ALLEN BRADLEY 1411-8SHT-601: Bulletin 1411 Solid-Core Current Transformer Product Description

Brand and Product Identification

The ALLEN BRADLEY 1411-8SHT-601 is a Bulletin 1411 current transformer from Rockwell Automation Allen-Bradley. The 1411 prefix identifies the Bulletin 1411 current transformer family, 8SHT identifies the square outer shape, solid-core, window type model, and 601 identifies the 600:5 current ratio designation. The Rockwell product description identifies the device as a current transformer with 3.25 inch inner diameter, square outer shape, 600 Amp primary to 5 Amp secondary ratio, and single-piece solid-core construction. The product lifecycle status is Active according to the Rockwell Automation product record.

Product Function and System Role

The 1411-8SHT-601 current transformer steps down a primary line current to a standardized 5 A secondary current for measurement, metering, protection or monitoring circuits. The primary conductor or busbar passes through the transformer window, while the secondary winding connects to an ammeter, power meter, relay, PowerMonitor device or other current sensing instrument. The transformer isolates the secondary measurement circuit from the high-current primary circuit and provides a low-current proportional signal. It is a current instrument transformer, not a busbar, contactor, circuit breaker, relay, current sensor output module or power meter.

Ratio and Core Specifications

Current ratio is 600 Amp primary to 5 Amp secondary. Core type is a single-piece solid-core current transformer. The module designation is 3.25 inch inner diameter with square outer shape. The solid window construction surrounds the primary conductor and does not split open for installation; the primary conductor must be routed through the window during installation. The 3.25 inch inner diameter accommodates the primary busbar or cable arrangement required for the 600 A rated application.

Application and Circuit Connection

Current transformers are used in low-voltage power distribution, motor control centers, panelboards, switchboards, feeder circuits, machine main feeds and industrial power monitoring systems. The secondary circuit connects the transformer secondary terminals to the rated burden device, such as an ammeter, wattmeter, power monitor or protection relay. The secondary winding must be connected to its burden or closed circuit before primary current is applied; an open current transformer secondary can produce dangerous voltage and should be avoided during installation or service.

Mechanical Construction

The 1411-8SHT-601 uses a solid-core square outer housing with a circular or rectangular window matching the 3.25 inch inner diameter designation. The transformer mounts near the busbar or primary conductor in the panel or control center. Primary wiring passes through the window, and secondary leads or terminals connect to the monitoring or protection device. The device is designed for fixed panel or busbar installation rather as a pluggable I/O module.

Installation and Safety Notes

Installation should follow the Allen-Bradley Bulletin 1411 product documentation, local electrical codes, panel wiring standards and instrument or relay manufacturer instructions. Verify primary conductor or busbar size fits the window, maintain proper phase and polarity on secondary leads, size secondary wiring and burden according to the transformer and instrument requirements, and ground the secondary circuit where required by code. Isolate primary power before panel work, treat the current transformer secondary as a live measurement circuit, and follow lockout and current transformer shorting procedures when servicing connected instruments.

Advantages and Selection Notes

The 1411-8SHT-601 offers a 600:5 A current ratio, solid-core construction, square outer shape, 3.25 inch inner diameter window and Bulletin 1411 compatibility with Allen-Bradley power monitoring and metering applications. When selecting a replacement, confirm current ratio, primary and secondary rating, window inner diameter, core type, burden requirement, frequency, accuracy class, mounting arrangement and connected instrument. The 1411-8SHT-601 is a current transformer, not a power meter, protection relay, busbar, circuit breaker, contactor or sensor module; its role is to proportionally reduce primary current to a 5 A secondary signal for measurement, metering or protection.