405A528G62
Description
Technical Specifications
Model: 405A528G62
Manufacturer: Westinghouse / Emerson
Compatible Systems: Ovation, WDPF DCS
Type: Chassis‑mounted, plug‑in DC power supply
Input: 115/230 VAC, 50/60 Hz (auto‑sensing)
Output: Multiple regulated DC rails (Multibus standard voltages), higher current rating than G61
Hot‑swap: Yes (replace online without system shutdown)
Redundancy: Supports 1+1 redundant operation
Dimensions (H×W×D): ~13.3 cm × 44.5 cm × 25.4 cm
Weight: ~1.42 kg
Operating Temperature: 0 °C to 50 °C
Relative Humidity: 5%–95%, non‑condensing
Protection: Overvoltage, overcurrent, short‑circuit, overtemperature
Features: EMI filtering, conformal coating, LED status indicators
Key Difference: G61 vs G62
405A528G61: Standard‑output power supply
405A528G62: Upgraded, higher‑current version; same form/fit/function, higher power capacity for heavier I/O loads
Application Fields
Power Generation: Thermal, nuclear plants (Ovation/WDPF DCS core power)
Process Industries: Petrochemical, pulp & paper, cement, water treatment
High‑Load Chassis: Preferred for chassis with full I/O and redundant DPUs
Legacy System Maintenance: Direct replacement for aging G61 or failed supplies
Installation & Operation
Insert into dedicated power slot of 405A528 series chassis.
Secure front‑panel screws; connect AC input to chassis.
Verify Power OK LED (green = normal).
For redundancy, install a second G62 in the adjacent slot.
Hot‑swap faulty units during operation if Fault LED (red) illuminates.
Diagnosis & Maintenance
Green Power LED: Normal DC output.
Red Fault LED: Overvoltage, overcurrent, overtemperature, or fan failure.
Quarterly: Inspect LEDs, connectors, and vents; clean dust if needed.
Safety: Disconnect AC before removal; allow capacitors to discharge.
Get a Quote