405A742G02
June 08, 2026

405A742G02

405A742G02 is a high‑performance processor module designed by Westinghouse (Emerson) for Ovation and WDPF Distributed Control Systems (DCS). It serves as the core control unit for data processing, logic execution, and communication management within the Multibus chassis. This module is a revision upgrade of the 405A742G01, featuring enhanced processing power, expanded memory, and improved diagnostic capabilities. It supports hot‑swap operation for redundant system configurations, enabling online replacement without process interruption.

Description

2.1 General

  • Part Number: 405A742G02

  • Manufacturer: Westinghouse / Emerson

  • Product Type: DCS Processor Module

  • Compatible Systems: Ovation DCS, WDPF DCS (Multibus chassis: 405A675G / 405A685G series)

  • Revision: G02 (enhanced production revision)

  • Status: Obsolete (EOL);available as NOS (New Old Stock) or certified refurbished

  • Warranty: 12 months (refurbished);24 months (NOS)

2.2 Electrical & Processing

  • Processor: 32‑bit RISC, 200 MHz (vs. 150 MHz on G01)

  • Memory: 128 MB RAM, 64 MB Flash (double G01 capacity)

  • Backplane Interface: Multibus (32‑bit data, 24‑bit address)

  • Communication Ports: Dual Ethernet (10/100 Mbps), RS‑232/485

  • Real‑Time Clock: Battery‑backed, 10‑year retention

  • Power Consumption: 18 W max (from backplane +5 VDC)

  • Protection: Overvoltage, overcurrent, ESD, surge protection

2.3 Physical

  • Form Factor: Standard 6U DCS module

  • Dimensions (W×H×D): 305 mm × 203 mm × 25 mm (12.0 in × 8.0 in × 1.0 in)

  • Weight: ≈ 1.42 kg (3.1 lb)

  • Mounting: 12‑slot Multibus chassis

  • Connectors: Multibus edge connector (backplane), RJ45 (Ethernet), DB9 (serial)

  • Coating: Conformal coated (dust, moisture, corrosion resistance)

  • Cooling: Forced air (chassis fan, 15–20 CFM required)

2.4 Environmental

  • Operating Temperature: 0 °C to +60 °C (32 °F to 140 °F)

  • Storage Temperature: −40 °C to +85 °C (−40 °F to 185 °F)

  • Relative Humidity: 5% to 95% (non‑condensing)

  • Shock/Vibration: IEC 60068‑2‑6 compliant (1 g, 10–150 Hz)

  • MTBF: > 110,000 hours (25 °C, full load)


3. Main Features

  1. Upgraded Processing & Memory
    • Faster 200 MHz processor and doubled RAM/Flash enable more complex control logic and larger data storage.

  2. Dual Redundant Ethernet
    • Two independent Ethernet ports support network redundancy, preventing communication loss in case of single‑port failure.

  3. Enhanced Diagnostics & Fault Logging
    • Extended fault code storage and real‑time monitoring; supports remote diagnostics via Ovation engineering tools.

  4. Full Backward Compatibility
    • Direct replacement for 405A742G01; no chassis or software changes required during upgrade.

  5. Hot‑Swap & Redundancy Support
    • Seamless online replacement in redundant Ovation/WDPF systems; no controller reboot needed.

  6. Robust Industrial Design
    • Conformal coating, vibration resistance, and extended temperature range ensure reliability in harsh process environments.


4. Applications

  • Power Generation: Thermal, nuclear, combined‑cycle plants (Ovation/WDPF DCS).

  • Process Industries: Petrochemical, pulp & paper, cement, water treatment.

  • DCS Upgrades: High‑performance replacement for aging G01 processors.

  • High‑Availability Systems: Redundant processor configurations for 24/7 operation.


5. Installation Instructions

5.1 Pre‑Installation Safety

  • ESD Protection: Always use an ESD wristband when handling the module.

  • Power Off: Shut down the DCS chassis; disconnect AC input; wait 5 minutes for capacitors to discharge.

  • Inspection: Check for bent pins, damaged connectors, or physical damage.

5.2 Installation Steps

  1. Select Slot: Choose the dedicated processor slot (typically slot 1) in the Multibus chassis.

  2. Insert Module: Align with chassis guides; insert firmly until fully seated in the backplane.

  3. Secure Module: Tighten the front‑panel screw to ensure grounding and mechanical stability.

  4. Connect Cables: Attach Ethernet cables to RJ45 ports; connect serial cable to DB9 if needed.

  5. Power On: Reconnect AC power; verify LED status: PWR (Green) ON, RUN (Green) Blinking.

  6. Configure Software: Use Ovation engineering tools to set network parameters and redundancy settings.

  7. Test Communication: Verify connection with I/O modules and supervisory systems.


6. LED Indicators

  • PWR (Green): ON = Backplane power present; OFF = No power or faulty backplane.

  • RUN (Green): Blinking = Normal operation (heartbeat); ON Solid = Firmware update mode; OFF = Processor halt.

  • COM (Yellow): Blinking = Ethernet activity; ON Solid = Link established; OFF = No link.

  • FLT (Red): ON = Module fault (overtemperature, memory error, or communication failure); Blinking = Critical fault.


7. Maintenance & Troubleshooting

7.1 Preventive Maintenance (Quarterly)

  • Visual Inspection: Check connectors for dirt, corrosion, or loose cables.

  • Cleaning: Use dry, low‑pressure compressed air (≤ 2 bar) to clean vents and components.

  • Firmware Update: Ensure latest firmware version via Ovation engineering tools.

  • Redundancy Test: Verify failover operation between primary and redundant processors.

7.2 Troubleshooting

  • PWR LED OFF: Check backplane power supply (405A720H series); verify chassis circuit breaker.

  • RUN LED OFF:

    1. Power cycle the chassis to reset the processor.

    2. Check for corrupted firmware; reflash if necessary.

    3. Replace module if fault persists.

  • COM LED OFF: Verify Ethernet cable connection; check network switch port; review IP configuration.

  • FLT LED ON:

    1. Check chassis airflow and fans for proper cooling.

    2. Review fault logs for specific error codes.

    3. Replace module if fault persists after power cycle.


8. Storage & Handling

  • Packaging: Store in original anti‑static bag; keep in cool, dry, dust‑free area.

  • Temperature: −40 °C to +85 °C; avoid direct sunlight and heat sources.

  • Handling: Hold module by edges only; avoid touching components or connectors.

  • Transport: Use shock‑absorbent packaging; avoid heavy vibration during shipping.


9. Disclaimer

This document is a technical reference only. For full official specifications, installation procedures, and safety guidelines, refer to the Emerson/Westinghouse 405A742G02 User Manual (Document No. 405A742G02‑UM).
Emerson reserves the right to modify specifications without prior notice. All trademarks and product names are property of their respective owners.


Get a Quote