shock: 15 g, ½ sine wave, 11 ms
Hazardous Area: ATEX / IECEx Ex ia IIC T4 Ga (with external safety barriers)
Chemical Resistance: Resists salt mist, oil vapors, and common industrial gases
3.5 Safety & Certification
Safety Standard: IEC 61508 SIL 3 (TÜV Certified)
Approvals: CE, UL, CSA, ATEX, IECEx, FM
Fault Tolerance: TMR 3‑2‑0; single‑fault safe
PFHd: < 1.0 × 10⁻⁹ / hour (SIL 3)
4. Front Panel Indicators
PWR (Green): ON = module power healthy
RUN (Green): ON = active; FLASHING = BIST/initialization
FAULT (Red): ON = critical fault; FLASHING = minor fault
COM (Green): FLASHING = backplane communication active
CH1–CH40 LEDs: Per‑channel status (ON = active; FLASH = fault)
5. Installation
Chassis: Insert into any vacant slot in T8100 / T8400 chassis
Hot‑Swap: Supported (Companion Slot / SmartSlot)
Front‑Panel Screws: Torque 0.8–1.0 Nm
Termination: Connect to T8880 FTA (standard or Ex ia with barriers)
Environmental Note: T8480C is mandatory for sites with > 85 % RH, corrosive vapors, salt mist, or temperature extremes
6. Wiring
Output Channels: To analog actuators, valve positioners, indicators (4–20 mA / 0–10 V)
Field Power: Isolated from system; no external field supply required
Isolation: Field side isolated 2500 VDC from system/backplane
Wire Gauge: 16–22 AWG, stranded, with suitable insulation for Ex areas
Safety Note: For hazardous areas, use approved intrinsic safety barriers between module and field devices
7. Ordering Information
T8480: Standard 40‑channel TMR analog output module (0 °C to +60 °C)
T8480C: Conformal coated 40‑channel TMR analog output module (–40 °C to +70 °C, harsh environments)
T8880: Dedicated 40‑channel analog output FTA for T8480 / T8480C (standard or Ex ia)
T8100 / T8400: Trusted system chassis
Get a Quote