Emerson Ovation 5A26137G08 Rack Secondary Power Distribution Module
Description
2.1 Multi-channel Isolated Branch Power Distribution
2.2 Per-branch Independent Fuse Overcurrent Protection
2.3 Real-time Sampling & Remote Upload of Power Parameters
2.4 Latched Local Fault Indication & Remote Alarm Triggering
2.5 Support Online Hot-swap Maintenance
2.6 Built-in EMI Filter Anti-interference Circuit
2.7 Native System Compatibility
3. Key Technical Specifications
Mounting Mode: Standard Ovation rack plug-in installation
Input Power: DC power output from rack redundant main power supply modules
Output Mode: Multiple mutually independent isolated DC power branches
Branch Protection: Independent replaceable fuse per channel, overcurrent limiting, short-circuit lockout
Monitoring Items: Branch output voltage, load current, internal temperature, fuse status
Isolation Performance: Reinforced electrical isolation between input and each output branch
Operating Temperature: 0 ℃ ~ +60 ℃
Storage & Transportation Temperature: −40 ℃ ~ +85 ℃
Relative Humidity: ≤95% RH, non-condensing
EMC Compliance: Complies with industrial G3 anti-corrosion grade and power plant cabinet anti-interference requirements
Hot-swap Restriction: Hot plugging is only allowed when dual redundant main power supplies are in normal operating state
4. Front Panel LED Indicator Definition
PWR IN (Green): Steady ON = total input power normal; OFF = input power loss or abnormal
BRx OK (Green): Independent branch power normal indicator; steady illumination denotes normal operation
FAULT (Red): Lights up for blown branch fuse, overload, undervoltage or overtemperature; fault status latched
COMM (Green): Periodic flashing = normal data communication with backplane DPU
5. Application Scope
Thermal Power Industry
Installed in boiler, turbine, generator main control cabinets and auxiliary system cabinets, realizing partitioned power supply protection and centralized power monitoring for DPUs and all slot-mounted I/O modules inside the rack.
Petrochemical Industry
Deployed in control cabinets of reactors, fractionators and compression units, implementing segmented power protection for each control loop and avoiding full-unit control shutdown caused by single branch failure.
Metallurgy, Waste Incineration Power Plants & District Heating Stations
Undertakes secondary power distribution and branch fault monitoring for automation control cabinets, ensuring long-cycle unattended stable operation of the whole production line control system.