5200D06H01 High-Temperature Special 6-Slot I/O Subrack Backplane for Common Q Class 1E Nuclear Safety DCS
Description
Parameter Specifications
Part Number: 5200D06H01
Manufacturer: Emerson Westinghouse
Compatible System: Common Q Class 1E Nuclear Safety DCS
Matching Devices
Up to 6 pcs standard 4D33xxx series I/O terminal daughter cards (AI/AO/DI/DO/RTD/TC/pulse/encoder)
Common Q redundant rack power supply: 475HP1ENA9GMT
Mainframe master control communication backplane
PCB Material: Extra thick multi-layer high-Tg high-temperature zero-halogen V-0 flame retardant FR-4 PCB, full-board high-temperature anti-oxidation & anti-mold triple conformal coating
Subrack Dimension: Standard cabinet 6U subrack, depth matching 145mm I/O daughter cards
Ambient Operating Envelope (H high-temp core advantage)
Operating Temperature: -25℃ ~ +80℃ (standard 5200D06G01 only up to +70℃)
Storage Temperature: -55℃ ~ +135℃
Humidity: 5%~98% RH, non-condensing, salt fog resistant
Power Distribution Specification
Input power: DC 12V / DC 24V dual redundant power input
Single slot rated power output: Max 30W per I/O slot
Independent slow-blow fuse per slot for overload/short-circuit isolation
Hot-swap soft-start circuit for each slot to suppress plug-in surge current
Bus & Signal Routing
Internal isolated parallel safety signal bus, isolated power bus, fault alarm bus
Each slot built-in LC EMI filter array to suppress inter-slot signal crosstalk
Gold plating thickness of slot connector: 5μm high-temperature anti-wear gold plating
Isolation & EMC Performance
Inter-slot signal isolation: 1500V AC basic isolation
Power bus dielectric withstand: 2000V AC / 60s
Power frequency interference attenuation ≥40dB, meets nuclear containment supplementary EMC screening standards
Mechanical & Seismic Reliability
Continuous vibration resistance: 8g (10–150Hz)
Shock resistance: 25g pulse, 11ms duration
Reinforced metal bracket positioning, anti-loose fixed screw structure
Core Feature
6-slot high-temperature dedicated I/O subrack backplane; full hot-swap support for all Common Q I/O daughter cards; independent single-slot fault isolation; compatible with all 4D33xxx series terminal modules; long-term stable operation under high ambient heat near nuclear primary equipment.
Certifications: CE, UL508, IEC60204-1, full NRC Class 1E nuclear safety qualification, high-temperature thermal aging screening certification
Aging Validation Standard: 144h full-load high-temperature thermal soak test + high-low temperature cyclic aging + electromagnetic stress screening
Design Service Life: ≥100,000 hours 24/7 continuous operation
Warranty Period: 12-month global unified warranty for original and factory refurbished backplanes
Application Fields
Nuclear Power Plant Common Q Safety I&C Cabinets
High-temperature 6-slot I/O subrack backplane for reactor primary equipment adjacent high-heat safety cabinets, carrying mixed configuration of AI, RTD, TC, DI, DO, pulse encoder daughter cards for primary coolant system, steam generator and containment safety parameter monitoring.
AP1000 Nuclear Post-Accident Monitoring System (PAMS)
High-temperature anti-interference I/O subrack deployed in containment peripheral high-temperature equipment rooms, carrying passive cooling system pressure/temperature/flow measurement modules and accident state digital feedback modules.
Thermal & Hydropower Seismic Power Station Main Control Cabinets
High-temperature reinforced 6-slot subrack for boiler furnace adjacent high-heat control cabinets, equipped with thermocouple, RTD and analog input modules for high-temperature flue gas and furnace wall monitoring.
High-Risk Petrochemical Explosion-Proof High-Temperature Zone Control Cabinets
High-temperature subrack backplane for reaction furnace adjacent hazardous zone cabinets, carrying high-temperature thermocouple and process analog acquisition I/O modules.
Offshore Oil & Gas Platform High-Temperature Process Cabinets
Anti-salt-fog high-temperature I/O subrack for crude high-temperature pipeline control cabinets, compatible with flow pulse, pressure analog and temperature measurement daughter cards.
Nuclear Island Emergency Backup Diesel Generator Control Cabinets
High-temperature subrack for genset exhaust high-heat adjacent cabinets, carrying exhaust thermocouple, speed encoder and safety interlock DI/DO modules.
H Suffix Special Version vs Standard 5200D06G01 Core Differences
Upper operating temperature limit increased from +70℃ to +80℃, suitable for poorly heat-dissipated cabinets near nuclear primary equipment and containment walls
Full PCB high-temperature anti-oxidation triple conformal coating, components passed extended 144h thermal soak aging screening
Slot connector upgraded to high-temperature wear-resistant gold-plated parts, no contact resistance drift under long-term high-temperature operation
Each slot power fuse and filter components adopt high-temperature resistant models, no performance degradation under wide temperature fluctuation
Added independent backplane temperature real-time monitoring circuit, upload over-temperature alarm signal to master control system
Mechanical outline, slot spacing, power/signal pin definition fully consistent with standard G version, direct drop-in replacement without cabinet modification
5200D Series Suffix Rule & Product Positioning
Suffix definition
Gxx: General industrial standard backplane (G01 basic version)
Hxx: High-temperature reinforced special backplane
Model digit meaning: 5200D06 = 6-slot standard I/O subrack backplane; other models include 5200D04 (4-slot), 5200D08 (8-slot)
Product division logic
4D33xxx series: Front-end I/O signal terminal daughter cards (AI/AO/DI/DO/Temp/Pulse/Encoder)
5200Dxxx series: Subrack backplane rack accessories, responsible for power distribution, bus interconnection and mechanical carrying of I/O daughter cards
Get a Quote