Emerson Ovation 5A23831G04 Analog Input (AI) Termination Base
Description
1. Overview
2. Core Functional Features
2.1 Numbered Standard Screw Terminals
2.2 Per-channel Independent Fuse Protection
2.3 Anti-vibration Mechanical Lock Structure
2.4 Backplane Bus Bridging & Isolated Power Distribution
2.5 Electronic Module Hot-swap Support
2.6 Enhanced Insulation & Surge Suppression
2.7 Excellent System Compatibility
3. Key Technical Specifications
Mounting Mode: Standard Ovation rack fixed installation, pluggable with matched AI electronic module
Wiring Terminal: Screw-type stranded cable terminals, clear unified channel number marking
Built-in Protection: Independent replaceable miniature fuse per channel, surge absorption circuit
Insulation Resistance: ≥100 MΩ (500 VDC test voltage)
Dielectric Withstand Voltage: Channel to backplane isolation withstands 1000 VAC
Working Power: DC power supplied from rack backplane and distributed to upper module
Operating Temperature: 0 ℃ ~ +60 ℃
Storage & Transport Temperature: −40 ℃ ~ +85 ℃
Relative Humidity: ≤95% RH, non-condensing
EMC Compliance: Complies with industrial G3 anti-corrosion grade and power plant cabinet anti-interference requirements
Hot-swap Rule: Single electronic module can be hot-swapped one by one under energized system; non-intrinsically safe field loops need power cut-off before plugging/unplugging
4. Front Panel LED Definition
PWR (Green): Steady ON = base power distribution normal; OFF = power loss or fuse blown
CH STATUS LED: Lights up when corresponding analog signal loop is normally connected
FAULT (Red): Illuminates on channel fuse blowout or terminal short circuit, supporting precise fault location
5. Application Scope
Thermal Power Industry
Wiring carrier for AI modules in boiler, turbine and generator control cabinets, collecting 4–20mA signals of pressure, flow, liquid level and temperature transmitters.
Petrochemical Industry
Analog signal termination for reactor, fractionator and pipeline process units, ensuring stable collection of continuous process parameters.
Metallurgy, Waste Incineration Power Plants & District Heating Stations
Centralized termination and protection of all analog measurement cables inside control cabinets, supporting long-cycle unattended stable operation of automation systems.
Get a Quote