4D33646G01 Standard 16-Channel Isolated Discrete Input Terminal Daughter Card for Common Q Class 1E Nuclear Safety DCS
Description
Parameter Specifications
Part Number: 4D33646G01
Manufacturer: Emerson Westinghouse
Compatible System: Common Q Class 1E Safety Instrument & Control DCS System
Matching Components: Discrete input acquisition master boards, 49E-3649 rack backplane, 475HP1ENA9GMT redundant rack power supply
PCB Material: Multi-layer isolated V-0 flame-retardant high-Tg FR-4
Dimension & Weight: 118mm × 64.5mm × 19.7mm; Net weight: 53g
Ambient Conditions: Operating temperature -25℃ ~ +70℃; Storage temperature -50℃ ~ +125℃; Humidity 5%–95% RH, non-condensing
Power Supply: DC 12V / DC 24V dual adaptive input
Input Channels: 16 fully independent isolated discrete input channels
Supported Signal: Passive dry contact, mechanical limit switch, valve position feedback contact, relay auxiliary contact
Isolation Performance: 1500V AC isolation voltage per channel; 2000V AC dielectric withstand for 60s; Insulation resistance ≥1200MΩ @ 500VDC
EMC Index: Power frequency interference attenuation ≥40dB, compliant with IEC 61000-6-2
Protection & Diagnosis: Per-channel current-limiting protection, bidirectional surge absorption, reverse polarity protection, open/short-circuit fault detection, real-time fault status upload to main controller
Mechanical Performance: Continuous vibration resistance 8g (10–150Hz); Shock resistance 25g pulse, duration 11ms
Core Function: Single-module hot swappable
Certifications: CE, UL508, IEC60204-1, NRC Class 1E nuclear safety certification
Aging Test Standard: 72-hour full-load high-low temperature cyclic aging
Design Service Life: ≥100,000 hours of 24/7 continuous operation
Warranty: 12-month global unified warranty
Application Fields
Nuclear power plant Common Q Class 1E safety I&C racks: Signal acquisition terminal for auxiliary cabinet conventional valve position feedback and auxiliary interlock limit switches
AP1000 nuclear Post-Accident Monitoring System (PAMS): Isolation signal conversion board for auxiliary equipment passive dry contact feedback signals
Thermal & hydropower station control systems: Input module for boiler auxiliary flame feedback, low-pressure water level interlock and turbine auxiliary limit switches
Explosion-proof petrochemical DCS: Wiring card for general pipeline safety interlock switches and low-risk reactor limit contacts
Offshore oil & gas explosion-proof automation racks: Signal isolation board for auxiliary pipeline valve feedback and conventional safety interlock contacts
Large diesel generator safety sequential control cabinets: Discrete input subcard for auxiliary overspeed feedback and cooling system routine fault passive switches
Municipal large-scale water treatment safety interlock DCS: Isolation terminal for conventional liquid level limit and auxiliary gate position interlock switches
Metallurgy and cement kiln production lines: Signal acquisition module for auxiliary furnace door interlock and low-pressure overpressure protection passive contacts