405A431G02
Description
Technical Specifications
Model: 405A431G02
Manufacturer: Emerson (Westinghouse)
System Compatibility: Ovation™ DCS, WDPF DCS
Function: Isolated AC/DC power supply, 24 VDC output
Input Voltage: 85–264 VAC, 50/60 Hz; 120–370 VDC
Output Voltage: 24 VDC ±0.5% (adjustable 22–26 VDC)
Output Current: 10 A continuous, 12 A peak
Power Rating: 240 W
Efficiency: ≥ 93% (full load, 230 VAC input)
Isolation: 3,000 VAC input‑to‑output
Protection: Overvoltage, overcurrent, short‑circuit, overtemperature, surge/EMI filtering, reverse polarity
Operating Temperature: 0 °C to +65 °C
Storage Temperature: −40 °C to +85 °C
Relative Humidity: 5%–95%, non‑condensing
Installation: Standard 35 mm DIN rail mount
Dimensions: ~125 × 90 × 55 mm
Weight: ~1.42 kg
Certifications: CE, UL, RoHS compliant
Key Features: Hot‑swappable, redundant parallel operation, active current sharing, enhanced diagnostics, improved surge immunity vs. G01
Application Fields
Power Generation: Ovation/WDPF DCS system power, DPU controller supply, redundant power for power plant control rooms.
Process Industries: Petrochemical, pulp & paper, cement — 24 VDC distribution for field transmitters, valves, and remote I/O.
Water Treatment: SCADA system power, sensor/actuator supply, redundant power for wastewater treatment plants.
Critical Infrastructure: Any application requiring high‑reliability, isolated 24 VDC in industrial environments.
Installation & Wiring
Pre‑Installation: Disconnect all AC/DC power; ensure DIN rail is properly grounded.
Mounting: Snap module onto a standard 35 mm DIN rail and lock in place.
AC Input: Connect 85–264 VAC to L/N/PE terminals; use 14–18 AWG wire.
DC Output: Connect 24 VDC to +24V/COM terminals; observe polarity.
Redundancy: For parallel redundancy, connect +24V terminals together and COM terminals together; enable active current sharing.
Grounding: Connect chassis ground to system earth for ESD/EMI protection.
Operation & Diagnostics
PWR (Green): Output voltage normal.
AC OK (Green): AC input present and within range.
FAULT (Red): Overvoltage, overcurrent, short circuit, overtemperature, or fan failure.
Monitoring: Output voltage/current can be monitored via Ovation workstation tools or local test points.
Maintenance & Safety
Maintenance: Inspect connections and terminals periodically; keep ventilation slots clear.
Safety: Disconnect all power before servicing; allow 5 minutes for capacitors to discharge.
Operating Limits: Do not exceed rated input/output voltage/current; keep within temperature/humidity ranges.
Product Status
Current Status: Active production; new original and refurbished spares available.
Compatibility: Fully interoperable with all Ovation/WDPF DCS releases; drop‑in replacement for 405A431G01.
Get a Quote