T8472C
May 15, 2026

T8472C

The T8472C is a conformal coated, triple‑modular redundant (TMR) 16‑channel 120 VAC digital output module for the Trusted T8000 Safety Instrumented System (SIS). It is the harsh‑environment conformal coated version of T8472, designed for safety‑critical 120 VAC solenoid, relay, and contactor driving in ESD, process shutdown, and burner management systems, especially in offshore, petrochemical, high‑humidity, salt‑mist, and extreme temperature locations.

Description

ICS10.jpg

1. Introduction

The T8472C is a conformal coated, triple‑modular redundant (TMR) 16‑channel 120 VAC digital output module for the Trusted T8000 Safety Instrumented System (SIS). It is the harsh‑environment conformal coated version of T8472, designed for safety‑critical 120 VAC solenoid, relay, and contactor driving in ESD, process shutdown, and burner management systems, especially in offshore, petrochemical, high‑humidity, salt‑mist, and extreme temperature locations.
The module provides 3‑2‑0 TMR fault tolerance, per‑channel line diagnostics, 1 ms SOE, and hot‑swap capability, with full SIL 3 certification.
  • Function: 16‑channel TMR digital output (120 VAC, solenoid/contactor drive, conformal coated)

  • Channels: 16 × 120 VAC digital outputs, grouped into 2 × 8‑channel isolated power groups

  • Outputs: 90–132 VAC range, 1.0 A continuous per channel; 8 A max per power group

  • Safety: IEC 61508 SIL 3 (TÜV), CE, UL, CSA, ATEX, IECEx

  • Architecture: 3‑2‑0 TMR, TriVote™ majority voting, single‑fault safe

  • Isolation: 2500 VAC opto‑galvanic (field ↔ system); 1500 VAC reinforced (group ↔ group)

  • Diagnostics: Open/short circuit, overload, TMR mismatch, load fault

  • SOE: 1 ms time‑stamp resolution (output state changes/faults)

  • Hot‑swap: Supported (Companion Slot / SmartSlot)

  • Operating Temp: –40 °C to +70 °C (extended harsh range)


2. Product Overview

The T8472C is a single‑width, 6U TMR output module for T8100 / T8400 chassis, optimized for high‑reliability 120 VAC load driving in extreme environments. It integrates 16 dedicated digital output channels arranged into 2 electrically isolated power groups (8 channels per group), enabling independent group power control and fault containment.
Key differences from standard T8472:
  • Conformal coated PCB and components (acrylic resin) for corrosion/moisture/dust protection

  • Extended operating temperature: –40 °C to +70 °C (vs 0 °C to +60 °C for T8472)

  • Enhanced resistance to salt mist, chemical vapors, condensation, and particulate contamination

  • Same TMR core, I/O performance, and safety certification as T8472

Common features with T8472:
  • 16 TMR digital outputs: 90–132 VAC (120 VAC nominal), 1.0 A continuous, for 120 VAC solenoids/relays/contactor coils

  • 2 isolated power groups: 8 channels each, 8 A max per group, fault isolation

  • TMR voting: auto‑corrects single‑slice faults; no single point of failure

  • Per‑channel diagnostics: open/short circuit, overload, stuck on/off detection

  • High‑speed SOE: 1 ms resolution for output state changes and fault events

  • Hot‑swap & hot‑standby: online replacement without safety loop interruption

  • Wide‑range safety certification: SIL 3, ATEX/IECEx for hazardous areas (with external barriers)


3. Specifications

3.1 Mechanical

  • Form Factor: T8000 chassis single‑width module, 6U height

  • Dimensions (H × W × D): 266 mm × 31 mm × 303 mm

  • Weight: Approx. 1.40 kg

  • Mounting: T8100 / T8400 chassis slots 1–16

  • Termination: T8872 FTA (120 VAC Digital Output FTA)

  • Protection: Conformal coated (acrylic) PCB and components

3.2 Electrical

  • System Supply: 20–32 VDC (nominal 24 VDC)

  • Power Consumption: ≤ 26 W (system); ≤ 22 W (field @ 120 VAC, 1.0 A/channel)

  • Field Supply (Outputs): 90–132 VAC (nominal 120 VAC), 50/60 Hz

  • Channels: 16, grouped into 2 × 8‑channel isolated power groups

  • Output Rating: 1.0 A continuous per channel; 3.0 A peak surge

  • Group Rating: 8 A max per power group

  • Output Voltage Range: 90–132 VAC (operating); –150 to 150 VAC (withstand)

  • Isolation: 2500 VAC opto‑galvanic (field ↔ system); 1500 VAC reinforced (group ↔ group)

  • Leakage Current (Output Off): < 150 µA @ 120 VAC

  • On‑State Voltage Drop (Output): ≤ 2.0 VAC @ 1.0 A

  • Short Circuit Protection: Electronic latching, automatic per‑channel shutdown

  • Minimum On‑State Load Current: 40 mA

3.3 Functional

  • Redundancy: TMR (3 slices, 3‑2‑0 fault tolerance)

  • Voting: TriVote™; auto‑corrects single‑slice faults

  • Channel Type: Dedicated digital output (no input configuration)

  • Diagnostics:

    • Open/short circuit detection (per channel)

    • Overload / overcurrent protection (per channel/group)

    • TMR mismatch & drift monitoring

    • Stuck on/off failure detection

    • On‑board BIST (self‑test interval: 5 minutes)

  • SOE Resolution: 1 ms (output state changes, faults, trips)

  • Response Time: ≤ 0.8 ms (command to output)

  • Fault Tolerance: Single‑channel/group fault does not affect safety function

3.4 Environmental (Enhanced for Harsh Conditions)

  • Operating Temperature: –40 °C to +70 °C

  • Storage Temperature: –40 °C to +85 °C

  • Humidity: 5–95 % RH, non‑condensing (coating reduces condensation risk)

  • Vibration: 10–57 Hz ±0.075 mm; 57–150 Hz 1.0 g

  • Shock: 15 g, ½ sine wave, 11 ms

  • Hazardous Area: ATEX / IECEx Ex ia IIC T4 Ga (with external safety barriers)

  • Chemical Resistance: Resists salt mist, oil vapors, and common industrial gases

3.5 Safety & Certification

  • Safety Standard: IEC 61508 SIL 3 (TÜV Certified)

  • Approvals: CE, UL, CSA, ATEX, IECEx, FM

  • Fault Tolerance: TMR 3‑2‑0; single‑fault safe

  • PFHd: < 1.0 × 10⁻⁹ / hour (SIL 3)


4. Front Panel Indicators

  • PWR (Green): ON = module power healthy

  • RUN (Green): ON = active; FLASHING = BIST/initialization

  • FAULT (Red): ON = critical fault; FLASHING = minor fault

  • COM (Green): FLASHING = backplane communication active

  • CH1–CH16 LEDs: Per‑channel status (ON = energized/active; FLASH = fault)


5. Installation

  • Chassis: Insert into any vacant slot in T8100 / T8400 chassis

  • Hot‑Swap: Supported (Companion Slot / SmartSlot)

  • Front‑Panel Screws: Torque 0.8–1.0 Nm

  • Termination: Connect to T8872 FTA (standard or Ex ia with barriers)

  • Environmental Note: T8472C is mandatory for sites with > 85 % RH, corrosive vapors, salt mist, or temperature extremes


6. Wiring

  • Output Channels: To 120 VAC solenoid valves, relays, contactor coils (1.0 A max)

  • Field Power: 90–132 VAC / 50–60 Hz to T8872 FTA (per power group)

  • Isolation: Field side isolated 2500 VAC from system/backplane

  • Wire Gauge: 14–20 AWG, stranded, with suitable insulation for Ex areas

  • Safety Note: For hazardous areas, use approved intrinsic safety barriers between module and field devices


7. Ordering Information

  • T8472: Standard 16‑channel TMR digital output module (120 VAC, 0 °C to +60 °C)

  • T8472C: Conformal coated 16‑channel TMR digital output module (–40 °C to +70 °C, harsh environments)

  • T8872: Dedicated 120 VAC digital output FTA for T8472 / T8472C (standard or Ex ia)

  • T8100 / T8400: Trusted system chassis


Get a Quote