405A720H03 – Power Supply Module
June 08, 2026

405A720H03 – Power Supply Module

405A720H03 is a high‑reliability industrial power supply module designed by Westinghouse (Emerson) for the WDPF and Ovation Distributed Control Systems (DCS). It provides regulated DC power to Multibus‑based controller chassis and I/O modules, ensuring stable operation in critical process environments. This unit is a drop‑in replacement for older 405A720H series revisions, featuring improved efficiency, enhanced surge protection, and a compact 6U form factor. It is hot‑swap capable for redundant systems, minimizing downtime during maintenance.

Description

2.1 General

  • Part Number: 405A720H03

  • Manufacturer: Westinghouse / Emerson

  • Product Type: Industrial Power Supply Module

  • Compatible Systems: WDPF DCS, Ovation DCS

  • Revision: H03 (latest field revision)

  • Status: Obsolete (EOL);available as NOS (New Old Stock) or refurbished

  • Warranty: 12 months (refurbished);24 months (NOS)

2.2 Electrical

  • Input Voltage: 100–240 VAC (±10%), 50/60 Hz (auto‑ranging)

  • Input Power: 300 VA max

  • Output Voltage: +5 VDC, ±12 VDC (Multibus standard)

  • Output Current:

    • +5 VDC: 20 A (100 W)

    • +12 VDC: 5 A (60 W)

    • −12 VDC: 2 A (24 W)

  • Regulation: ±0.5% (full load)

  • Ripple & Noise: < 50 mV p‑p

  • Protection: Overvoltage (OVP), overcurrent (OCP), short‑circuit (SCP), overtemperature (OTP)

2.3 Physical

  • Dimensions (W×H×D): 305 mm × 203 mm × 25 mm (12.0 in × 8.0 in × 1.0 in) – standard 6U DCS module

  • Weight: ≈ 1.2 kg (2.6 lb)

  • Mounting: 12‑slot Multibus chassis (405A675G / 405A685G series)

  • Connectors: Multibus edge connector (backplane), AC input terminal block

  • Coating: Conformal coated (dust, moisture, corrosion resistance)

2.4 Environmental

  • Operating Temperature: 0 °C to +55 °C (32 °F to 131 °F)Westinghouse

  • Storage Temperature: −40 °C to +85 °C (−40 °F to 185 °F)

  • Relative Humidity: 5% to 95% (non‑condensing)Westinghouse

  • Shock/Vibration: IEC 60068‑2‑6 compliant (industrial grade)

  • MTBF: > 100,000 hours (25 °C, full load)


3. Main Features

  1. Wide‑Range AC Input
    • Auto‑ranging 100–240 VAC eliminates need for voltage selection switches; global compatibility.

  2. High Efficiency & Low Heat
    • Active power factor correction (PFC) reduces energy consumption; efficiency > 85% at full load.

  3. Hot‑Swap & Redundancy Ready
    • Supports online replacement in redundant Ovation/WDPF chassis; no system shutdown required.

  4. Comprehensive Protection
    • OVP/OCP/SCP/OTP safeguards against electrical faults; automatic shutdown with fault logging.

  5. LED Diagnostic Indicators
    • Front‑panel LEDs for power, output, and fault status; rapid troubleshooting.

  6. Robust Industrial Design
    • Conformal coating, vibration resistance, and extended temperature range for 24/7 operation.


4. Applications

  • Power Generation: Thermal, nuclear, combined‑cycle plants (WDPF/Ovation DCS).

  • Process Industries: Petrochemical, pulp & paper, cement, water treatment, pharmaceutical.

  • DCS Migration & Maintenance: Replaces aging power supplies in legacy Multibus chassis; extends system lifespan.

  • Industrial Control Rooms: Powers PLCs, operator workstations, and remote I/O panels.


5. Comparison with 405A720H01/H02

表格
Feature405A720H03405A720H02405A720H01
Input Range100–240 VAC (auto)110/220 VAC (switch)110 VAC only
Efficiency> 85%> 80%> 75%
ProtectionOVP/OCP/SCP/OTPOVP/OCP/SCPBasic OCP
Hot‑SwapYesYesNo
MTBF>100,000 h>80,000 h>50,000 h
CompatibilityAll WDPF/OvationMost WDPF/OvationLegacy WDPF only

6. Installation Instructions

6.1 Pre‑Installation Safety

  • ESD Protection: Use an ESD wristband when handling; avoid static‑sensitive areas.

  • Power Off: Shut down the chassis; disconnect AC input; wait 5 minutes for capacitors to discharge.

  • Inspection: Check for bent pins, burnt components, or damaged connectors.

6.2 Installation Steps

  1. Locate Slot: Select an available 6U Multibus slot in the 405A675G/685G chassis.

  2. Insert Module: Align with chassis guides; insert firmly until fully seated.

  3. Secure Module: Tighten front‑panel screw for grounding and stability.

  4. Connect AC Input: Wire 100–240 VAC to the terminal block (L/N/PE).

  5. Power On: Reconnect AC; verify LEDs: PWR (Green) ON, OUT (Yellow) ON.

  6. Verify Output: Measure +5 VDC (±0.5%) and ±12 VDC at backplane connectors.


7. LED Indicators

表格
LEDColorStatusDescription
PWRGreenONAC input present, standby power OK.
OUTYellowONAll DC outputs within regulation.
FLTRedONFault: OVP/OCP/SCP/OTP; check load or replace module.
FLTRedBlinkingOver temperature; check chassis ventilation.

8. Maintenance & Troubleshooting

8.1 Preventive Maintenance (Quarterly)

  • Visual Inspection: Check connectors for dirt/corrosion; verify wiring tightness.

  • Cleaning: Use dry, low‑pressure air (≤ 2 bar) to clean vents and components.

  • Load Test: Verify output voltages under full load; compare to specs.

8.2 Troubleshooting

  • PWR LED OFF: Check AC input, fuse, and terminal block wiring.

  • OUT LED OFF: Check for short circuits in I/O modules; verify backplane voltage.

  • FLT LED ON:

    1. Disconnect all loads; power on to test if fault persists.

    2. If fault clears, reconnect loads one by one to isolate faulty module.

    3. If fault remains, replace 405A720H03.

  • Blinking FLT LED: Ensure chassis fans are operational; clear blocked vents.


9. Storage & Handling

  • Packaging: Store in original anti‑static bag; keep in cool, dry area.

  • Temperature: −40 °C to +85 °C; avoid direct sunlight and heat sources.

  • Handling: Hold by edges only; avoid touching components or connectors.


10. Disclaimer

This document is a technical reference only. For full official specifications, installation procedures, and safety guidelines, refer to the Emerson/Westinghouse 405A720H03 User Manual (Document No. 405A720H03‑UM).
Emerson reserves the right to modify specifications without prior notice. All trademarks are property of their respective owners.


Get a Quote