3A99132G02
Description
1. Product Overview
2. Core Parameter Specification
Electrical Ratings
Input Power: AC 110~240V wide-range alternating input (50/60Hz)
Multi-channel DC Output: +5V, ±12V, +24V standard rail voltages for Ovation backplane bus
Max total output power: 420VA, single channel load ≤2.5A
Built-in protection: overvoltage, overcurrent, short-circuit, overheat automatic cut-off protection circuit
Mechanical & Environmental
Structure: Standard European plug-in card, fits Ovation DPU rack slot
Dimension: 415(L)×110(W)×26(H) mm; Net weight ≈0.36kg
Operating ambient temp: -40℃ ~ +70℃; Storage temperature: -45℃~+85℃
Working humidity: 5%~95%RH non-condensing, comply with CE industrial EMC standard
3. Main Features
Redundancy compatible: Supports dual-module redundant parallel power supply, one unit fails while another automatically bears full load without DPU system shutdown
Hot-plug capable: Online replacement without powering off entire DPU cabinet for maintenance
Onboard fault indicator LED: Power OK / overload / fault alarm status visible on front panel
Industrial grade switching power topology, low ripple output, strong anti-interference for harsh power plant workshop environment
Backplane gold finger connector design, reliable bus power distribution with Ovation system rack
4. Application Field
5. Installation & Maintenance Notes
Install vertically into designated DPU power slot of Ovation standard cabinet, keep ventilation gap around PCB for heat dissipation
Recommended redundant configuration (two pcs 3A99132G02 per DPU rack) for critical unit control
Regularly clean surface dust of electrolytic capacitors every 12 months; replace aging power components when abnormal overheating occurs
Input AC wiring must equip front-end 6A slow-blow fuse for input circuit protection