T8472C
Description

1. Introduction
Function: 16‑channel TMR digital output (120 VAC, solenoid/contactor drive, conformal coated)
Channels: 16 × 120 VAC digital outputs, grouped into 2 × 8‑channel isolated power groups
Outputs: 90–132 VAC range, 1.0 A continuous per channel; 8 A max per power group
Safety: IEC 61508 SIL 3 (TÜV), CE, UL, CSA, ATEX, IECEx
Architecture: 3‑2‑0 TMR, TriVote™ majority voting, single‑fault safe
Isolation: 2500 VAC opto‑galvanic (field ↔ system); 1500 VAC reinforced (group ↔ group)
Diagnostics: Open/short circuit, overload, TMR mismatch, load fault
SOE: 1 ms time‑stamp resolution (output state changes/faults)
Hot‑swap: Supported (Companion Slot / SmartSlot)
Operating Temp: –40 °C to +70 °C (extended harsh range)
2. Product Overview
Conformal coated PCB and components (acrylic resin) for corrosion/moisture/dust protection
Extended operating temperature: –40 °C to +70 °C (vs 0 °C to +60 °C for T8472)
Enhanced resistance to salt mist, chemical vapors, condensation, and particulate contamination
Same TMR core, I/O performance, and safety certification as T8472
16 TMR digital outputs: 90–132 VAC (120 VAC nominal), 1.0 A continuous, for 120 VAC solenoids/relays/contactor coils
2 isolated power groups: 8 channels each, 8 A max per group, fault isolation
TMR voting: auto‑corrects single‑slice faults; no single point of failure
Per‑channel diagnostics: open/short circuit, overload, stuck on/off detection
High‑speed SOE: 1 ms resolution for output state changes and fault events
Hot‑swap & hot‑standby: online replacement without safety loop interruption
Wide‑range safety certification: SIL 3, ATEX/IECEx for hazardous areas (with external barriers)
3. Specifications
3.1 Mechanical
Form Factor: T8000 chassis single‑width module, 6U height
Dimensions (H × W × D): 266 mm × 31 mm × 303 mm
Weight: Approx. 1.40 kg
Mounting: T8100 / T8400 chassis slots 1–16
Termination: T8872 FTA (120 VAC Digital Output FTA)
Protection: Conformal coated (acrylic) PCB and components
3.2 Electrical
System Supply: 20–32 VDC (nominal 24 VDC)
Power Consumption: ≤ 26 W (system); ≤ 22 W (field @ 120 VAC, 1.0 A/channel)
Field Supply (Outputs): 90–132 VAC (nominal 120 VAC), 50/60 Hz
Channels: 16, grouped into 2 × 8‑channel isolated power groups
Output Rating: 1.0 A continuous per channel; 3.0 A peak surge
Group Rating: 8 A max per power group
Output Voltage Range: 90–132 VAC (operating); –150 to 150 VAC (withstand)
Isolation: 2500 VAC opto‑galvanic (field ↔ system); 1500 VAC reinforced (group ↔ group)
Leakage Current (Output Off): < 150 µA @ 120 VAC
On‑State Voltage Drop (Output): ≤ 2.0 VAC @ 1.0 A
Short Circuit Protection: Electronic latching, automatic per‑channel shutdown
Minimum On‑State Load Current: 40 mA
3.3 Functional
Redundancy: TMR (3 slices, 3‑2‑0 fault tolerance)
Voting: TriVote™; auto‑corrects single‑slice faults
Channel Type: Dedicated digital output (no input configuration)
Diagnostics:
Open/short circuit detection (per channel)
Overload / overcurrent protection (per channel/group)
TMR mismatch & drift monitoring
Stuck on/off failure detection
On‑board BIST (self‑test interval: 5 minutes)
SOE Resolution: 1 ms (output state changes, faults, trips)
Response Time: ≤ 0.8 ms (command to output)
Fault Tolerance: Single‑channel/group fault does not affect safety function
3.4 Environmental (Enhanced for Harsh Conditions)
Operating Temperature: –40 °C to +70 °C
Storage Temperature: –40 °C to +85 °C
Humidity: 5–95 % RH, non‑condensing (coating reduces condensation risk)
Vibration: 10–57 Hz ±0.075 mm; 57–150 Hz 1.0 g
Shock: 15 g, ½ sine wave, 11 ms
Hazardous Area: ATEX / IECEx Ex ia IIC T4 Ga (with external safety barriers)
Chemical Resistance: Resists salt mist, oil vapors, and common industrial gases
3.5 Safety & Certification
Safety Standard: IEC 61508 SIL 3 (TÜV Certified)
Approvals: CE, UL, CSA, ATEX, IECEx, FM
Fault Tolerance: TMR 3‑2‑0; single‑fault safe
PFHd: < 1.0 × 10⁻⁹ / hour (SIL 3)
4. Front Panel Indicators
PWR (Green): ON = module power healthy
RUN (Green): ON = active; FLASHING = BIST/initialization
FAULT (Red): ON = critical fault; FLASHING = minor fault
COM (Green): FLASHING = backplane communication active
CH1–CH16 LEDs: Per‑channel status (ON = energized/active; FLASH = fault)
5. Installation
Chassis: Insert into any vacant slot in T8100 / T8400 chassis
Hot‑Swap: Supported (Companion Slot / SmartSlot)
Front‑Panel Screws: Torque 0.8–1.0 Nm
Termination: Connect to T8872 FTA (standard or Ex ia with barriers)
Environmental Note: T8472C is mandatory for sites with > 85 % RH, corrosive vapors, salt mist, or temperature extremes
6. Wiring
Output Channels: To 120 VAC solenoid valves, relays, contactor coils (1.0 A max)
Field Power: 90–132 VAC / 50–60 Hz to T8872 FTA (per power group)
Isolation: Field side isolated 2500 VAC from system/backplane
Wire Gauge: 14–20 AWG, stranded, with suitable insulation for Ex areas
Safety Note: For hazardous areas, use approved intrinsic safety barriers between module and field devices
7. Ordering Information
T8472: Standard 16‑channel TMR digital output module (120 VAC, 0 °C to +60 °C)
T8472C: Conformal coated 16‑channel TMR digital output module (–40 °C to +70 °C, harsh environments)
T8872: Dedicated 120 VAC digital output FTA for T8472 / T8472C (standard or Ex ia)
T8100 / T8400: Trusted system chassis
Get a Quote