T8471C
May 15, 2026

T8471C

The T8471C is a conformal coated, triple‑modular redundant (TMR) 32‑channel 120 VDC digital output module for the Trusted T8000 Safety Instrumented System (SIS). It is the harsh‑environment coated version of T8471, designed for safety‑critical 120 VDC solenoid, relay, and actuator loads in ESD, process shutdown, and burner management systems, especially in offshore, petrochemical, high‑humidity, salt‑mist, and extreme temperature locations。

Description

ICS11.jpg

1. Introduction

The T8471C is a conformal coated, triple‑modular redundant (TMR) 32‑channel 120 VDC digital output module for the Trusted T8000 Safety Instrumented System (SIS). It is the harsh‑environment coated version of T8471, designed for safety‑critical 120 VDC solenoid, relay, and actuator loads in ESD, process shutdown, and burner management systems, especially in offshore, petrochemical, high‑humidity, salt‑mist, and extreme temperature locations。
The module provides 3‑2‑0 TMR fault tolerance, per‑channel line diagnostics, 1 ms SOE, and hot‑swap capability, with full SIL 3 certification.
  • Function: 32‑channel TMR digital output (120 VDC, solenoid/relay drive, conformal coated)

  • Channels: 32 × 120 VDC digital outputs, grouped into 4 × 8‑channel isolated power groups

  • Outputs: 90–140 VDC range, 0.5 A continuous per channel; 4 A max per power group

  • Safety: IEC 61508 SIL 3 (TÜV), CE, UL, CSA, ATEX, IECEx

  • Architecture: 3‑2‑0 TMR, TriVote™ majority voting, single‑fault safe

  • Isolation: 2500 VDC opto‑galvanic (field ↔ system); 150 V reinforced (group ↔ group)

  • Diagnostics: Open/short circuit, overload, TMR mismatch, load fault

  • SOE: 1 ms time‑stamp resolution (output state changes/faults)

  • Hot‑swap: Supported (Companion Slot / SmartSlot)

  • Operating Temp: –40 °C to +70 °C (extended harsh range)


2. Product Overview

The T8471C is a single‑width, 6U TMR output module for T8100 / T8400 chassis, optimized for high‑reliability 120 VDC load driving in extreme environments. It integrates 32 dedicated digital output channels arranged into 4 electrically isolated power groups (8 channels per group), enabling independent group power control and fault containment。
Key differences from standard T8471:
  • Conformal coated PCB and components (acrylic resin) for corrosion/moisture/dust protection

  • Extended operating temperature: –40 °C to +70 °C (vs 0 °C to +60 °C for T8471)

  • Enhanced resistance to salt mist, chemical vapors, condensation, and particulate contamination

  • Same TMR core, I/O performance, and safety certification as T8471

Common features with T8471:
  • 32 TMR digital outputs: 90–140 VDC (120 VDC nominal), 0.5 A continuous, for 120 VDC solenoids/relays/actuators

  • 4 isolated power groups: 8 channels each, 4 A max per group, fault isolation

  • TMR voting: auto‑corrects single‑slice faults; no single point of failure

  • Per‑channel diagnostics: open/short circuit, overload, stuck on/off detection

  • High‑speed SOE: 1 ms resolution for output state changes and fault events

  • Hot‑swap & hot‑standby: online replacement without safety loop interruption

  • Wide‑range safety certification: SIL 3, ATEX/IECEx for hazardous areas (with external barriers)


3. Specifications

3.1 Mechanical

  • Form Factor: T8000 chassis single‑width module, 6U height

  • Dimensions (H × W × D): 266 mm × 31 mm × 303 mm

  • Weight: Approx. 1.35 kg

  • Mounting: T8100 / T8400 chassis slots 1–16

  • Termination: T8871 FTA (120 VDC Digital Output FTA)

  • Protection: Conformal coated (acrylic) PCB and components

3.2 Electrical

  • System Supply: 20–32 VDC (nominal 24 VDC)

  • Power Consumption: ≤ 24 W (system); ≤ 20 W (field @ 120 V, 0.5 A/channel)

  • Field Supply (Outputs): 90–140 VDC (nominal 120 VDC)

  • Channels: 32, grouped into 4 × 8‑channel isolated power groups

  • Output Rating: 0.5 A continuous per channel; 1.5 A peak surge

  • Group Rating: 4 A max per power group

  • Output Voltage Range: 90–140 VDC (operating); –1 to 150 VDC (withstand)

  • Isolation: 2500 VDC opto‑galvanic (field ↔ system); 150 V reinforced (group ↔ group)

  • Leakage Current (Output Off): < 120 µA

  • On‑State Voltage Drop (Output): ≤ 1.5 VDC @ 0.5 A

  • Short Circuit Protection: Electronic latching, automatic per‑channel shutdown

  • Minimum On‑State Load Current: 30 mA

3.3 Functional

  • Redundancy: TMR (3 slices, 3‑2‑0 fault tolerance)

  • Voting: TriVote™; auto‑corrects single‑slice faults

  • Channel Type: Dedicated digital output (no input configuration)

  • Diagnostics:

    • Open/short circuit detection (per channel)

    • Overload / overcurrent protection (per channel/group)

    • TMR mismatch & drift monitoring

    • Stuck on/off failure detection

    • On‑board BIST (self‑test interval: 5 minutes)

  • SOE Resolution: 1 ms (output state changes, faults, trips)

  • Response Time: ≤ 0.5 ms (command to output)

  • Fault Tolerance: Single‑channel/group fault does not affect safety function

3.4 Environmental (Enhanced for Harsh Conditions)

  • Operating Temperature: –40 °C to +70 °C

  • Storage Temperature: –40 °C to +85 °C

  • Humidity: 5–95 % RH, non‑condensing (coating reduces condensation risk)

  • Vibration: 10–57 Hz ±0.075 mm; 57–150 Hz 1.0 g

  • Shock: 15 g, ½ sine wave, 11 ms

  • Hazardous Area: ATEX / IECEx Ex ia IIC T4 Ga (with external safety barriers)

  • Chemical Resistance: Resists salt mist, oil vapors, and common industrial gases

3.5 Safety & Certification

  • Safety Standard: IEC 61508 SIL 3 (TÜV Certified)

  • Approvals: CE, UL, CSA, ATEX, IECEx, FM

  • Fault Tolerance: TMR 3‑2‑0; single‑fault safe

  • PFHd: < 1.0 × 10⁻⁹ / hour (SIL 3)


4. Front Panel Indicators

  • PWR (Green): ON = module power healthy

  • RUN (Green): ON = active; FLASHING = BIST/initialization

  • FAULT (Red): ON = critical fault; FLASHING = minor fault

  • COM (Green): FLASHING = backplane communication active

  • CH1–CH32 LEDs: Per‑channel status (ON = energized/active; FLASH = fault)


5. Installation

  • Chassis: Insert into any vacant slot in T8100 / T8400 chassis

  • Hot‑Swap: Supported (Companion Slot / SmartSlot)

  • Front‑Panel Screws: Torque 0.8–1.0 Nm

  • Termination: Connect to T8871 FTA (standard or Ex ia with barriers)

  • Environmental Note: T8471C is mandatory for sites with > 85 % RH, corrosive vapors, salt mist, or temperature extremes


6. Wiring

  • Output Channels: To 120 VDC solenoid valves, relays, actuators (0.5 A max)

  • Field Power: 90–140 VDC to T8871 FTA (per power group)

  • Isolation: Field side isolated 2500 VDC from system/backplane

  • Wire Gauge: 14–20 AWG, stranded, with suitable insulation for Ex areas

  • Safety Note: For hazardous areas, use approved intrinsic safety barriers between module and field devices


7. Ordering Information

  • T8471: Standard 32‑channel TMR digital output module (120 VDC, 0 °C to +60 °C)

  • T8471C: Conformal coated 32‑channel TMR digital output module (–40 °C to +70 °C, harsh environments)

  • T8871: Dedicated 120 VDC digital output FTA for T8471 / T8471C (standard or Ex ia)

  • T8100 / T8400: Trusted system chassis


Get a Quote