5X00119G01 8-Channel Isolated RTD Input Module for Emerson Ovation DCS
Description
1. Basic Information
Part Number: 5X00119G01
Manufacturer: Emerson Automation Solutions (Former Westinghouse)
Module Type: 8-channel isolated RTD resistance temperature detector input module
Compatible System: Ovation DCS Distributed Control System
Matching accessory: Needs personality module 5X00121G01 for combined use (except CE-certified versions)
Mounting Mode: Plug-in installation on standard Ovation I/O backplane rack
Maintenance Feature: Hot swappable, module replacement without system shutdown
Protection Grade: IP20, installed only inside indoor control cabinets
2. Complete Technical Specifications
2.1 Signal Input Parameters
Channel quantity: 8 fully independent isolated input channels
Supported RTD sensors: Pt100, Pt1000, 10Ω Copper, 120Ω Nickel and other standard thermal resistances
Wiring modes: Compatible with 2-wire, 3-wire and 4-wire RTD connection modes, automatically compensates lead wire resistance for 3-wire circuits
A/D conversion: Sigma-Delta high-resolution ADC, 14~16-bit resolution
Measurement accuracy: ≤ ±0.1% full scale at 25°C
Isolation rating: 1000V AC/DC channel-to-logic side isolation; 200V AC/DC channel-to-channel isolation, single-channel fault will not affect other channels
Sampling rate: 16.67 samples/sec (50Hz system), 20 samples/sec (60Hz system); reduced sampling rate for 3-wire compensation mode
Common-mode rejection ratio: ≥120dB, effectively suppresses on-site power frequency interference
2. Electrical Specifications
Power supply: Powered by 24VDC from DCS backplane, no external auxiliary power supply required
Power consumption: Maximum less than 5W
Each channel integrates open-circuit detection, overload and overvoltage protection circuits to prevent module burnout caused by field wiring errors
2. Environmental & Certification Indicators
Operating temperature range: 0℃ ~ +60℃
Storage temperature range: -40℃ ~ +85℃
Relative humidity: 5%–95% RH, non-condensing
Complies with IEC 61000 series EMC electromagnetic compatibility standards, shock-resistant and vibration-resistant
Obtained CE, UL, CSA international industrial safety certifications
2. Diagnosis & Maintenance Functions
Onboard LED indicators separately display module power status, communication status, internal faults and individual channel faults
Real-time full self-inspection detects sensor open circuit, signal out-of-range and loop anomalies; fault codes are uploaded to the upper controller via backplane bus for quick troubleshooting
Supports on-demand automatic calibration, reduces routine on-site calibration workload
Standard FRU field replaceable unit design, convenient disassembly and maintenance without reworking cabinet wiring layout
Get a Quote