4D33676G03 Gen3 High-Isolation High-Precision 16-Channel Isolated Analog Input Terminal Daughter Card for Common Q Class 1E Nuclear Safety DCS
Description
Parameter Specifications
Part Number: 4D33676G03
Manufacturer: Emerson Westinghouse
Compatible System: Common Q Class 1E Safety Instrument & Control DCS System
Matching Accessories: Analog input master acquisition boards, 49E-3649 rack backplane, 475HP1ENA9GMT redundant rack power supply
PCB Material: Multi-layer thick copper V-0 zero-halogen flame-retardant high-Tg FR-4
Dimension & Weight: 118mm × 64.5mm × 19.7mm; Net weight: 55g
Ambient Conditions: Operating temperature -30℃ ~ +75℃; Storage temperature -50℃ ~ +130℃; Humidity 5%~98% RH, non-condensing
Power Input: DC 12V / DC 24V dual wide-range adaptive power supply
Input Channels: 16 fully independent galvanic isolated analog input channels
Supported Signal Range: 4–20mA DC current signal, 0–10V DC voltage signal
Isolation Performance: 2000V AC isolation voltage per channel; 2000V AC dielectric withstand for 60s; Insulation resistance ≥1500MΩ @ 500VDC
EMC Index: Power frequency interference attenuation ≥50dB, compliant with IEC 61000-6-2 industrial EMC specification
Protection & Diagnosis: Per-channel precision constant current limiting protection, bidirectional ultra-high-energy surge absorption, reverse polarity lockout, microsecond-level open/short-circuit instant detection, real-time fault identification, microsecond high-precision timestamp fault upload, fault transient waveform capture
Mechanical Reliability: Continuous vibration resistance 10g (10–150Hz); Shock resistance 30g pulse, duration 11ms
Core Feature: Single module hot swappable under energized rack
Certifications: CE, UL508, IEC60204-1, NRC Class 1E nuclear safety certification
Aging Test Standard: 96-hour full-load high-low temperature cyclic aging test with thermal cycle fatigue verification
Design Service Life: ≥150,000 hours of 24/7 uninterrupted continuous operation
Warranty: 12-month global unified warranty for original and refurbished modules
Application Fields
Nuclear power plant Common Q Class 1E safety I&C racks: High-isolation high-precision analog signal acquisition terminal for reactor auxiliary cabinet flow, pressure, liquid level and temperature transmitters
AP1000 nuclear Post-Accident Monitoring System (PAMS): Reinforced anti-interference isolation signal conversion board for containment critical process analog transmitters
Thermal & hydropower station main control systems: High-stability analog input module for boiler main steam pressure, feedwater flow and drum water level transmitters
High-risk explosion-proof petrochemical DCS: Premium precision wiring card for core reactor pressure, pipeline flow and storage tank level analog transmitters
Offshore oil & gas explosion-proof automation racks: Anti-vibration signal isolation interface for wellhead primary pressure, crude pipeline flow and medium temperature transmitters
Large diesel generator safety sequential control cabinets: Analog input subcard for unit lubricating oil pressure, cooling water temperature and fuel flow transmitters
Municipal large-scale water treatment safety interlock DCS: High-precision isolation terminal for main pipeline flow, sedimentation tank level and water pressure transmitters
Metallurgy and cement kiln production lines: Heavy-duty analog acquisition module for kiln internal pressure, flue gas flow and raw material bin level transmitters
Get a Quote