3A99114G04 QRD Universal Analog Input Card
Description
1. Product Identification
QSR:3A99101Gxx (Servo control board)
QRS:3A99108G01
QRF:3A99109G01 (RTD dedicated acquisition card)
2. Core Function Description
Collect field process analog signals (pressure, flow, displacement, auxiliary temperature) from turbine oil system, feedwater system, pump monitoring loop;
Onboard filtering, amplification, isolation and A/D conversion;
Transmit digital data to DPU main controller via standard VME backplane bus;
Supports partial 200Ω Platinum RTD auxiliary measurement besides standard voltage/current input (enhanced RTD compatibility than G03).
Channel Configuration
4 galvanic-isolated independent analog input channels;
Onboard configurable jumpers to switch multiple input signal types:
• DC Current: 4–20mA standard loop signal
• DC Voltage: 0~5VDC, 0~10VDC, ±10VDC
• Thermocouple: Type K, J, E, T with built-in cold junction compensation
• Auxiliary: 200Ω Pt RTD partial channel input (unique upgrade for G04)
Front panel reserved test terminals for zero/span field calibration offline.
3. Electrical Parameters
Power Supply: +5VDC, ±12VDC, powered by crate backplane power module;
A/D Conversion Resolution: 16-bit high precision;
Input Impedance: ≥1MΩ for voltage channel; ≤250Ω default sampling resistance for 4–20mA loop;
Isolation Rating: Each channel isolated ≥1500VAC between field side and backplane side.
4. Environmental Specifications
Operating Temp: Continuous working 0℃ ~ +55℃ inside control cabinet;
Storage Temp: -40℃ ~ +85℃;
Humidity: 5%~95%RH, non-condensing, non-corrosive ambient gas required;
EMC Performance: Enhanced multi-stage EMI filter & full PCB shielding on G04 revision, anti-interference for cabinet inverter, contactor noise, comply with CE industrial control standard.
5. Installation & Replacement Instruction
Install into standard Q-Line VME rack slot, backplane automatic power & bus connection after slot insertion;
Direct drop-in replacement for G01/G02/G03 faulty cards, no wiring modification needed;
After replacement: perform zero-point calibration via front test terminals before on-load operation.
6. Application & Commercial Info
Typical Application: Power plant unit overhaul spare replacement, old WDPF DCS retrofit, emergency breakdown maintenance of turbine DEH analog measurement loop;
Original OEM production discontinued globally; available stock: fully tested refurbished modules & inspected used original spare parts;
Standard repair cycle: 2~4 weeks, rush maintenance repair available; global shipment via DHL/UPS/FedEx.
7. Troubleshooting Brief
No channel reading: Check backplane ±12V/+5V power supply, front terminal field wiring;
Drifting measured value: Re-cal zero/span via front test port, inspect field signal source;
Interference fluctuation: Check cabinet ground connection, verify channel jumper configuration matches field signal type.