Emerson Ovation 3A99163G01-G50 QAI Analog Input Module (SUB8 Quad Bus AI Card, Alternate PN:4256A64G01)3A99163G01G50 is an 8-channel isolated analog input card of Ovation SUB8 Q-series I/O suite, full
Description
1. Product Overview
2. Electrical Specifications
Channel configuration: 8 fully isolated analog input channels, Quad-Bus SUB8 architecture, standard 4–20mA passive loop input
Backplane power supply: +5VDC & ±12VDC powered via SUB8 rack backplane; typical power consumption ≤4.2W
Galvanic isolation: 1000VAC channel-to-bus isolation; G50 variant adds extra transient surge suppression for power plant high-interference cabinet environment
Input loop: Supports 2-wire/3-wire field transmitter power feed; max loop resistance 850Ω per channel
Measurement accuracy: ≤0.1% full-scale precision; all-channel refresh cycle ≤2.8ms
Built-in diagnostics: Individual channel open-circuit detection, over-range alarm, short-circuit fault diagnosis, all fault codes transmitted to DCS system; G50 improves fault anti-jamming capability
3. Mechanical & Environmental Parameters
Form factor: Standard hot-swappable plug-in PCB for SUB8 rack; unified dimension:260mm×100mm×25mm, same as other Q-series I/O cards
Operating temperature: -40℃ ~ +70℃; storage: -45℃ ~ +85℃; humidity 5%~95%RH non-condensing; G50 conforms to power plant coal-fired site EMC enhanced standard, CE certified
Net weight: ~0.35kg
4. Front Panel LED Definition & Core Features
LED Indicators
POWER(Green): Backplane power supply normal
RUN(Green): Normal Quad-Bus communication with SUB8 master card
CH1~CH8 LED: On when corresponding input channel has valid field signal
FAULT(Red): Triggered by channel open/overrange/onboard hardware error
Key Functions
Online hot-swap: Module replacement without cutting rack power, no interruption to other I/O modules in same rack
G50 customized upgrade: Extra TVS surge components, optimized PCB layout for high-voltage interference in thermal power, petrochemical plant
Redundant bus compatible: Supports dual redundant master card (3A99159G03) SUB8 bus setup
Software configurable: Input range, filtering coefficient, alarm threshold adjustable via Ovation Developer configuration software
5. Typical Application
Thermal power plant: Boiler drum level, main steam pressure/temperature, furnace pressure analog signal collection
Petrochemical industry: Pipeline flow, tank level, reactor pressure monitoring
Waste incineration & water treatment DCS analog parameter acquisition
6. Complete SUB8 Q-series Matching Inventory
QBI DI:3A99160G02 (16CH Digital Input)
QAO AO:3A99161G01 (8CH Analog Output)
QBO DO:3A99162G01 (16CH Digital Output)
QAI AI:3A99163G01G50 (8CH Analog Input, G50 enhanced spec)
SUB8 Bus Master:3A99158G01 /3A99159G03
Get a Quote