3A99141G01
Description
1. Product Overview
2. Core Technical Specifications
Electrical Parameter
Working Power: +5VDC / ±12VDC powered by rack backplane, rated power consumption ≤28W
Bus Protocol: Ovation proprietary high-speed local I/O field bus, redundant bus channel design
Communication Rate: Max 2Mbps real-time synchronous data transmission
Drive Capacity: Single card supports up to 32pcs standard Ovation I/O cards cascading in local rack
Built-in circuit protection: Overvoltage, overcurrent, reverse polarity, EMC surge protection
Mechanical & Environmental
Structure: Standard plug-in European card for Ovation Q-type I/O rack, front panel with blue lock buckles
Net Weight: ~1.42kg; Dimension: standard Ovation module outline size
Operating Temp: -30℃ ~ +72℃; Storage Temp: -45℃ ~ +85℃
Humidity: 5%~95%RH non-condensing; comply with CE & IEC industrial anti-interference standard
3. Key Product Features
Hot-swap Support: Online plug and replacement without cabinet power-off, no system outage during maintenance
Redundancy Compatibility: Supports dual-card redundant parallel running; standby module automatically takes over communication upon primary failure
Front Panel Status LED: Power OK, BUS RUN, Fault, Channel Alarm indicator for quick on-site troubleshooting
Self-diagnosis Function: Onboard MCU real-time detects bus short-circuit, I/O rack offline, communication abnormal, and upload fault code to DPU controller
Backplane gold finger connection: Directly plug into I/O rack backplane for power supply and bus wiring, no extra external wiring required
4. Main Application Scenarios
5. Installation & Maintenance Guidance
Install into specified interface slot of Ovation standard Q-type I/O rack, fix front lock buckle to avoid loose contact from equipment vibration
Critical control cabinet recommends redundant configuration (2pcs 3A99141G01 per I/O rack) to improve system reliability
Annual maintenance: Clean PCB surface dust, inspect backplane golden finger oxidation condition, check rack cooling fan operating status
Prohibit plugging/unplugging module under live power when field bus is loaded with full I/O points to avoid instantaneous bus surge damage
Get a Quote