Emerson Ovation 5A26137G13 Rack Secondary Power Distribution Module
Description
1. Module Introduction
2. Core Functional Features
(1) Multi-channel Isolated Branch Power Distribution
(2) Independent Fuse Overcurrent Protection Per Branch
(3) Real-time Electrical Parameter Sampling & Remote Upload
(4) Latched Fault, Local Indication & Remote Alarm
(5) Support Online Hot Maintenance
(6) EMI Filter Built-in for Anti-interference Performance
(7) Native System Compatibility
3. Key Technical Specifications
Mounting Mode: Standard Ovation rack plug-in installation
Input Power: DC power output from rack redundant main power supply modules
Output Form: Multiple mutually independent isolated DC power branches
Branch Protection: Individual replaceable fuse per channel, current limiting and short-circuit lockout
Monitored Items: Branch output voltage, load current, internal module temperature, fuse status
Isolation Grade: Reinforced electrical isolation between input and each output branch
Operating Ambient Temperature: 0 ℃ ~ +60 ℃
Storage & Transportation Temperature: −40 ℃ ~ +85 ℃
Relative Humidity: ≤95% RH, non-condensing
EMC Compliance: Meets industrial G3 anti-corrosion grade and anti-interference requirements for power plant control cabinets
Hot-swap Restriction: Hot plugging is only allowed when dual redundant main power supplies work normally
4. Definition of Front Panel LED Indicators
PWR IN (Green): Steady ON = normal total input power; OFF = input power loss or abnormality
BRx OK (Green): Individual branch power indicator; steady ON means normal power supply of this branch
FAULT (Red): Lights up for blown branch fuse, overload, undervoltage/overvoltage or overtemperature, with fault status latched
COMM (Green): Periodic flashing = normal communication with backplane DPU
5. Typical Application Scenarios
- Thermal Power IndustryInstalled in main control cabinets for boilers, turbines, generators and auxiliary control cabinets, implementing separate power supply protection and centralized power monitoring for DPUs and I/O modules in all rack slots.
- Petrochemical IndustryApplied in control cabinets for reactors, fractionation units and compressor sets to realize segmented power protection for each control loop, avoiding total unit control shutdown triggered by single branch failure.
- Metallurgy, Waste Incineration Power Plants & Heating StationsPerforms secondary power distribution and branch fault monitoring for automatic control cabinets, guaranteeing long-cycle unattended stable operation of the whole production line control system.