T8461
May 15, 2026

T8461

The T8461 is a triple‑modular redundant (TMR) 40‑channel 24/48 VDC digital output module for the Trusted T8000 Safety Instrumented System (SIS). It is designed for safety‑critical solenoid, relay, and actuator driving in ESD, process shutdown, and burner management applications, supporting both 24 VDC and 48 VDC field loads.

Description

ICS13.jpg

1. Introduction

The T8461 is a triple‑modular redundant (TMR) 40‑channel 24/48 VDC digital output module for the Trusted T8000 Safety Instrumented System (SIS). It is designed for safety‑critical solenoid, relay, and actuator driving in ESD, process shutdown, and burner management applications, supporting both 24 VDC and 48 VDC field loads.
The module provides 3‑2‑0 TMR fault tolerance, per‑channel line diagnostics, 1 ms SOE, and hot‑swap capability, with full SIL 3 certification.
  • Function: 40‑channel TMR digital output (24/48 VDC, solenoid/relay drive)

  • Channels: 40 × 24/48 VDC digital outputs, grouped into 5 × 8‑channel isolated power groups

  • Outputs: 18–60 VDC range, 0.75 A continuous per channel; 6 A max per power group

  • Safety: IEC 61508 SIL 3 (TÜV), CE, UL, CSA, ATEX, IECEx

  • Architecture: 3‑2‑0 TMR, TriVote™ majority voting, single‑fault safe

  • Isolation: 2500 VDC opto‑galvanic (field ↔ system; ch ↔ ch)

  • Diagnostics: Open/short circuit, overload, TMR mismatch, load fault

  • SOE: 1 ms time‑stamp resolution (output state changes/faults)

  • Hot‑swap: Supported (Companion Slot / SmartSlot)

  • Operating Temp: –5 °C to +60 °C (standard)


2. Product Overview

The T8461 is a single‑width, 6U TMR output module for T8100 / T8400 chassis, optimized for high‑reliability 24/48 VDC load driving in safety loops. It integrates 40 dedicated digital output channels arranged into 5 electrically isolated power groups (8 channels per group), allowing independent group power control and fault containment.
Key features:
  • 40 TMR digital outputs: 18–60 VDC (24/48 VDC nominal), 0.75 A continuous, for solenoids, relays, actuators

  • 5 isolated power groups: 8 channels each, 6 A max per group, fault isolation

  • TMR voting: auto‑corrects single‑slice faults; no single point of failure

  • Per‑channel diagnostics: open/short circuit, overload, stuck on/off detection

  • High‑speed SOE: 1 ms resolution for output state changes and fault events

  • Hot‑swap & hot‑standby: online replacement without safety loop interruption

  • Wide‑range safety certification: SIL 3, ATEX/IECEx for hazardous areas (with external barriers)


3. Specifications

3.1 Mechanical

  • Form Factor: T8000 chassis single‑width module, 6U height

  • Dimensions (H × W × D): 266 mm × 31 mm × 303 mm

  • Weight: Approx. 1.285 kg

  • Mounting: T8100 / T8400 chassis slots 1–16

  • Termination: T8861 FTA (Digital Output FTA)

  • Protection: Standard industrial coating (conformal coated version T8461C available on request)

3.2 Electrical

  • System Supply: 20–32 VDC (nominal 24 VDC)

  • Power Consumption: ≤ 22 W (system); ≤ 18 W (field @ 24 V, 0.75 A/channel)

  • Field Supply (Outputs): 18–60 VDC (nominal 24/48 VDC)

  • Channels: 40, grouped into 5 × 8‑channel isolated power groups

  • Output Rating: 0.75 A continuous per channel; 2 A peak surge

  • Group Rating: 6 A max per power group

  • Output Voltage Range: 18–60 VDC (operating); –1 to 60 VDC (withstand)

  • Isolation: 2500 VDC opto‑galvanic (field ↔ system; ch ↔ ch)

  • Leakage Current (Output Off): < 100 µA

  • On‑State Voltage Drop (Output): ≤ 1.2 VDC @ 0.75 A

  • Short Circuit Protection: Electronic latching, automatic per‑channel shutdown

  • Minimum On‑State Load Current: 25 mA

3.3 Functional

  • Redundancy: TMR (3 slices, 3‑2‑0 fault tolerance)

  • Voting: TriVote™; auto‑corrects single‑slice faults

  • Channel Type: Dedicated digital output (no input configuration)

  • Diagnostics:

    • Open/short circuit detection (per channel)

    • Overload / overcurrent protection (per channel/group)

    • TMR mismatch & drift monitoring

    • Stuck on/off failure detection

    • On‑board BIST (self‑test interval: 2 minutes)

  • SOE Resolution: 1 ms (output state changes, faults, trips)

  • Response Time: ≤ 0.5 ms (command to output)

  • Fault Tolerance: Single‑channel/group fault does not affect safety function

3.4 Environmental

  • Operating Temperature: –5 °C to +60 °C

  • Storage Temperature: –25 °C to +70 °C

  • Humidity: 5–95 % RH, non‑condensing

  • Vibration: 10–57 Hz ±0.075 mm; 57–150 Hz 1.0 g

  • Shock: 15 g, ½ sine wave, 11 ms

  • Hazardous Area: ATEX / IECEx Ex ia IIC T4 Ga (with external safety barriers)

3.5 Safety & Certification

  • Safety Standard: IEC 61508 SIL 3 (TÜV Certified)

  • Approvals: CE, UL, CSA, ATEX, IECEx, FM

  • Fault Tolerance: TMR 3‑2‑0; single‑fault safe

  • PFHd: < 1.0 × 10⁻⁹ / hour (SIL 3)


4. Front Panel Indicators

  • PWR (Green): ON = module power healthy

  • RUN (Green): ON = active; FLASHING = BIST/initialization

  • FAULT (Red): ON = critical fault; FLASHING = minor fault

  • COM (Green): FLASHING = backplane communication active

  • CH1–CH40 LEDs: Per‑channel status (ON = energized/active; FLASH = fault)


5. Installation

  • Chassis: Insert into any vacant slot in T8100 / T8400 chassis

  • Hot‑Swap: Supported (Companion Slot / SmartSlot)

  • Front‑Panel Screws: Torque 0.8–1.0 Nm

  • Termination: Connect to T8861 FTA (standard or Ex ia with barriers)

  • Environmental Note: For harsh environments, order conformal coated version T8461C


6. Wiring

  • Output Channels: To solenoid valves, relays, 24/48 VDC actuators (0.75 A max)

  • Field Power: 18–60 VDC to T8861 FTA (per power group)

  • Isolation: Field side isolated 2500 VDC from system/backplane

  • Wire Gauge: 16–22 AWG, stranded, with suitable insulation for Ex areas

  • Safety Note: For hazardous areas, use approved intrinsic safety barriers between module and field devices


7. Ordering Information

  • T8461: Standard 40‑channel TMR digital output module (24/48 VDC, –5 °C to +60 °C)

  • T8461C: Conformal coated 40‑channel TMR digital output module (extended temperature, harsh environments)

  • T8861: Dedicated digital output FTA for T8461 / T8461C (standard or Ex ia)

  • T8100 / T8400: Trusted system chassis


Get a Quote