405A528G33
June 08, 2026

405A528G33

The 405A528G33 is a 12‑slot MOD chassis (Multibus) manufactured by Westinghouse (Emerson), belonging to the same 405A528 series as the G01/G02/G21 but configured with a 2MBB2 backplane (7381A61G01) and a 1FILM2 filter assembly (7381A26G01). It is a legacy WDPF/Ovation DCS enclosure for industrial control, providing mechanical support, electrical interconnection, and cooling for DPU controllers, I/O modules, and power supplies.

Description

Technical Specifications

  • Model: 405A528G33

  • Manufacturer: Westinghouse / Emerson

  • Compatible Systems: Legacy WDPF, Ovation DCS

  • Configuration: 12‑slot chassis with 2MBB2 Multibus backplane (7381A61G01) and 1FILM2 EMI/line filter (7381A26G01)

  • Input Power: 115/230 VAC auto‑sensing, 50/60 Hz

  • Cooling: Dual hot‑swappable fans, front‑to‑back airflow

  • Mounting: Standard 19‑inch EIA rack mount

  • Dimensions (H×W×D): ~13.3 cm × 44.5 cm × 50.8 cm

  • Weight: ~16.3 kg (empty, with backplane/filter)

  • Operating Temperature: 0 °C to 50 °C

  • Relative Humidity: 5% to 95%, non‑condensing

  • Key Features: Integrated 2MBB2 backplane + 1FILM2 filter; hot‑swappable modules; redundant power supply support; enhanced EMI shielding; optimized for legacy WDPF/Ovation reliability

Series Model Comparison

  • 405A528G01: 12 slots, 115/230 VAC, standard backplane, basic version

  • 405A528G02: 12 slots, fixed 230 VAC, standard backplane, basic version

  • 405A528G21: 12 slots, 115/230 VAC, enhanced backplane, high‑reliability version

  • 405A528G33: 12 slots, 115/230 VAC, 2MBB2 backplane + 1FILM2 filter, high‑reliability MOD chassis

Application Fields

  • Power Generation: Thermal/nuclear power plants, WDPF/Ovation DCS main chassis for DPUs, I/O, and redundant power

  • Process Industries: Petrochemical, pulp & paper, cement—rack‑mounted DCS control nodes

  • Legacy System Upgrades: Replacement/enhancement for aging WDPF/Ovation chassis requiring integrated backplane/filter

Installation & Operation

  1. Mount to standard 19‑inch EIA rack; reserve 1U top/bottom for ventilation

  2. Connect 115/230 VAC to chassis inlet; verify power LED

  3. Install DPUs, I/O, power supplies per system slot layout

  4. Complete Multibus wiring and chassis grounding for multi‑chassis coordination

  5. Check fan LEDs quarterly; keep front/back vents unobstructed

Diagnosis & Maintenance

  • Green Power LED: Normal AC input

  • Green Fan LED: Dual fans operational

  • Red Fault LED: Overheat, fan failure, backplane voltage fault, or filter anomaly

  • Quarterly: Inspect connectors, backplane, filter, and air filters

  • Safety: Disconnect all power before maintenance; wait for capacitor discharge

Product Status

Obsolete legacy product. Available as new old stock (NOS) or refurbished spare parts; fully compatible with WDPF/Ovation modules.


Get a Quote