405A431G02
June 08, 2026

405A431G02

405A431G02 is a high‑reliability, industrial‑grade AC/DC power supply module designed for the Emerson Ovation™ / WDPF DCS platform (legacy Westinghouse). It provides regulated 24 VDC power to DPU controllers, I/O bases, and field devices. The G02 variant is an upgraded, fully compatible drop‑in replacement for the 405A431G01, with enhanced surge immunity, wider input tolerance, and improved long‑term stability for critical control environments.

Description

Technical Specifications

  • Model: 405A431G02

  • Manufacturer: Emerson (Westinghouse)

  • System Compatibility: Ovation™ DCS, WDPF DCS

  • Function: Isolated AC/DC power supply, 24 VDC output

  • Input Voltage: 85–264 VAC, 50/60 Hz; 120–370 VDC

  • Output Voltage: 24 VDC ±0.5% (adjustable 22–26 VDC)

  • Output Current: 10 A continuous, 12 A peak

  • Power Rating: 240 W

  • Efficiency: ≥ 93% (full load, 230 VAC input)

  • Isolation: 3,000 VAC input‑to‑output

  • Protection: Overvoltage, overcurrent, short‑circuit, overtemperature, surge/EMI filtering, reverse polarity

  • Operating Temperature: 0 °C to +65 °C

  • Storage Temperature: −40 °C to +85 °C

  • Relative Humidity: 5%–95%, non‑condensing

  • Installation: Standard 35 mm DIN rail mount

  • Dimensions: ~125 × 90 × 55 mm

  • Weight: ~1.42 kg

  • Certifications: CE, UL, RoHS compliant

  • Key Features: Hot‑swappable, redundant parallel operation, active current sharing, enhanced diagnostics, improved surge immunity vs. G01

Application Fields

  • Power Generation: Ovation/WDPF DCS system power, DPU controller supply, redundant power for power plant control rooms.

  • Process Industries: Petrochemical, pulp & paper, cement — 24 VDC distribution for field transmitters, valves, and remote I/O.

  • Water Treatment: SCADA system power, sensor/actuator supply, redundant power for wastewater treatment plants.

  • Critical Infrastructure: Any application requiring high‑reliability, isolated 24 VDC in industrial environments.

Installation & Wiring

  1. Pre‑Installation: Disconnect all AC/DC power; ensure DIN rail is properly grounded.

  2. Mounting: Snap module onto a standard 35 mm DIN rail and lock in place.

  3. AC Input: Connect 85–264 VAC to L/N/PE terminals; use 14–18 AWG wire.

  4. DC Output: Connect 24 VDC to +24V/COM terminals; observe polarity.

  5. Redundancy: For parallel redundancy, connect +24V terminals together and COM terminals together; enable active current sharing.

  6. Grounding: Connect chassis ground to system earth for ESD/EMI protection.

Operation & Diagnostics

  • PWR (Green): Output voltage normal.

  • AC OK (Green): AC input present and within range.

  • FAULT (Red): Overvoltage, overcurrent, short circuit, overtemperature, or fan failure.

  • Monitoring: Output voltage/current can be monitored via Ovation workstation tools or local test points.

Maintenance & Safety

  • Maintenance: Inspect connections and terminals periodically; keep ventilation slots clear.

  • Safety: Disconnect all power before servicing; allow 5 minutes for capacitors to discharge.

  • Operating Limits: Do not exceed rated input/output voltage/current; keep within temperature/humidity ranges.

Product Status

  • Current Status: Active production; new original and refurbished spares available.

  • Compatibility: Fully interoperable with all Ovation/WDPF DCS releases; drop‑in replacement for 405A431G01.


Get a Quote