Emerson Ovation 3A99162G01 QBO Digital Output Module (SUB8 Quad Bus DO Card, alternate part:2840A79G01)
Description
1. Product Overview
2. Electrical Specifications
Channel layout: 16 isolated digital output channels grouped in Quad-Bus architecture, solid-state transistor non-contact output design
Rated field load: 24VDC dry/wet contact drive; single channel max continuous load current 0.5A, inrush surge current limited internally
Backplane power supply: +5VDC & ±12VDC fed via SUB8 rack backplane; typical power consumption ≤3.9W
Galvanic isolation: 1000VAC isolation between field output loops and internal Quad-Bus backplane for anti-EMI & surge suppression
Per-channel protection: built-in overcurrent, short-circuit automatic cutoff protection; circuit fault diagnosed and uploaded to DPU
Scan cycle: Full 16-channel command refresh ≤2ms, compatible with Ovation SOE event sequence recording function
3. Mechanical & Environmental Parameters
Form factor: Standard plug-in SUB8 rack module, unified dimension:260mm×100mm×25mm; supports online hot-swap without rack power shutdown
Operating ambient: -40℃ ~ +70℃; storage temperature: -45℃ ~ +85℃; humidity 5%~95%RH non-condensing, CE industrial EMC certified
Net weight: approx 0.345kg
4. Front Panel LED Indicators & Core Features
LED Status Definition
POWER(Green): Normal backplane power input
RUN(Green): Healthy Quad-Bus communication with SUB8 master card
CH1~CH16 individual LED: Illuminates when corresponding output channel is switched ON
FAULT(Red): Alarm for channel short-circuit, over-load or onboard hardware failure
Key Functional Highlights
Hot-swap maintenance: Single card replacement online without affecting other I/O modules on same rack
Channel independent diagnostics: Short/open/overload fault reported to DCS for real-time system alarm
Redundant bus compatible: Fully works with redundant 3A99159G03 master cards for SUB8 dual-bus redundant configuration
Software configurable: Set fail-safe status (ON/OFF hold) and output delay filtering via Ovation Developer configuration software
5. Typical Industrial Application
On-off control of boiler auxiliary fans, coal feeder, soot blower solenoid valves in thermal power plants
Interlock control of shutdown valves, pump on-off contactors in refining & chemical process units
Motor start/stop logic output and field status lamp driving for metallurgy and waste incineration DCS control
6. Complete SUB8 Q-series Matching List
QBI DI:3A99160G02 (16CH Digital Input)
QAO AO:3A99161G01 (8CH Analog Output)
QBO DO:3A99162G01 (16CH Digital Output)
SUB8 Bus Master:3A99158G02 /3A99159G03
Get a Quote