405A720H03 – Power Supply Module
Description
2.1 General
Part Number: 405A720H03
Manufacturer: Westinghouse / Emerson
Product Type: Industrial Power Supply Module
Compatible Systems: WDPF DCS, Ovation DCS
Revision: H03 (latest field revision)
Status: Obsolete (EOL);available as NOS (New Old Stock) or refurbished
Warranty: 12 months (refurbished);24 months (NOS)
2.2 Electrical
Input Voltage: 100–240 VAC (±10%), 50/60 Hz (auto‑ranging)
Input Power: 300 VA max
Output Voltage: +5 VDC, ±12 VDC (Multibus standard)
Output Current:
+5 VDC: 20 A (100 W)
+12 VDC: 5 A (60 W)
−12 VDC: 2 A (24 W)
Regulation: ±0.5% (full load)
Ripple & Noise: < 50 mV p‑p
Protection: Overvoltage (OVP), overcurrent (OCP), short‑circuit (SCP), overtemperature (OTP)
2.3 Physical
Dimensions (W×H×D): 305 mm × 203 mm × 25 mm (12.0 in × 8.0 in × 1.0 in) – standard 6U DCS module
Weight: ≈ 1.2 kg (2.6 lb)
Mounting: 12‑slot Multibus chassis (405A675G / 405A685G series)
Connectors: Multibus edge connector (backplane), AC input terminal block
Coating: Conformal coated (dust, moisture, corrosion resistance)
2.4 Environmental
Operating Temperature: 0 °C to +55 °C (32 °F to 131 °F)Westinghouse
Storage Temperature: −40 °C to +85 °C (−40 °F to 185 °F)
Relative Humidity: 5% to 95% (non‑condensing)Westinghouse
Shock/Vibration: IEC 60068‑2‑6 compliant (industrial grade)
MTBF: > 100,000 hours (25 °C, full load)
3. Main Features
- Wide‑Range AC Input
Auto‑ranging 100–240 VAC eliminates need for voltage selection switches; global compatibility.
- High Efficiency & Low Heat
Active power factor correction (PFC) reduces energy consumption; efficiency > 85% at full load.
- Hot‑Swap & Redundancy Ready
Supports online replacement in redundant Ovation/WDPF chassis; no system shutdown required.
- Comprehensive Protection
OVP/OCP/SCP/OTP safeguards against electrical faults; automatic shutdown with fault logging.
- LED Diagnostic Indicators
Front‑panel LEDs for power, output, and fault status; rapid troubleshooting.
- Robust Industrial Design
Conformal coating, vibration resistance, and extended temperature range for 24/7 operation.
4. Applications
Power Generation: Thermal, nuclear, combined‑cycle plants (WDPF/Ovation DCS).
Process Industries: Petrochemical, pulp & paper, cement, water treatment, pharmaceutical.
DCS Migration & Maintenance: Replaces aging power supplies in legacy Multibus chassis; extends system lifespan.
Industrial Control Rooms: Powers PLCs, operator workstations, and remote I/O panels.
5. Comparison with 405A720H01/H02
| Feature | 405A720H03 | 405A720H02 | 405A720H01 |
|---|---|---|---|
| Input Range | 100–240 VAC (auto) | 110/220 VAC (switch) | 110 VAC only |
| Efficiency | > 85% | > 80% | > 75% |
| Protection | OVP/OCP/SCP/OTP | OVP/OCP/SCP | Basic OCP |
| Hot‑Swap | Yes | Yes | No |
| MTBF | >100,000 h | >80,000 h | >50,000 h |
| Compatibility | All WDPF/Ovation | Most WDPF/Ovation | Legacy WDPF only |
6. Installation Instructions
6.1 Pre‑Installation Safety
ESD Protection: Use an ESD wristband when handling; avoid static‑sensitive areas.
Power Off: Shut down the chassis; disconnect AC input; wait 5 minutes for capacitors to discharge.
Inspection: Check for bent pins, burnt components, or damaged connectors.
6.2 Installation Steps
Locate Slot: Select an available 6U Multibus slot in the 405A675G/685G chassis.
Insert Module: Align with chassis guides; insert firmly until fully seated.
Secure Module: Tighten front‑panel screw for grounding and stability.
Connect AC Input: Wire 100–240 VAC to the terminal block (L/N/PE).
Power On: Reconnect AC; verify LEDs: PWR (Green) ON, OUT (Yellow) ON.
Verify Output: Measure +5 VDC (±0.5%) and ±12 VDC at backplane connectors.
7. LED Indicators
| LED | Color | Status | Description |
|---|---|---|---|
| PWR | Green | ON | AC input present, standby power OK. |
| OUT | Yellow | ON | All DC outputs within regulation. |
| FLT | Red | ON | Fault: OVP/OCP/SCP/OTP; check load or replace module. |
| FLT | Red | Blinking | Over temperature; check chassis ventilation. |
8. Maintenance & Troubleshooting
8.1 Preventive Maintenance (Quarterly)
Visual Inspection: Check connectors for dirt/corrosion; verify wiring tightness.
Cleaning: Use dry, low‑pressure air (≤ 2 bar) to clean vents and components.
Load Test: Verify output voltages under full load; compare to specs.
8.2 Troubleshooting
PWR LED OFF: Check AC input, fuse, and terminal block wiring.
OUT LED OFF: Check for short circuits in I/O modules; verify backplane voltage.
FLT LED ON:
Disconnect all loads; power on to test if fault persists.
If fault clears, reconnect loads one by one to isolate faulty module.
If fault remains, replace 405A720H03.
Blinking FLT LED: Ensure chassis fans are operational; clear blocked vents.
9. Storage & Handling
Packaging: Store in original anti‑static bag; keep in cool, dry area.
Temperature: −40 °C to +85 °C; avoid direct sunlight and heat sources.
Handling: Hold by edges only; avoid touching components or connectors.
Get a Quote