Emerson Ovation 3A99164G03 QAV RTD Analog Input Module (SUB8 Quad-Bus Series)
Description
1. Part Number Explanation
3A99164: QAV low-level analog input product line for Ovation SUB8 I/O rack
G03: Dedicated 8-channel RTD resistance temperature detector input version
Optional reinforced model: 3A99164G03G50: Factory upgraded version with enhanced surge and EMC protection for harsh industrial environments
G01: Narrow-range millivolt input for thermocouple (-5~+20mV)
G02: Wide-range millivolt input for thermocouple (-12.5~+50mV)
G03: Specialized RTD platinum resistance temperature input
2. Electrical Specifications
Channel configuration: 8 galvanically isolated RTD input channels; software configurable for 3-wire or 4-wire RTD connection
Supported sensors: PT100, PT500, Cu50 resistance temperature detectors
Measuring resistance range: 0 ~ 400Ω; corresponding measuring temperature range: -200℃ ~ +850℃
Onboard excitation: Fixed 0.8mA constant excitation current per channel
Galvanic isolation: 1000VAC isolation between field circuit and internal Quad-Bus backplane
Measurement accuracy: ≤0.07% Full Scale; full-channel scan cycle ≤3.0ms
Built-in diagnostic: Open wire detection, short-circuit alarm, over-range resistance identification and module self-diagnosis; all fault signals transmitted to DPU via SUB8 Quad-Bus
Backplane power supply: Powered by +5VDC and ±12VDC from SUB8 rack backplane; typical power consumption ≈4.2W
3. Mechanical & Environmental Specifications
Form factor: Standard hot-swappable plug-in module for SUB8 rack; dimension: 260mm×100mm×25mm, fully interchangeable with all Q-series SUB8 I/O cards
Hot-swap capability: Online module replacement without rack power shutdown
Operating temperature: -40℃ ~ +70℃; storage temperature: -45℃ ~ +85℃
Ambient humidity: 5%~95%RH non-condensing; G50 variant complies with CE and power plant EMC standards
4. Front Panel LED Indicators
POWER (Green): Illuminated when backplane power is normal
RUN (Green): Lit during healthy Quad-Bus communication with SUB8 master card (3A99158G02 / 3A99159G03)
CH1~CH8: Individual LED turns on when valid RTD signal is detected
FAULT (Red): Activated for open circuit, short circuit or onboard hardware malfunction
5. Key Features
Supports both 3-wire and 4-wire RTD wiring to eliminate line resistance measuring error.
G50 customized version is equipped with multi-stage surge suppression components to resist surge interference from power plant and petrochemical field.
User configurable temperature range, digital filter and alarming parameters via Ovation Developer configuration software.
Fully compatible with redundant SUB8 bus architecture matched with dual redundant master cards.
6. Typical Application
Thermal power plant: Boiler wall temperature, air preheater and flue gas temperature acquisition via PT100 RTD
Petrochemical industry: Reactor, pipeline medium temperature monitoring
Waste incineration and water treatment equipment temperature measurement
7. Matching SUB8 Series Components
SUB8 Bus Master: 3A99158G02, 3A99159G03
DI Module(QBI):3A99160G02
4–20mA AI Module(QAI):3A99163G01G50
AO Module(QAO):3A99161G01
Solid-state DO(QBO):3A99162G01