T8240
Description

Manufacturer: ICS Triplex / Rockwell Automation
Safety Level: IEC 61508 SIL 3, TÜV certified
Architecture: TMR-compatible, N+1 redundant, current-sharing
Hot Swap: Power packs can be replaced online without system shutdown
Applications: ESD, F&G, BMS, Turbine Control, and other high-integrity safety systems
2. Product Range (from original manual)
| Catalog No. | Product Name | Description |
|---|---|---|
| T8240 | Power Shelf | 19” × 1U chassis for up to 3 power packs; includes power port + 10-way cable connector, 3 mains plugs, retaining clips |
| T8231 | Power Pack | 24 V DC, 750 W, universal AC input |
| T8232 | Power Pack | 28 V DC, 750 W, universal AC input |
| T8235 | Power Shield | Blank cover for unused slots |
| T8243 | Power Port | Plug-in diagnostic interface + 10-way cable connector |
3. Specifications
3.1 Mechanical
Form Factor: 1U (44 mm) × 19” rack width × 300 mm depth
Weight: 0.7–1.2 kg
Slots: 3 × single-width power pack slots (T8231/T8232)
Mounting: 19” rack, horizontal, front–rear airflow
Backplane: T8240 dedicated power backplane, redundant 24/28 V DC output to system I/O backplane
3.2 Electrical (Shelf Capability)
Output Voltage: 24 V DC nominal (20–32 V DC adjustable) or 28 V DC
Max Total Power: 2250 W (3 × 750 W); typical 1500 W (2 × 750 W)
Max Total Current: 90 A @ 24 V DC
Redundancy: N+1 parallel, automatic current sharing, fault isolation
Isolation: 2500 V AC (input ↔ output)
Protection: Overvoltage, undervoltage, overcurrent, short circuit, overtemperature (module-level)
3.3 Environmental
Operating Temp: –20 °C to +60 °C
Storage Temp: –40 °C to +85 °C
Humidity: 5–95 % RH (non-condensing)
Altitude: Up to 2000 m
Vibration/Shock: IEC 60068‑2‑6/27 (industrial)
Protection: IP40 (when mounted in cabinet)
4. Installation
4.1 Rack Mounting
Mount the T8240 into a standard 19” rack using 4 × M5 screws.
Ensure ≥100 mm front and rear clearance for airflow.
Connect chassis PE ground to system earth (single-point ground).
4.2 Power Pack Insertion (Hot‑Swap Enabled)
Remove the T8235 blanking plate from an empty slot.
Align the T8231/T8232 with the shelf guides and push firmly until fully seated.
Secure the front latch.
Repeat for second/third modules (2 units for standard redundancy).
Confirm PWR and OK LEDs on each power pack are steady green.
4.3 AC Wiring
Input: 110 / 240 V AC (auto‑sensing, 50/60 Hz) per power pack (IEC C14 rear connector)
Cable: 14–18 AWG stranded, 3‑conductor (L/N/PE)
Redundancy: Dual independent AC feeds recommended (separate circuits)
Ground: PE to chassis earth; field ground isolated from system ground
4.4 DC Output
The T8240 backplane automatically distributes redundant 24/28 V DC to the T8100/T8300 I/O backplane.
No user DC wiring required (internal backplane connection).
5. Front Panel Indicators (on T823x Power Packs)
PWR (Green): Steady = AC input OK; Flashing = AC input fault
OK (Green): Steady = TMR health OK; Flashing = Single internal circuit fault
FAULT (Red): On = Overvoltage / Overcurrent / Overtemperature; Flashing = Isolation fault
READY (Yellow): On = DC output active and stable
6. Operation & Redundancy
Normal Operation: 2 or 3 power packs operate in parallel current-sharing mode, load balanced.
Single Pack Fault: Faulty unit is automatically isolated; remaining packs carry 100 % load (N+1 redundancy).
Hot Swap: Replace faulty packs online; system remains operational during swap.
Diagnostics: Voltage, current, and temperature monitored continuously; faults logged to system alarm list.
7. Maintenance & Troubleshooting
7.1 Routine Maintenance
Quarterly: Inspect seating, latch tightness, LED status.
Annually: Clean with dry lint-free cloth; check AC cable torque and connections.
7.2 Common Faults
PWR LED Off: Check AC input (110/240 V AC); reseat module; check circuit breaker.
FAULT LED On: Overvoltage/overcurrent/overtemperature via diagnostics; reduce load; check for short circuits.
OK LED Flashing: Single TMR circuit fault; replace at next scheduled maintenance.
Excessive Heat: Check ambient temperature; verify airflow; clean vents.
8. Safety & Compliance
Install only in Trusted T8100/T8300 chassis environment.
Disconnect AC before wiring (except hot-swap replacement).
Use shielded AC cables; comply with IEC 61000‑6‑2/4.
Certifications: CE, UL, CSA, IEC 61508 SIL 3, TÜV certified.
9. Ordering Information
T8240: Trusted 1U Power Shelf (for up to 3 × T823x power packs)
T8231: 24 V DC, 750 W Power Pack
T8232: 28 V DC, 750 W Power Pack
T8235: Power Shield (blanking plate)
Get a Quote