Emerson Ovation 3A99163G02G50 QAI Universal Analog Input Module (SUB8 Quad Bus AI, Alternate PN:4256A64G02)
Description
1. Product Overview
2. Electrical Specifications
Channel layout: 8 fully galvanic isolated universal analog input channels, Quad-Bus SUB8 architecture, software configurable per channel for 4–20mA DC current / 0–5V / 0–10V DC voltage input (core upgrade from G01 single 4–20mA only)
Backplane power: +5VDC & ±12VDC powered via SUB8 rack backplane; typical power consumption ≤4.5W
Isolation rating: 1000VAC channel-to-backplane isolation; G50 variant adds multi-stage TVS surge absorption circuit for anti-lightning & cabinet power clutter interference
Loop parameter: 2-wire/3-wire transmitter loop supply supported; max loop resistance: 900Ω(@4–20mA); voltage input high impedance ≥1MΩ
Measurement performance: Basic accuracy ≤0.1%FS; full 8-channel scan refresh ≤3ms; built-in per-channel open-circuit, over-range, short-circuit diagnostic, fault codes uploaded to DCS automatically
Signal filtering: Digital low-pass filter adjustable via Ovation software to suppress field EMI noise
3. Mechanical & Environmental Data
Form factor: Standard hot-swappable plug-in SUB8 rack module, unified dimension:260mm×100mm×25mm, same mechanical outline as all other Q-series I/O modules
Operating ambient: -40℃ ~ +70℃; storage temp: -45℃ ~ +85℃; humidity 5%~95%RH non-condensing; G50 passes enhanced power-industry EMC certification for coal-fired thermal plant site
Net weight: approx 0.36kg
4. Front Panel LED Definition & Core Features
LED Indicator Description
POWER(Green): Normal backplane power feed
RUN(Green): Healthy Quad-Bus communication with SUB8 master card
CH1~CH8 Individual LED: Lights up when valid analog signal detected on corresponding channel
FAULT(Red): Alarm for channel open/overrange/onboard hardware failure
Main Functional Highlights
Online hot-swap: Module replacement without rack power shutdown, no impact on adjacent I/O cards
G02 universal input: Software switch current/voltage mode per single channel without field wiring modification
G50 reinforced protection: Extra surge & transient suppression for harsh power/chemical field installation
Redundant bus compatible: Fully applicable to dual-redundant master card(3A99159G03) SUB8 redundant system
Flexible configuration: Input range, filter coefficient, upper/lower alarm threshold editable on Ovation Developer software
5. Typical Industrial Application
Thermal power: Boiler drum level, main steam temp/pressure, furnace negative pressure, feedwater flow universal signal collection (mixed current+voltage field sensors)
Petrochemical: Reactor pressure, tank level, pipeline flow mixed analog parameter acquisition
Waste incineration & water treatment plant multi-type transmitter signal acquisition
6. Full SUB8 Q-Series Matching List
QBI DI:3A99160G02 (16CH Digital Input)
QAO AO:3A99161G01 (8CH Analog Output)
QBO DO:3A99162G01 (16CH Digital Output)
QAI AI:3A99163G01G50(4–20mA only) / 3A99163G02G50(Universal mA+V)
SUB8 Bus Master:3A99158G02 / 3A99159G03
Get a Quote