3A99168G01 8-Channel Relay Digital Output Module
Description
1. Product Overview
2. Core Electrical Specifications
Backplane power supply: +5VDC, +24VDC supplied by Ovation rack power modules
Channel configuration: total 8 independent isolated relay output channels (SPST dry contact)
Rated contact capacity: Max 250VAC/5A or 30VDC/5A per single channel
Channel isolation: 1000VAC isolation between every channel and internal circuit, anti-cross-interference design
Built-in protection: onboard channel fuse, transient TVS absorption for relay coil surge, overcurrent lockout protection
Signal matching: direct logic communication via Ovation backplane bus with system controller
3. Environmental & Mechanical Parameters
Operating ambient temp inside cabinet: 0℃ ~ +60℃; storage temperature: -40℃ ~ +85℃
PCB conformal coating: full three-layer moisture-proof, anti-mold and anti-salt spray coating for high-humidity power plant cabinet environment
EMC standard: comply with IEC61000-6-2 industrial anti-interference & CE certification
Dimension: standard single-width Ovation Eurocard form factor, unified installation size with 3A99166/3A99165 series boards
4. Front Panel Indicator & Installation Features
Front panel LED status lamps: green POWER LED for module power-on; separate per-channel status LED to show relay pull-in status
Equipped with edge connector terminal for field wiring connection; no extra adapter needed for standard Ovation base wiring baseplate
Hot pluggable design: module can be pulled out and replaced without cutting off rack power, only relevant local field loop temporarily offline; critical protection loops adopt dual-module redundant setup to avoid unit shutdown risk
5. Spare Part & On-site Troubleshooting Guide
All channels no output: abnormal backplane input power or damaged module main power circuit
Individual channel cannot close contact: blown channel fuse, aging internal relay coil or contact burnout
LED indicator abnormal but contact works normally: damaged onboard channel indicator circuit
Random contact bounce under operation: loose wiring terminals or degraded relay mechanical structure
Get a Quote