5X00226G01 | Emerson Ovation HART Analog Output Module
June 03, 2026

5X00226G01 | Emerson Ovation HART Analog Output Module

Product Introduction 5X00226G01 is Emerson(legacy Westinghouse) Ovation 8-channel HART analog output module, core I/O card for Ovation DCS system, converts controller digital calculation data into standard 4–20mA analog field signal with HART digital superimposed communication, single-slot rack hot-swappable design, matched dedicated terminal base for field actuator wiring, widely used as spare part for thermal power and petrochemical Ovation control cabinet.

Description

Part Code Definition

5X00226G01 is fixed factory order PN for Ovation HART AO module; suffix G01 denotes fixed hardware revision, corresponding alternative revision is 5X00226G04 without full interchange for hardware version difference.

Technical Specifications

Backplane power: 24VDC supplied via rack backplane, typical power consumption ≤7.2W
Channel configuration: total 8 independent isolated AO channels, standard output range 4–20mA DC, support HART 5/7 protocol digital communication on each loop
Output precision: full-scale accuracy ≤±0.05%, load resistance max 750Ω per single channel
Isolation parameter: channel-to-backplane optoelectronic isolation 1500VAC, inter-channel group isolation for anti-surge interference
Ambient rating: operating -20℃~+60℃, storage -40℃~+85℃, 5%~95%RH non-condensing, conform IEC60068 industrial anti-vibration standard
Dimension & Weight: standard Ovation single slot 155×84×218mm, net weight≈0.40kg
Protection design: per-channel short-circuit, overvoltage and reverse wiring protection.

Interface & Communication Layout

Rear golden finger: Ovation proprietary backplane bus, high-speed receive control instruction from rack main processor
Front docking port: lock connector matched exclusive AO terminal base for valve positioner, frequency converter field wiring
Front panel LED: POWER, RUN, FAULT + grouped channel indicator lamps, display module power, operating status, hardware fault and each channel output state
Onboard HART circuit: independent HART modem for each channel, realize remote parameter reading/writing of HART smart instruments via DCS system.

Core Functions

Convert DCS internal digital control value into standard 4–20mA analog signal to drive field regulating valves, actuators and frequency converters for process closed-loop PID regulation
Built-in full HART communication, upload smart device model, fault code, calibration data to Ovation operator station without extra handheld HART communicator on-site
Full online hot swap: replace module online without cabinet power cut, residual normal channels keep continuous output control
Complete self-diagnosis: detect output loop open circuit, short circuit and overloading automatically, fault information uploaded to DCS historical alarm log in real time.

Application Scenarios

Boiler fuel control valve, feedwater regulating valve analog output control for coal-fired power plant; turbine lubricating oil pressure regulating actuator drive; desulfurization absorption tower liquid level adjusting valve output; petrochemical reactor feed flow control cabinet spare replacement.

Operation & Maintenance Notes

Only install into standard Ovation single I/O slot and matching original terminal base, confirm slot coding before plug-in to avoid backplane burnout
Field 4–20mA HART signal cable separated from high-current AC power wire during wiring to avoid EMI causing output drift
Complete HART instrument address configuration via Ovation engineering software after wiring and power-on
Periodically check front fault indicator and DCS alarm log for loop abnormal troubleshooting, fasten terminal screws regularly to eliminate poor contact.


Get a Quote