Emerson Ovation 3A99164G01 (QBO Solid-State Digital Output Module, SUB8 Series)
Description
1. Part Number Definition
3A99164: Base SUB8 QBO digital output module family for Ovation DCS Quad-Bus rack system
G01: Standard base variant, solid-state transistor DC output type; matching reinforced surge version marked as 3A99164G01G50
Related model differentiation:
3A99164G01: Standard 16-channel solid-state DO, 24VDC sinking/sourcing output (basic non-surge)
3A99164G01G50: G50 enhanced anti-surge, lightning & EMC hardened version for heavy industrial site
Relay-type DO: 3A99168 series (Form A mechanical relay output, separate from QBO solid-state)
2. Electrical Specifications
Channel count: 16 galvanically isolated solid-state digital output channels (no mechanical relay)
Rated output: 24VDC field load, max 0.5A per single channel; total module aggregated load ≤6A
Output type: Configurable sink/source transistor drive for solenoid valves, contactors, indicator lamps
Isolation: Field-to-backplane isolation 1000VAC; G50 variant adds multi-stage TVS + varistor surge suppression
Diagnostic functions: Per-channel short-circuit protection, overload fault detection, open-load alarm, internal hardware self-test; all fault status uploaded to DPU via Quad-Bus automatically
Backplane power supply: +5V & ±12VDC from SUB8 rack backplane; typical power consumption ≈3.9W
Response time: Channel switching delay ≤0.3ms, fast logic output for interlock & sequence control
3. Mechanical & Environmental Data
Form factor: Standard plug-in SUB8 rack card, dimension 260mm × 100mm × 25mm, fully mechanically interchangeable with SUB8 QAI/QBI/QAO modules
Hot-swap feature: Supports online hot-plug replacement without shutting down rack power, no disturbance to adjacent I/O cards
Operating temperature: -40℃ ~ +70℃; storage temperature: -45℃ ~ +85℃
Ambient humidity: 5%~95%RH non-condensing; G50 version complies with power plant EMC & CE industrial certification
4. Front Panel LED Indicators
POWER (Green): Lights up when backplane supply is normal
RUN (Green): Illuminated during healthy Quad-Bus communication with SUB8 master card (3A99158G02 / 3A99159G03)
CH1~CH16: Individual channel LED turns ON when corresponding output channel is energized
FAULT (Red): Activated by channel overload, short-circuit or module internal hardware failure
5. Core Features
Solid-state non-relay design, long service life, no contact abrasion for frequent on-off switching applications
G50 optional surge reinforced circuit against field surge spike, inverter & motor EMI interference for thermal power, petrochemical site
Compatible with redundant SUB8 master controller for dual-redundant DCS I/O drop configuration
Output logic inversion, fault alarm threshold configurable via Ovation Developer software
6. Typical Application
Thermal power plant: Control of solenoid valves, field auxiliary relays, local status indicator lights
Petrochemical / Waste-to-energy plant: Interlock logic drive for pump, fan auxiliary control circuit
Water treatment plant: On-off control of dosing valve and auxiliary field equipment
7. Matching SUB8 System Components
SUB8 Quad-Bus Master Card: 3A99158G02 (standard), 3A99159G03 (redundant)
DI QBI Module: 3A99160G02
AI QAI Module: 3A99163G01/G01G50
AO QAO Module: 3A99161G01
Relay Output QRO Module: 3A99168G01
Get a Quote