4D33770G01 Standard 12-Channel Isolated Analog Input Terminal Daughter Card for Common Q Class 1E Nuclear Safety DCS
Description
Parameter Specifications
Part Number: 4D33770G01
Manufacturer: Emerson Westinghouse
Compatible System: Common Q Class 1E Safety Instrument & Control DCS System
Matching Accessories: Analog input master acquisition boards, 49E-3649 rack backplane 49E-3649, redundant power supply 475HP1ENA9GMT
PCB Material: Multi-layer isolated V-0 flame-retardant high-Tg FR-4
Dimension & Weight: 120mm × 66mm × 20.6mm; Net weight: 58g
Ambient Operating Envelope
Operating Temp: -25℃ ~ +70℃
Storage Temp: -50℃ ~ +125℃
Humidity: 5%–95% RH, non-condensing
Power Supply: DC 12V / DC 24V dual adaptive wide-range input
Input Channels: 12 fully independent galvanic isolated analog input channels
Supported Standard Signals: 4–20mA DC loop current, 0–10V DC voltage
Isolation Performance
Channel-to-backplane isolation: 1500V AC
Dielectric withstand: 2000V AC / 60s
Insulation resistance: ≥1200MΩ @ 500VDC
EMC Index: Power frequency interference attenuation ≥40dB, compliant with IEC 61000-6-2 industrial EMC standard
Protection & Diagnosis Functions
Per-channel precise current limiting protection
Bidirectional TVS high-energy surge absorption
Reverse polarity miswiring protection
Analog loop open-circuit / short-circuit real-time detection
Time-stamped fault status uploaded to master controller
Mechanical Reliability
Continuous vibration resistance: 8g (10–150Hz)
Shock resistance: 25g pulse, duration 11ms
Core Feature: Single-module hot swappable under energized rack
Certifications: CE, UL508, IEC60204-1, NRC Class 1E nuclear safety qualification
Aging Validation Standard: 72-hour full-load high-low temperature cyclic aging test
Design Service Life: ≥100,000 hours of 24/7 unattended continuous operation
Warranty: 12-month global unified warranty for original & factory refurbished modules
Application Fields
Nuclear Power Plant Common Q Safety I&C Racks
Standard analog signal acquisition terminal for auxiliary cabinet flow, pressure, liquid level and cooling medium transmitters of reactor auxiliary systems.
AP1000 Nuclear Post-Accident Monitoring System (PAMS)
Isolation analog signal conversion board for containment auxiliary process measurement transmitters.
Thermal & Hydropower Station Main Control Systems
Compact analog input module for boiler auxiliary pressure, feedwater flow and tank level transmitters.
Explosion-Proof Petrochemical DCS Distributed Control System
Field wiring terminal card for reactor medium pressure, pipeline flow and storage tank level analog transmitters.
Offshore Oil & Gas Explosion-Proof Automation Racks
Isolation signal acquisition interface for wellhead pressure, crude pipeline flow and medium temperature transmitters.
Large Diesel Generator Safety Sequential Control Cabinets
Compact analog input subcard for engine oil pressure, cooling water temperature and fuel flow transmitters.
Municipal Large-Scale Water Treatment Safety Interlock DCS
Isolation measurement terminal for pipeline flow, sedimentation tank level and water pressure transmitters.
Metallurgy & Cement Kiln Production Lines
Multi-point analog acquisition module for kiln pressure, flue gas flow and raw material bin level industrial transmitters.
Get a Quote