4D33942G01 Standard 12-Channel Isolated Thermocouple Temperature Input Terminal Daughter Card for Common Q Class 1E Nuclear Safety DCS
June 10, 2026

4D33942G01 Standard 12-Channel Isolated Thermocouple Temperature Input Terminal Daughter Card for Common Q Class 1E Nuclear Safety DCS

NRC Class 1E nuclear safety certified, the 4D33942G01 is a dedicated high-precision thermocouple temperature acquisition terminal daughter card for Emerson Westinghouse Common Q nuclear safety I&C platform, designed for high-temperature equipment thermal monitoring in nuclear safety systems. It supports K, S, B, E, J, T-type thermocouple signals from reactor steam pipelines, containment exhaust flues, boiler furnace walls, auxiliary heater surfaces and high-temperature process equipment, converts thermoelectric potential difference into standardized digital temperature data and uploads to master acquisition boards for high-temperature equipment over-temperature trip interlock, thermal state trend monitoring and post-accident high-temperature sequence recording.

Description

Parameter Specifications

  1. Part Number: 4D33942G01

  2. Manufacturer: Emerson Westinghouse

  3. Compatible System: Common Q Class 1E Safety Instrument & Control DCS System

  4. Matching Accessories: Thermocouple master acquisition boards, 49E-3649 rack backplane, 475HP1ENA9GMT redundant rack power supply

  5. PCB Material: Multi-layer isolated V-0 flame-retardant high-Tg FR-4 substrate

  6. Dimension & Weight: 145mm × 66mm × 20.6mm; Net weight: 62g

  7. Ambient Operating Envelope

    Operating Temp: -25℃ ~ +70℃

    Storage Temp: -50℃ ~ +125℃

    Humidity: 5%–95% RH, non-condensing

  8. Power Supply: DC 12V / DC 24V dual adaptive wide-range input

  9. Input Channels: 12 fully independent galvanic isolated thermocouple input channels

  10. Supported Thermocouple Types & Range

    • K-type: -200 ~ +1300℃

    • S/B-type: 0 ~ +1700℃ (nuclear high-temperature containment flue dedicated)

    • E/J/T-type: -200 ~ +800℃

      Measurement precision: ±0.1℃ full span

      Built-in on-board cold junction compensation, compensation precision ±0.2℃

  11. Isolation Performance

    Channel-to-backplane isolation: 1500V AC

    Dielectric withstand: 2000V AC / 60s

    Insulation resistance: ≥1200MΩ @ 500VDC

  12. EMC Anti-interference Performance

    Power frequency interference attenuation ≥40dB, fully compliant with IEC 61000-6-2 industrial EMC standard

  13. Protection & Intelligent Diagnosis Functions

    Per-channel microvolt signal overcurrent limiting protection

    Bidirectional TVS high-energy surge absorption circuit

    Reverse wiring polarity lockout anti-damage protection

    Real-time full fault detection: thermocouple wire open-circuit, short-circuit, cold junction abnormal, signal potential drift, sensor aging failure

    Time-stamped fault status + channel number + thermocouple type identification uploaded to master controller

  14. Mechanical Reliability

    Continuous vibration resistance: 8g (10–150Hz)

    Shock resistance: 25g pulse, duration 11ms

  15. Core Feature: Single module hot swappable under energized rack without interrupting safety high-temperature equipment temperature monitoring loops

  16. Certifications: CE, UL508, IEC60204-1, NRC Class 1E nuclear safety qualification

  17. Aging Validation Standard: 72-hour full-load high-low temperature cyclic aging test + multi-point thermocouple precision calibration screening

  18. Design Service Life: ≥100,000 hours of 24/7 unattended continuous operation

  19. Warranty Period: 12-month global unified warranty for original factory modules and certified factory refurbished modules

Application Fields

  1. Nuclear Power Plant Common Q Safety I&C Racks

    Dedicated high-temperature multi-point thermocouple acquisition terminal for reactor auxiliary safety cabinets, centralized collection of main steam pipeline S/B-type thermocouples, containment exhaust flue K-type temperature signals and steam generator high-temperature wall measuring points.

  2. AP1000 Nuclear Post-Accident Monitoring System (PAMS)

    Isolated multi-channel thermocouple input board for containment passive cooling high-temperature pipeline sensors, containment atmosphere high-temperature measuring points and post-accident core auxiliary equipment over-temperature monitoring.

  3. Thermal & Hydropower Station Main Control Systems

    High-density dedicated thermocouple module for boiler furnace wall temperature, superheater pipeline temperature, turbine exhaust gas high-temperature measuring points.

  4. High-Risk Explosion-Proof Petrochemical DCS Distributed Control System

    Special high-temperature wiring terminal card for reactor furnace wall thermocouples, high-temperature reaction pipeline temperature sensors and heating furnace flue measuring points in hazardous zones.

  5. Offshore Oil & Gas Explosion-Proof Automation Racks

    Isolation thermocouple acquisition interface for crude oil high-temperature pipeline probes, separator heating furnace wall thermocouples and marine platform waste flue temperature measuring points.

  6. Large Diesel Generator Safety Sequential Control Cabinets

    Multi-point thermocouple input subcard for genset cylinder exhaust temperature, exhaust manifold high-temperature and waste heat recovery pipeline temperature sensors.

  7. Municipal Large-Scale Water Treatment Safety Interlock DCS Systems

    High-precision isolation thermocouple terminal for waste incineration furnace wall temperature, heat exchange high-temperature pipeline measuring points.

  8. Metallurgy & Cement Kiln Production Lines

    Dedicated ultra-high-temperature thermocouple acquisition module for rotary kiln firing zone wall temperature, high-temperature flue gas pipeline and preheating furnace thermocouple probes.

Series Unified Iteration Rule (Consistent with full Common Q I/O board product line)

  • G01: Standard basic industrial version, 1500V isolation, 40dB EMI attenuation, basic wire break/short-circuit fault alarm, no waveform storage

  • G02: Reinforced industrial enhanced version, 1800V isolation, 45dB attenuation, optimized cold junction compensation, fast thermal drift diagnosis

  • G03: Gen3 nuclear high-isolation grade, 2000V isolation, 50dB attenuation, fault waveform capture + non-volatile historical fault storage

  • G04: Gen4 flagship ultra-high isolation, 2200V isolation, 55dB attenuation, nanosecond high-precision timestamp, wider operating temperature range

  • G05: Gen5 premium seismic qualified grade, 2500V isolation, 60dB attenuation, anti-loose locking terminal structure, full IEEE 344 seismic certification, extended service life & warranty

  • G06: Gen6 extreme super-isolation flagship, 3000V isolation, 65dB attenuation, nuclear anti-radiation component screening, double anti-loose terminals, 15-year power-off fault data retention, full seismic & radiation dual certification

Series Distinction Note

  • 4D33922 series: PT100 RTD low/medium temperature acquisition

  • 4D33942 series: Multi-type thermocouple high-temperature dedicated acquisition


Get a Quote