4D33945G01 Standard 16-Channel Isolated Universal Analog Input Terminal Daughter Card for Common Q Class 1E Nuclear Safety DCS
June 10, 2026

4D33945G01 Standard 16-Channel Isolated Universal Analog Input Terminal Daughter Card for Common Q Class 1E Nuclear Safety DCS

NRC Class 1E nuclear safety certified, the 4D33945G01 is a general-purpose high-density analog signal acquisition terminal daughter card developed for Emerson Westinghouse Common Q nuclear safety I&C platform. It supports on-board jumper configuration of two mainstream analog signals: 4–20mA DC loop current and 0–10V DC voltage, collecting process measurement signals from nuclear safety field transmitters including pressure, flow, liquid level, differential pressure, containment atmosphere monitoring transmitters. After galvanic isolation and high-precision signal conditioning, analog signals are converted to digital values and uploaded to master acquisition boards for safety parameter monitoring, closed-loop control calculation, over-limit interlock protection and accident data recording.

Description

Parameter Specifications

  1. Part Number: 4D33945G01

  2. Manufacturer: Emerson Westinghouse

  3. Compatible System: Common Q Class 1E Safety Instrument & Control DCS System

  4. Matching Accessories: Universal analog input master acquisition boards, 49E-3649 rack backplane, 475HP1ENA9GMT redundant rack power supply

  5. PCB Material: Multi-layer isolated V-0 flame-retardant high-Tg FR-4 substrate

  6. Dimension & Weight: 145mm × 66mm × 20.6mm; Net weight: 63g

  7. Ambient Operating Envelope

    Operating Temp: -25℃ ~ +70℃

    Storage Temp: -50℃ ~ +125℃

    Humidity: 5%–95% RH, non-condensing

  8. Power Supply: DC 12V / DC 24V dual adaptive wide-range input

  9. Input Channels: 16 fully independent galvanic isolated universal analog input channels

  10. Jumper configurable signal types

    • 4–20mA DC two-wire loop current (passive field transmitters)

    • 0–10V DC voltage signal (active voltage output transmitters)

      Measurement precision: ±0.05% FS full scale

      4–20mA max allowable loop resistance: 750Ω

      0–10V minimum load impedance: ≥10kΩ

  11. Isolation Performance

    Channel-to-backplane isolation: 1500V AC

    Dielectric withstand: 2000V AC / 60s

    Insulation resistance: ≥1200MΩ @ 500VDC

  12. EMC Anti-interference Performance

    Power frequency interference attenuation ≥40dB, fully compliant with IEC 61000-6-2 industrial EMC standard

  13. Protection & Intelligent Diagnosis Functions

    Per-channel precise constant current limiting protection

    Bidirectional TVS high-energy surge absorption circuit

    Reverse wiring polarity lockout anti-damage protection

    Real-time full fault detection: analog loop open-circuit, short-circuit, signal over-range, abnormal load impedance, transmitter power loss

    Time-stamped fault status + channel number + signal type identification uploaded to master controller

  14. Mechanical Reliability

    Continuous vibration resistance: 8g (10–150Hz)

    Shock resistance: 25g pulse, duration 11ms

  15. Core Feature: Single module hot swappable under energized rack without interrupting safety analog parameter monitoring loops

  16. Certifications: CE, UL508, IEC60204-1, NRC Class 1E nuclear safety qualification

  17. Aging Validation Standard: 72-hour full-load high-low temperature cyclic aging test + multi-point analog precision calibration screening

  18. Design Service Life: ≥100,000 hours of 24/7 unattended continuous operation

  19. Warranty Period: 12-month global unified warranty for original factory modules and certified factory refurbished modules

Application Fields

  1. Nuclear Power Plant Common Q Safety I&C Racks

    Universal multi-point analog acquisition terminal for reactor auxiliary safety cabinets, centralized collection of primary coolant pressure/flow transmitters, containment differential pressure, liquid level and radiation monitoring analog signals.

  2. AP1000 Nuclear Post-Accident Monitoring System (PAMS)

    Isolated multi-channel universal analog input board for containment passive cooling medium pressure/flow sensors, containment atmosphere pressure/humidity transmitters and post-accident safety parameter measuring points.

  3. Thermal & Hydropower Station Main Control Systems

    High-density universal analog input module for boiler water level, steam pressure, feedwater flow and furnace differential pressure process transmitters.

  4. High-Risk Explosion-Proof Petrochemical DCS Distributed Control System

    Universal analog wiring terminal card for reactor medium pressure, storage tank liquid level and pipeline flow transmitters in hazardous explosion zones.

  5. Offshore Oil & Gas Explosion-Proof Automation Racks

    Isolation analog acquisition interface for wellhead manifold pressure, separator liquid level and crude pipeline flow analog transmitters.

  6. Large Diesel Generator Safety Sequential Control Cabinets

    Multi-point analog input subcard for genset lube oil pressure, cooling water temperature/flow and exhaust backpressure transmitters.

  7. Municipal Large-Scale Water Treatment Safety Interlock DCS Systems

    Universal isolation analog terminal for pipeline flow, tank liquid level and disinfection reagent concentration monitoring transmitters.

  8. Metallurgy & Cement Kiln Production Lines

    Dedicated analog acquisition module for kiln gas pressure, raw material feeding flow and cooling water pressure analog probes.

Series Unified Iteration Rule (Consistent with full Common Q I/O board product line)

  • G01: Standard basic industrial version, 1500V isolation, 40dB EMI attenuation, basic loop fault alarm, no waveform storage

  • G02: Reinforced industrial enhanced version, 1800V isolation, 45dB attenuation, optimized signal drift fast diagnosis

  • G03: Gen3 nuclear high-isolation grade, 2000V isolation, 50dB attenuation, fault waveform capture + non-volatile historical fault storage

  • G04: Gen4 flagship ultra-high isolation, 2200V isolation, 55dB attenuation, nanosecond high-precision timestamp, expanded operating temperature range

  • G05: Gen5 premium seismic qualified grade, 2500V isolation, 60dB attenuation, anti-loose locking terminal structure, full IEEE 344 seismic certification, extended service life & warranty

  • G06: Gen6 extreme super-isolation flagship, 3000V isolation, 65dB attenuation, nuclear anti-radiation component screening, double anti-loose terminals, 15-year power-off fault data retention, full seismic & radiation dual certification

Product Positioning Distinction

  • 4D33888 series: Mixed DI/AI/RTD multi-function universal card

  • 4D33945 series: Pure analog dedicated card (4–20mA / 0–10V), higher analog sampling precision and channel density than mixed-signal boards

  • 4D33913 series: Analog output AO regulating drive card